Changes for page 3.5 Battery control
Last modified by Admin on 2025/06/11 15:20
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -137,7 +137,9 @@ 137 137 * Delay before current measurement, millisecond; 138 138 * Precharge time – a duration of closing the precharge relay before closing the discharging relay, millisecond; 139 139 * Precharge current threshold to start discharging – a minimum current value to finish precharging and start discharge, A; 140 -* Keep the precharging relay closed until precharge is finished 140 +* Keep the precharging relay closed until precharge is finished – a flag to ignore the Precharge time and wait precharging to finish before open precharge relay; 141 +* Delay before clearing the "Precharge error", second – 142 +* Lock the "Precharge error" until the device is reset 141 141 * Voltage to clear the “Ready to discharge” signal – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared; 142 142 * Voltage to reset the “Ready to discharge” signal – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set; 143 143 * Treat negative currents as zero currents for generating the "Ready to charge" signal – a flag to disable voltage correction for "Ready to charge" signal at discharging current;