Changes for page 3.5 Battery control
Last modified by Admin on 2025/03/10 12:50
Summary
-
Page properties (1 modified, 0 added, 0 removed)
-
Attachments (0 modified, 2 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -169,3 +169,51 @@ 169 169 In this section: 170 170 171 171 * Enable – a flag to enable Charging/Discharging contactor controller. 172 + 173 +== 3.5.5 Main contactor == 174 + 175 +The BMS Main 2.x has a relay to control the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in a case of sealing of the charging or discharging contactor. 176 + 177 +The main contactor closes if there are no errors from the list below: 178 + 179 +* Overcurrent; 180 +* Undervoltage; 181 +* Overvoltage; 182 +* High temperature (charging); 183 +* High temperature (discharging); 184 +* Unallowable charging; 185 +* Critical error. 186 + 187 +The main contactor opens if the charging and discharging relays are opened and any of the following conditions is met: 188 + 189 +* charging or discharging current is detected during a set time; 190 +* voltage of any cell is lower than the minimum cell voltage configured in the section "Protections → Undervoltage protection" during a set time; 191 +* voltage of any cell is greater than the maximum cell voltage configured in the section "Protections → Overvoltage protection" during a set time; 192 +* temperature of any cell is greater than the maximum cell temperature configured in the section "Protections → High temperature protection" during a set time; 193 +* Critical error stays on during a set time. 194 + 195 +To change the parameters of the main contactor, select the menu "Cells → Main contactor": 196 + 197 +[[Main contactor settings>>image:1732209137414-912.png||data-xwiki-image-style-alignment="center" height="132" width="352"]] 198 + 199 + 200 +In this section: 201 + 202 +* Enable – a flag to enable the main contactor control; 203 +* Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, second; 204 +* Keep the contactor open until the device is reset – a flag for keeping the main contactor opened until the system be reset. 205 + 206 +== 3.5.6 Power down control == 207 + 208 +The BMS Main 2.x can command the BMS Power Control board to shut down the battery system if the battery voltage is low or the battery is idle for a long time. The BMS Main 2.x interacts with the BMS Power Control using the “Power down request” and the “Acknowledgement of power down” discrete signals. 209 + 210 +Shutting down the battery system is performed according to the following conditions: 211 + 212 +* the battery voltage is below the minimum level; 213 +* the “Charger connected” signal is cleared for 60 seconds. 214 + 215 +The BMS Main 2.x also shuts down the battery if it stays in the “Charging OFF”, “Discharging OFF”, “Relaxed (after charging)” or “Relaxed (after discharging)” for the set time. 216 + 217 +To change the parameters of the power down control, select the menu "Cells → Power down control": 218 + 219 +[[Power down >>image:1732211675123-235.png||data-xwiki-image-style-alignment="center" height="198" width="402"]]
- 1732209137414-912.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +9.7 KB - Content
- 1732211675123-235.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +13.2 KB - Content