Changes for page 3.5 Battery control
Last modified by Admin on 2025/03/10 12:50
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -62,7 +62,7 @@ 62 62 63 63 (% class="box infomessage" %) 64 64 ((( 65 -**Note:** The allow chargingrelay closes under two independent conditions:65 +**Note:** The "Allow charging" signal appears under two independent conditions: 66 66 1) the voltage on the cells reaches the Voltage to reset the “Ready to charge" level and 67 67 2) the "Delay before recharging" time has passed since the opening of the allow charging relay. 68 68 ))) ... ... @@ -128,5 +128,6 @@ 128 128 * Switch off the discharging relay on errors without delay – a flag to protectively open the discharging relay without delay. In the opposite case, when an error is detected, the discharging relay opens always with the delay “Delay before stopping discharging”. 129 129 * Precharge time – a duration of closing the precharge relay before closing the discharging relay, millisecond; 130 130 * Voltage to clear the “Ready to discharge” signal – a threshold voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared; 131 +* Voltage to reset the “Ready to discharge” signal – a tolerant voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set. 131 131 132 - Voltageto reset the “Ready to discharge” signal – a tolerant voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;133 +3.5.3