... ... @@ -137,7 +137,9 @@
137 137  * Delay before current measurement, millisecond;
138 138  * Precharge time – a duration of closing the precharge relay before closing the discharging relay, millisecond;
139 139  * Precharge current threshold to start discharging – a minimum current value to finish precharging and start discharge, A;
140 -* Keep the precharging relay closed until precharge is finished
140 +* Keep the precharging relay closed until precharge is finished – a flag to ignore the Precharge time and wait precharging to finish before open precharge relay;
141 +* Delay before clearing the "Precharge error", second – a
142 +* Lock the "Precharge error" until the device is reset
141 141  * Voltage to clear the “Ready to discharge” signal – a threshold U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
142 142  * Voltage to reset the “Ready to discharge” signal – a tolerant U,,ocv,, (corrected due to current and cell resistance) voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
143 143  * Treat negative currents as zero currents for generating the "Ready to charge" signal – a flag to disable voltage correction for "Ready to charge" signal at discharging current;