... ... @@ -1,1 +1,1 @@
1 -Battery management systems.BMS Main 2\.1.3\. Configuration.WebHome
1 +drafts.BMS Main 2\.1.3\. Configuration.WebHome
Content
... ... @@ -1,11 +1,5 @@
1 -(% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 -= Configuration =
1 +== 3.5.1 Charge control ==
3 3  
4 -(% data-numbered-headings-start="5" style="--numbered-headings-start: 4;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
5 -== Battery control ==
6 -
7 -=== Charge control ===
8 -
9 9  There are two relays that serve charging the battery: a charging relay and an allow charging relay. With the help of the allow charging relay, the BMS commands the charger to start or stop charging.
10 10  
11 11  The board supports two charge control algorithms:
... ... @@ -73,7 +73,7 @@
73 73  2) the "Delay before recharging" time has passed since the opening of the allow charging relay.
74 74  )))
75 75  
76 -=== Discharge control ===
70 +== 3.5.2 Discharge control ==
77 77  
78 78  The board has a discharging relay to connect battery to the load.
79 79  
... ... @@ -132,11 +132,10 @@
132 132  * Use specific delays before stopping discharging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
133 133  * Switch off the discharging relay on errors without delay – a flag to protectively open the discharging relay without delay. In the opposite case, when an error is detected, the discharging relay opens always with the delay “Delay before stopping discharging”.
134 134  * Precharge time – a duration of closing the precharge relay before closing the discharging relay, millisecond;
135 -* Precharge current threshold to start discharging – a minimum current value to finish precharging and start discharge, A;
136 136  * Voltage to clear the “Ready to discharge” signal – a threshold voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
137 137  * Voltage to reset the “Ready to discharge” signal – a tolerant voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set.
138 138  
139 -=== Discharging (AUX) control ===
132 +== 3.5.3 Discharging (AUX) control ==
140 140  
141 141  The BMS Main 2.x board can control the power supply of external equipment using the auxiliary (AUX) discharging relay. An example of external equipment can be an inverter that converts DC to AC to power a service laptop and other devices.
142 142  
... ... @@ -163,7 +163,7 @@
163 163  ** Maximum voltage – maximum battery voltage, V;
164 164  * Switch off the discharging (AUX) relay on errors – the auxiliary (AUX) discharging relay opens if the following errors occur: Undervoltage, Overcurrent, High temperature (discharging), Short circuit, Critical error.
165 165  
166 -=== Charging/Discharging control ===
159 +== 3.5.4 Charging/Discharging control ==
167 167  
168 168   BMS Main 2.x allows to control charging/discharging contactor that combines algorithms of charging and discharging contactor. It behaves as charging contactor when «Charge request» or «Charger connected» are set, otherwise – as discharging contactor.
169 169  
... ... @@ -175,7 +175,7 @@
175 175  
176 176  * Enable – a flag to enable Charging/Discharging contactor controller.
177 177  
178 -=== Main contactor ===
171 +== 3.5.5 Main contactor ==
179 179  
180 180  The BMS Main 2.x has a relay to control the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in a case of sealing of the charging or discharging contactor.
181 181  
... ... @@ -207,7 +207,7 @@
207 207  * Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, second;
208 208  * Keep the contactor open until the device is reset – a flag for keeping the main contactor opened until the system be reset.
209 209  
210 -=== Power down control ===
203 +== 3.5.6 Power down control ==
211 211  
212 212  The BMS Main 2.x can command the BMS Power Control board to shut down the battery system if the battery voltage is low or the battery is idle for a long time. The BMS Main 2.x interacts with the BMS Power Control using the “Power down request” and the “Acknowledgement of power down” discrete signals.
213 213