... ... @@ -1,1 +1,1 @@
1 -Battery management systems.BMS Main 2\.1.3\. Configuration.WebHome
1 +Battery management systems.EOL devices.BMS Main 2\.1.3\. Configuration.WebHome
Content
... ... @@ -88,7 +88,7 @@
88 88  provided that
89 89  
90 90  {{formula fontSize="SMALL"}}
91 -| I_{stable2}-I_{stable1} | > 0.2 × Qmax
91 +| I_{stable2}-I_{stable1} | > 0.2 × Q_{max}
92 92  {{/formula}}
93 93  
94 94  where Q,,max,, is the maximum cell capacity; U,,2,, is the voltage on the cell at the moment when the stabilized current I,,stable2,, is flowing through it; U,,1,, – the voltage on the cell at the moment when the stabilized current I,,stable1,, flowing through it.
... ... @@ -136,7 +136,7 @@
136 136  * the voltage on the cell is less than the balancing stop voltage;
137 137  * the difference between the voltage on the cell and the minimum voltage among the battery cells is less than the balancing stop threshold.
138 138  
139 -If the BMS Logic board overheats, then the balancing of the cells connected to this board will not be performed (see [[Logic high temperature protection>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HLogichightemperatureprotection"]]).
139 +If the BMS Logic board overheats, then the balancing of the cells connected to this board will not be performed (see [[Logic high temperature protection>>doc:Battery management systems.EOL devices.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HLogichightemperatureprotection"]]).
140 140  
141 141  The BMS Main 2.1 can enable the cell balancing by the external “Balancing request” signal. Balancing process will be started to cells which the voltage is higher than the balancing start voltage and the difference between the cell voltage and the minimum voltage among all the cells is greater than the balancing stop threshold.
142 142  
... ... @@ -257,7 +257,7 @@
257 257  
258 258  === Charge current map ===
259 259  
260 -The BMS Main 2.x board calculates maximum allowable charge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage.
260 +The BMS Main 2.x board calculates maximum allowable charge current values in respect to cell SOC and battery temperature, contactor temperature and maximum cell voltage.
261 261  
262 262  Calculated currents values are sending to chargers over the CAN bus.
263 263  
... ... @@ -269,9 +269,9 @@
269 269  
270 270  * Enable – a flag to start calculation of the charge current limit;
271 271  * Maximum charging current – a maximum allowable value of the charge current (under normal conditions):
272 -* Limit charging current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on SOC and temperature;
272 +* Limit charging current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on the __maximum cell SOC__ and temperature;
273 273  * Limit charging current by the contactor temperature – a flag to enable correction of maximum allowable charging current Kcc depending on the contactor temperature;
274 -* Limit charging current by the maximum cell voltage – a flag to enable correction of maximum allowable charging current Kcv depending on maximum cell voltage;
274 +* Limit charging current by the maximum cell voltage – a flag to enable correction of maximum allowable charging current Kcv depending on __the maximum cell U,,ocv,, voltage__ (corrected due to current and cell resistance);
275 275  * Limit charging current by the maximum cell temperature – a flag to enable correction of maximum allowable charging current Kct depending on cell temperature.
276 276  
277 277  Value of the charge current limit at given SOC, temperature, contactors temperature and maximum cell voltage is calculated as follows:
... ... @@ -280,11 +280,11 @@
280 280  
281 281  === Discharge current map ===
282 282  
283 -The BMS Main 2.x board calculates maximum allowable discharge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage.
283 +The BMS Main 2.x board calculates maximum allowable discharge current values in respect to cell SOC and battery temperature, contactor temperature and minimum cell voltage.
284 284  
285 285  Calculated currents values are sending or intellectual loads over the CAN bus.
286 286  
287 -To configure parameters for determining the charge current limit, select the menu "Cells → Charge current map":
287 +To configure parameters for determining the discharge current limit, select the menu "Cells → Charge current map":
288 288  
289 289  [[image:1732208218667-968.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="631" width="434"]]
290 290  
... ... @@ -293,9 +293,9 @@
293 293  * Enable – a flag to start calculation of the discharge current limit;
294 294  * Maximum discharging current – a maximum allowable value of the discharge current (under normal conditions):
295 295  * Current factor – the dependence of the correction factor on SOC and the battery temperature – Kdischarge=Kdischarge (SOC, t°C).
296 -* Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current Kds depending on SOC and temperature;
296 +* Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current Kds depending __on the minimum cell SOC__ and temperature;
297 297  * Limit discharging current by the contactor temperature – a flag to enable correction of maximum allowable discharging current Kdc depending on the contactor temperature;
298 -* Limit discharging current by the maximum cell voltage - a flag to enable correction of maximum allowable discharging current Kdv depending on maximum cell voltage;
298 +* Limit discharging current by the maximum cell voltage - a flag to enable correction of maximum allowable discharging current Kdv depending __the minimum cell U,,ocv,, voltage__ (corrected due to current and cell resistance);
299 299  * Limit discharging current by the maximum cell temperature - a flag to enable correction of maximum allowable discharging current Kdt depending on cell temperature .
300 300  