42 42  To change the battery protection parameters from low voltage on the cells, select the menu "Protections → Undervoltage protection":
43 43  
44 -[[Caption>>image:1732212212350-294.png||data-xwiki-image-style-alignment="center" height="207" width="359"]]
44 +[[Undervoltage protection settings>>image:1732212212350-294.png||data-xwiki-image-style-alignment="center" height="207" width="359"]]
45 +
46 + In this section:
47 +
48 +* Enable – a flag to enable the protection;
49 +* Minimum cell voltage, V;
50 +* Tolerant cell voltage, V;
51 +* Delay before setting the error, second;
52 +* Delay before clearing the error, second;
53 +* Lock the error until the device is reset.
54 +
55 +As a result of the operation of battery protection from low voltage, the "Undervoltage" error is generated.
56 +
57 +Error generation conditions:
58 +
59 +* the minimum voltage among all cells of the battery is less than the “Minimum cell voltage” value for the “Delay before setting the error” time.
60 +
61 +Conditions for removing the error:
62 +
63 +* the minimum voltage among all cells of the battery is greater than the “Tolerant cell voltage” value for the “Delay before clearing the error” time.
64 +
65 +(% class="box infomessage" %)
66 +(((
67 +If there is the "Undervoltage" error, the discharging relay opens.
68 +)))
69 +