Changes for page 3.4 Battery parameters

Last modified by Admin on 2025/04/09 12:04

From version 31.2
edited by Admin
on 2025/02/20 11:09
Change comment: There is no comment for this version
To version 34.1
edited by Admin
on 2025/02/20 14:24
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -73,19 +73,25 @@
73 73  
74 74  Calculation of the resistance of cells is carried out in two ways. The first method is used when the battery passes from a relaxation state to a charge or discharge state, wherein the cell resistance value
75 75  
76 -R = (U-Uocv) / Istable,
76 +{{formula fontSize="SMALL" imageType="PNG"}}
77 +R = \frac{U-U_{ocv}}{I_{stable}}
78 +{{/formula}}
77 77  
78 78  where U is the cell voltage measured in the charge or discharge state, V; Uocv is the cell voltage measured in the state of relaxation (before switching to the state of charge or discharge); Istable – stabilized current through the cell in the state of charge or discharge.
79 79  
80 80  The second method is used for a stepwise change in the current through the cell, while the value of the cell resistance:
81 81  
82 -R = (U,,2,,-U,,1,,) / (I,,stable2,,-I,,stable1,,)
84 +{{formula fontSize="SMALL"}}
85 +R = \frac{U_2-U_1}{I_{stable2}-I_{stable1}}
86 +{{/formula}}
83 83  
84 -provided that | I,,stable2,,-I,,stable1,, | > 0.2 × Q,,max,,
88 +provided that
85 85  
86 -(Q,,max,, is the maximum cell capacity),
90 +{{formula fontSize="SMALL"}}
91 +| I_{stable2}-I_{stable1} | > 0.2 × Q_{max}
92 +{{/formula}}
87 87  
88 -where U,,2,, is the voltage on the cell at the moment when the stabilized current I,,stable2,, is flowing through it; U,,1,, – the voltage on the cell at the moment when the stabilized current I,,stable1,, flowing through it.
94 +where Q,,max,, is the maximum cell capacity; U,,2,, is the voltage on the cell at the moment when the stabilized current I,,stable2,, is flowing through it; U,,1,, – the voltage on the cell at the moment when the stabilized current I,,stable1,, flowing through it.
89 89  
90 90  The stabilized current I,,stable,, = I, if during the stabilization time the instantaneous current I is in the range from 0.95 × I to 1.05 × I.
91 91  
... ... @@ -251,7 +251,7 @@
251 251  
252 252  === Charge current map ===
253 253  
254 -The BMS Main 2.x board calculates maximum allowable charge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage.
260 +The BMS Main 2.x board calculates maximum allowable charge current values in respect to cell SOC and battery temperature, contactor temperature and maximum cell voltage.
255 255  
256 256  Calculated currents values are sending to chargers over the CAN bus.
257 257  
... ... @@ -263,9 +263,9 @@
263 263  
264 264  * Enable – a flag to start calculation of the charge current limit;
265 265  * Maximum charging current – a maximum allowable value of the charge current (under normal conditions):
266 -* Limit charging current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on SOC and temperature;
272 +* Limit charging current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on the __maximum cell SOC__ and temperature;
267 267  * Limit charging current by the contactor temperature – a flag to enable correction of maximum allowable charging current Kcc depending on the contactor temperature;
268 -* Limit charging current by the maximum cell voltage – a flag to enable correction of maximum allowable charging current Kcv depending on maximum cell voltage;
274 +* Limit charging current by the maximum cell voltage – a flag to enable correction of maximum allowable charging current Kcv depending on __the maximum cell voltage__;
269 269  * Limit charging current by the maximum cell temperature – a flag to enable correction of maximum allowable charging current Kct depending on cell temperature.
270 270  
271 271  Value of the charge current limit at given SOC, temperature, contactors temperature and maximum cell voltage is calculated as follows:
... ... @@ -274,11 +274,11 @@
274 274  
275 275  === Discharge current map ===
276 276  
277 -The BMS Main 2.x board calculates maximum allowable discharge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage.
283 +The BMS Main 2.x board calculates maximum allowable discharge current values in respect to cell SOC and battery temperature, contactor temperature and minimum cell voltage.
278 278  
279 279  Calculated currents values are sending or intellectual loads over the CAN bus.
280 280  
281 -To configure parameters for determining the charge current limit, select the menu "Cells → Charge current map":
287 +To configure parameters for determining the discharge current limit, select the menu "Cells → Charge current map":
282 282  
283 283  [[image:1732208218667-968.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="631" width="434"]]
284 284  
... ... @@ -287,9 +287,9 @@
287 287  * Enable – a flag to start calculation of the discharge current limit;
288 288  * Maximum discharging current – a maximum allowable value of the discharge current (under normal conditions):
289 289  * Current factor – the dependence of the correction factor on SOC and the battery temperature – Kdischarge=Kdischarge (SOC, t°C).
290 -* Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current Kds depending on SOC and temperature;
296 +* Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current Kds depending __on the minimum cell SOC__ and temperature;
291 291  * Limit discharging current by the contactor temperature – a flag to enable correction of maximum allowable discharging current Kdc depending on the contactor temperature;
292 -* Limit discharging current by the maximum cell voltage - a flag to enable correction of maximum allowable discharging current Kdv depending on maximum cell voltage;
298 +* Limit discharging current by the maximum cell voltage - a flag to enable correction of maximum allowable discharging current Kdv depending __on the minimum cell voltage__;
293 293  * Limit discharging current by the maximum cell temperature - a flag to enable correction of maximum allowable discharging current Kdt depending on cell temperature .
294 294  
295 295  Value of the discharge current limit at given SOC, temperature, contactors temperature and maximum cell voltage is calculated as follows: