... ... @@ -1,1 +1,1 @@ 1 -drafts.bms-main-2 -1.configuration.WebHome1 +drafts.bms-main-2.configuration.WebHome - Content
-
... ... @@ -225,10 +225,55 @@ 225 225 * OCV – cell voltage Uocv, V; 226 226 * Resistance – cell resistance, Ohm. 227 227 228 +== 3.4.7 Charge current map == 228 228 230 +The BMS Main 2.x board calculates maximum allowable charge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage. 229 229 230 - == SOC correction==232 +Calculated currents values are sending to chargers or intellectual loads over the CAN bus. 231 231 234 +To configure parameters for determining the charge current limit, select the menu "Cells → Charge current map": 235 + 236 +[[Charge current map settings>>image:1732208033738-498.png||data-xwiki-image-style-alignment="center" height="655" width="453"]] 237 + 238 +In this section: 239 + 240 +* Enable – a flag to start calculation of the charge current limit; 241 +* Maximum charging current – a maximum allowable value of the charge current (under normal conditions): 242 +* Limit charging current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on SOC and temperature; 243 +* Limit charging current by the contactor temperature – a flag to enable correction of maximum allowable charging current Kcc depending on the contactor temperature; 244 +* Limit charging current by the maximum cell voltage – a flag to enable correction of maximum allowable charging current Kcv depending on maximum cell voltage; 245 +* Limit charging current by the maximum cell temperature – a flag to enable correction of maximum allowable charging current Kct depending on maximum cell temperature. 246 + 247 +Value of the charge current limit at given SOC, temperature, contactors temperature and maximum cell voltage is calculated as follows: 248 + 249 +Charging current limit = Maximum charging current × Kcs × Kcc × Kcv × Kct. 250 + 251 +== 3.4.8 Discharge current map == 252 + 253 +The BMS Main 2.x board calculates maximum allowable discharge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage. 254 + 255 +Calculated currents values are sending to chargers or intellectual loads over the CAN bus. 256 + 257 +To configure parameters for determining the charge current limit, select the menu "Cells → Charge current map": 258 + 259 +[[Discharge current map settings>>image:1732208218667-968.png||data-xwiki-image-style-alignment="center" height="631" width="434"]] 260 + 261 +In this section: 262 + 263 +* Enable – a flag to start calculation of the discharge current limit; 264 +* Maximum discharging current – a maximum allowable value of the discharge current (under normal conditions): 265 +* Current factor – the dependence of the correction factor on SOC and the battery temperature – Kdischarge=Kdischarge (SOC, t°C). 266 +* Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current Kds depending on SOC and temperature; 267 +* Limit discharging current by the contactor temperature – a flag to enable correction of maximum allowable discharging current Kdc depending on the contactor temperature; 268 +* Limit discharging current by the maximum cell voltage - a flag to enable correction of maximum allowable discharging current Kdv depending on maximum cell voltage; 269 +* Limit discharging current by the maximum cell temperature - a flag to enable correction of maximum allowable discharging current Kdt depending on maximum cell temperature . 270 + 271 +Value of the discharge current limit at given SOC, temperature, contactors temperature and maximum cell voltage is calculated as follows: 272 + 273 +Discharging current limit = Maximum discharging current × Kds × Kdc × Kdv × Kdt. 274 + 275 +== 3.4.9 SOC correction == 276 + 232 232 The BMS Main 2.x board can recalculate the battery SOC after long-term storage or after long-term working in the case when the battery was not charged fully or discharged totally. Recalculation is done based on the tabular dependency Uocv = Uocv (SOC, t) (see section Calculating the state of charge (SOC)). 233 233 234 234 To configure parameters for periodically correcting the battery state of charge, select the menu "Cells → SOC correction":
- 1732208033738-498.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +42.7 KB - Content
- 1732208218667-968.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +41.9 KB - Content