Changes for page 3.4 Battery parameters
Last modified by Admin on 2025/04/09 12:04
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -235,6 +235,19 @@ 235 235 236 236 [[Charge current map settings>>image:1732208033738-498.png||data-xwiki-image-style-alignment="center" height="655" width="453"]] 237 237 238 +In this section: 239 + 240 +* Enable – a flag to start calculation of the charge current limit; 241 +* Maximum charging current – a maximum allowable value of the charge current (under normal conditions): 242 +* Limit charging current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on SOC and temperature; 243 +* Limit charging current by the contactor temperature – a flag to enable correction of maximum allowable charging current Kcc depending on the contactor temperature; 244 +* Limit charging current by the maximum cell voltage - a flag to enable correction of maximum allowable charging current Kcv depending on maximum cell voltage; 245 +* Limit charging current by the maximum cell temperature - a flag to enable correction of maximum allowable charging current Kc depending on maximum cell voltage. 246 + 247 +Value of the charge current limit at given SOC, temperature, contactors temperature and maximum cell voltage is calculated as follows: 248 + 249 +Charging current limit = Maximum charging current × Kcs × Kcc × Kcv 250 + 238 238 == 3.4.8 Discharge current map == 239 239 240 240 The BMS Main 2.x board calculates maximum allowable discharge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage.