... ... @@ -202,3 +202,20 @@
202 202  * Enable – a flag to enable the main contactor control;
203 203  * Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, second;
204 204  * Keep the contactor open until the device is reset – a flag for keeping the main contactor opened until the system be reset.
205 +
206 +== 3.5.6 Power down control ==
207 +
208 +The BMS Main 2.x can command the BMS Power Control board to shut down the battery system if the battery voltage is low or the battery is idle for a long time. The BMS Main 2.x interacts with the BMS Power Control using the “Power down request” and the “Acknowledgement of power down” discrete signals.
209 +
210 +Shutting down the battery system is performed according to the following conditions:
211 +
212 +* the battery voltage is below the minimum level;
213 +* the “Charger connected” signal is cleared for 60 seconds.
214 +
215 +The BMS Main 2.x also shuts down the battery if it stays in the “Charging OFF”, “Discharging OFF”, “Relaxed (after charging)” or “Relaxed (after discharging)” for the set time.
216 +
217 +To change the parameters of the power down control, select the menu "Cells → Power down control":
218 +
219 +[[Power down control section>>image:1732211675123-235.png||data-xwiki-image-style-alignment="center" height="198" width="402"]]
220 +
221 +
1732211675123-235.png