134 134  * Use specific delays before stopping discharging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
135 135  * Switch off the discharging relay on errors without delay – a flag to protectively open the discharging relay without delay. In the opposite case, when an error is detected, the discharging relay opens always with the delay “Delay before stopping discharging”.
136 136  * Control the precharging relay – a flag to enable precharge at discharging;
137 -* Delay before current measurement – a delay before first current measurement after closing precharge, millisecond;
137 +* Delay before current measurement, millisecond;
138 138  * Precharge time – a duration of closing the precharge relay before closing the discharging relay, millisecond;
139 139  * Precharge current threshold to start discharging – a minimum current value to finish precharging and start discharge, A;
140 140  * Keep the precharging relay closed until precharge is finished – a flag to ignore the Precharge time and wait precharging to finish before open precharge relay;