Changes for page 3.5 Battery control

Last modified by Admin on 2025/03/10 12:50

From version 6.1
edited by Admin
on 2024/11/21 17:12
Change comment: Uploaded new attachment "1732209137414-912.png", version {1}
To version 6.2
edited by Admin
on 2024/11/21 17:12
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -169,3 +169,29 @@
169 169  In this section:
170 170  
171 171  * Enable – a flag to enable Charging/Discharging contactor controller.
172 +
173 +== 3.5.5 Main contactor ==
174 +
175 +The BMS Main 2.x has a relay to control the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in a case of sealing of the charging or discharging contactor.
176 +
177 +The main contactor closes if there are no errors from the list below:
178 +
179 +* Overcurrent;
180 +* Undervoltage;
181 +* Overvoltage;
182 +* High temperature (charging);
183 +* High temperature (discharging);
184 +* Unallowable charging;
185 +* Critical error.
186 +
187 +The main contactor opens if the charging and discharging relays are opened and any of the following conditions is met:
188 +
189 +* charging or discharging current is detected during a set time;
190 +* voltage of any cell is lower than the minimum cell voltage configured in the section "Protections → Undervoltage protection" during a set time;
191 +* voltage of any cell is greater than the maximum cell voltage configured in the section "Protections → Overvoltage protection" during a set time;
192 +* temperature of any cell is greater than the maximum cell temperature configured in the section "Protections → High temperature protection" during a set time;
193 +* Critical error stays on during a set time.
194 +
195 +To change the parameters of the main contactor, select the menu "Cells → Main contactor":
196 +
197 +[[Caption>>image:1732209137414-912.png||data-xwiki-image-style-alignment="center" height="132" width="352"]]