Changes for page 3.4 Battery parameters
Last modified by Admin on 2025/04/09 12:04
Summary
-
Page properties (1 modified, 0 added, 0 removed)
-
Attachments (0 modified, 1 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -227,10 +227,35 @@ 227 227 228 228 == 3.4.7 Charge current map == 229 229 230 +The BMS Main 2.x board calculates maximum allowable charge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage. 230 230 232 +Calculated currents values are sending to chargers or intellectual loads over the CAN bus. 233 + 234 +To configure parameters for determining the charge current limit, select the menu "Cells → Charge current map": 235 + 236 +[[Charge current map settings>>image:1732208033738-498.png||data-xwiki-image-style-alignment="center" height="655" width="453"]] 237 + 238 +In this section: 239 + 240 +* Enable – a flag to start calculation of the charge current limit; 241 +* Maximum charging current – a maximum allowable value of the charge current (under normal conditions): 242 +* Limit charging current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on SOC and temperature; 243 +* Limit charging current by the contactor temperature – a flag to enable correction of maximum allowable charging current Kcc depending on the contactor temperature; 244 +* Limit charging current by the maximum cell voltage - a flag to enable correction of maximum allowable charging current Kcv depending on maximum cell voltage; 245 +* Limit charging current by the maximum cell temperature - a flag to enable correction of maximum allowable charging current Kc depending on maximum cell voltage. 246 + 247 +Value of the charge current limit at given SOC, temperature, contactors temperature and maximum cell voltage is calculated as follows: 248 + 249 +Charging current limit = Maximum charging current × Kcs × Kcc × Kcv 250 + 231 231 == 3.4.8 Discharge current map == 232 232 253 +The BMS Main 2.x board calculates maximum allowable discharge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage. 233 233 255 +Calculated currents values are sending to chargers or intellectual loads over the CAN bus. 256 + 257 +To configure parameters for determining the charge current limit, select the menu "Cells → Charge current map": 258 + 234 234 == 3.4.9 SOC correction == 235 235 236 236 The BMS Main 2.x board can recalculate the battery SOC after long-term storage or after long-term working in the case when the battery was not charged fully or discharged totally. Recalculation is done based on the tabular dependency Uocv = Uocv (SOC, t) (see section Calculating the state of charge (SOC)).
- 1732208218667-968.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +41.9 KB - Content