Changes for page 3.5 Battery control
Last modified by Admin on 2025/03/10 12:50
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -202,18 +202,3 @@ 202 202 * Enable – a flag to enable the main contactor control; 203 203 * Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, second; 204 204 * Keep the contactor open until the device is reset – a flag for keeping the main contactor opened until the system be reset. 205 - 206 -== 3.5.6 Power down control == 207 - 208 -The BMS Main 2.x can command the BMS Power Control board to shut down the battery system if the battery voltage is low or the battery is idle for a long time. The BMS Main 2.x interacts with the BMS Power Control using the “Power down request” and the “Acknowledgement of power down” discrete signals. 209 - 210 -Shutting down the battery system is performed according to the following conditions: 211 - 212 -* the battery voltage is below the minimum level; 213 -* the “Charger connected” signal is cleared for 60 seconds. 214 - 215 -The BMS Main 2.x also shuts down the battery if it stays in the “Charging OFF”, “Discharging OFF”, “Relaxed (after charging)” or “Relaxed (after discharging)” for the set time. 216 - 217 -To change the parameters of the power down control, select the menu "Cells → Power down control": 218 - 219 -[[Power down >>image:1732211675123-235.png||data-xwiki-image-style-alignment="center" height="198" width="402"]]