Changes for page 3.4 Battery parameters

Last modified by Admin on 2026/04/24 10:30

From version 35.5
edited by Admin
on 2026/04/24 10:23
Change comment: Renamed back-links.
To version 34.1
edited by Admin
on 2025/02/20 14:24
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -Battery management systems.EOL devices.BMS Main 2\.1.3\. Configuration.WebHome
1 +Battery management systems.BMS Main 2\.1.3\. Configuration.WebHome
Content
... ... @@ -136,7 +136,7 @@
136 136  * the voltage on the cell is less than the balancing stop voltage;
137 137  * the difference between the voltage on the cell and the minimum voltage among the battery cells is less than the balancing stop threshold.
138 138  
139 -If the BMS Logic board overheats, then the balancing of the cells connected to this board will not be performed (see [[Logic high temperature protection>>doc:Battery management systems.EOL devices.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HLogichightemperatureprotection"]]).
139 +If the BMS Logic board overheats, then the balancing of the cells connected to this board will not be performed (see [[Logic high temperature protection>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HLogichightemperatureprotection"]]).
140 140  
141 141  The BMS Main 2.1 can enable the cell balancing by the external “Balancing request” signal. Balancing process will be started to cells which the voltage is higher than the balancing start voltage and the difference between the cell voltage and the minimum voltage among all the cells is greater than the balancing stop threshold.
142 142  
... ... @@ -271,7 +271,7 @@
271 271  * Maximum charging current – a maximum allowable value of the charge current (under normal conditions):
272 272  * Limit charging current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on the __maximum cell SOC__ and temperature;
273 273  * Limit charging current by the contactor temperature – a flag to enable correction of maximum allowable charging current Kcc depending on the contactor temperature;
274 -* Limit charging current by the maximum cell voltage – a flag to enable correction of maximum allowable charging current Kcv depending on __the maximum cell U,,ocv,, voltage__ (corrected due to current and cell resistance);
274 +* Limit charging current by the maximum cell voltage – a flag to enable correction of maximum allowable charging current Kcv depending on __the maximum cell voltage__;
275 275  * Limit charging current by the maximum cell temperature – a flag to enable correction of maximum allowable charging current Kct depending on cell temperature.
276 276  
277 277  Value of the charge current limit at given SOC, temperature, contactors temperature and maximum cell voltage is calculated as follows:
... ... @@ -295,7 +295,7 @@
295 295  * Current factor – the dependence of the correction factor on SOC and the battery temperature – Kdischarge=Kdischarge (SOC, t°C).
296 296  * Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current Kds depending __on the minimum cell SOC__ and temperature;
297 297  * Limit discharging current by the contactor temperature – a flag to enable correction of maximum allowable discharging current Kdc depending on the contactor temperature;
298 -* Limit discharging current by the maximum cell voltage - a flag to enable correction of maximum allowable discharging current Kdv depending __the minimum cell U,,ocv,, voltage__ (corrected due to current and cell resistance);
298 +* Limit discharging current by the maximum cell voltage - a flag to enable correction of maximum allowable discharging current Kdv depending __on the minimum cell voltage__;
299 299  * Limit discharging current by the maximum cell temperature - a flag to enable correction of maximum allowable discharging current Kdt depending on cell temperature .
300 300  
301 301  Value of the discharge current limit at given SOC, temperature, contactors temperature and maximum cell voltage is calculated as follows: