Changes for page 3.4 Battery parameters
Last modified by Admin on 2025/04/09 12:04
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -48,6 +48,8 @@ 48 48 * Final SOC – a method of calculating the battery SOC: 49 49 ** Minimum cell SOC – the battery SOC is assumed to be equal to the minimum SOC of cells; 50 50 ** Average cell SOC – the battery SOC is assumed to be equal to the average SOC of cells; 51 +** Min-Max SOC – the battery SOC is calculated based on the minimum and maximum SOC of the cells. Final SOC will be a) 100% if any cell has 100% SOC, b) 0% if any cell has 0% SOC; 52 +** Max-Min SOC – the battery SOC is calculated based on the minimum and maximum SOC of the cells. Final SOC will be a) 100% if all cells have 100% SOC, b) 0% if all cells have 0% SOC; 51 51 * Scale the final SOC – flag to scale the battery SOC by the following values; 52 52 * Internal SOC corresponding to 0% – battery SOC that sets to be 0%; 53 53 * Internal SOC corresponding to 100% – battery SOC that sets to be 100%.