Changes for page 3.4 Battery parameters

Last modified by Admin on 2025/04/09 12:04

From version 30.1
edited by Admin
on 2025/02/17 17:30
Change comment: There is no comment for this version
To version 23.1
edited by Admin
on 2024/12/02 15:24
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -Battery management systems.BMS Main 2\.1.3\. Configuration.WebHome
1 +drafts.BMS Main 2\.1.3\. Configuration.WebHome
Content
... ... @@ -1,11 +1,5 @@
1 -(% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 -= Configuration =
1 +== 3.4.1 Cell defaults ==
3 3  
4 -(% data-numbered-headings-start="4" style="--numbered-headings-start: 3;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
5 -== Battery parameters ==
6 -
7 -=== Cell defaults ===
8 -
9 9  To change the default cell settings, select the menu "Cells → Cell defaults":
10 10  
11 11  [[image:1732205873121-893.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="281" width="374"]]
... ... @@ -26,7 +26,7 @@
26 26  
27 27  The “Reset cell parameters” command is used for starting-up and adjustment of battery.
28 28  
29 -=== SOC estimation ===
23 +== 3.4.2 SOC estimation ==
30 30  
31 31  The BMS Main 2.x board calculates the state of charge of the battery (SOC) using two algorithms:
32 32  
... ... @@ -51,7 +51,7 @@
51 51  * Scale the final SOC – flag to scale the battery SOC by the following values;
52 52  * Internal SOC corresponding to 0% – battery SOC that sets to be 0%;
53 53  * Internal SOC corresponding to 100% – battery SOC that sets to be 100%.
54 -* Uocv = Uocv(SOC, t °C) – the dependence of the cell open circuit voltage Uocv on SOC and the cell temperature (selected for specific batteries, can be established experimentally – see [[Cell analysis>>doc:||anchor="HCellanalysis"]]);
48 +* Uocv = Uocv(SOC, t °C) – the dependence of the cell open circuit voltage Uocv on SOC and the cell temperature (selected for specific batteries, can be established experimentally – see [[3.4.6 Cell analysis>>doc:||anchor="H3.4.6Cellanalysis"]]);
55 55  * Linear zone – linear zone of dependence Uocv = Uocv(SOC, t °C):
56 56  ** Uocv ,,[point 1],, – starting point of the linear zone;
57 57  ** Uocv ,,[point 2],, – end point of the linear zone;
... ... @@ -67,7 +67,7 @@
67 67  
68 68  The SOC calculation algorithm “Current and voltage (enhanced)” differs from the simplified algorithm by online correction of effective capacitance. When using this algorithm, it is necessary to fine tune the tabular dependence Uocv = Uocv (SOC, t °C).
69 69  
70 -=== Cell resistance estimation ===
64 +== 3.4.3 Cell resistance estimation ==
71 71  
72 72  Calculation of the resistance of cells is carried out in two ways. The first method is used when the battery passes from a relaxation state to a charge or discharge state, wherein the cell resistance value
73 73  
... ... @@ -97,9 +97,9 @@
97 97  * Minimum SOC – minimum cell SOC value for resistance calculation;
98 98  * Maximum SOC – maximum cell SOC value for resistance calculation.
99 99  
100 -The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance/2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[Cell defaults>>doc:||anchor="HCelldefaults"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
94 +The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance/2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[3.4.1 Cell defaults>>doc:||anchor="3.4.1 Cell defaults"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
101 101  
102 -=== Cell balancing ===
96 +== 3.4.4 Cell balancing ==
103 103  
104 104  The BMS Main 2.x supports two cell balancing algorithms:
105 105  
... ... @@ -121,20 +121,11 @@
121 121  * the voltage on the cell is higher than the starting voltage of the balancing;
122 122  * the difference between the cell voltage and the minimum voltage among the cells of the battery is greater than the balancing threshold.
123 123  
124 -A balancing resistor is disconnected from the cell if any of the following conditions are met:
118 +If the BMS Logic board overheats, then the balancing of the cells connected to this board will not be performed (see [[3.6.18 Logic high temperature protection>>doc:drafts.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="H3.6.18 Logic high temperature protection"]]).
125 125  
126 -* the voltage on the cell is less than the balancing stop voltage;
127 -* the difference between the voltage on the cell and the minimum voltage among the battery cells is less than the balancing stop threshold.
128 -
129 -If the BMS Logic board overheats, then the balancing of the cells connected to this board will not be performed (see [[Logic high temperature protection>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HLogichightemperatureprotection"]]).
130 -
131 -The BMS Main 2.1 can enable the cell balancing by the external “Balancing request” signal. Balancing process will be started to cells which the voltage is higher than the balancing start voltage and the difference between the cell voltage and the minimum voltage among all the cells is greater than the balancing stop threshold.
132 -
133 -BMS Main 2.1 can force a cell balancing, if its voltage is higher than estimated value.
134 -
135 135  To change the cell balancing parameters, select the menu "Cell → Cell balancing":
136 136  
137 -[[image:1739812799920-892.png||alt="1732207485773-804.png" data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="264" width="387"]]
122 +[[image:1732207485773-804.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="264" width="387"]]
138 138  
139 139  In this section:
140 140  
... ... @@ -146,21 +146,16 @@
146 146  ** Charging;
147 147  ** Charging or relaxed;
148 148  ** Always (regardless of battery state);
149 -* Balancing condition:
150 -** Automatic – balancing will be performed automatically if needed conditions are met;
151 -** On balancing request – balancing will start only if a remote request is received. In this case cells will start to balance regardless the "Voltage deviation to start balancing" value;
152 152  * Minimum cell voltage to start balancing, V;
153 -* Deviation to start balancing;
154 -* Deviation to stop balancing;
155 -* Voltage for forced balancing – if cell voltage is above this value, it will start discharging through balancing resistor;
135 +* Balancing threshold, V;
156 156  * Start cell discharging – a command to start forced balancing of all battery cells (used for service purposes);
157 157  * Stop cell discharging – a command to stop forced balancing of all battery cells (used for service purposes).
158 158  
159 -=== Series balancing ===
139 +== 3.4.5 Series balancing ==
160 160  
161 161  The BMS Main 2.x board supports work with two independent (galvanically unrelated) cell series. To monitor the status of two series, two current sensors are used: primary and secondary (AUX). A series of cells must be equivalent: they must have the same number of cells and the same capacity.
162 162  
163 -Since the series of cells can operate at different loads, they must be balanced. For this, the BMS Main 2.x provides two relays: “Balancing series 1” and “Balancing series 2” (see [[Input and output signals>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.3 Input and output signals.WebHome]]), as well as a combined algorithm that considers both the voltage of each series and the charge that these series gave load. “Balancing series 1” and “Balancing series 2” relays are used to connect high-power balancing resistors in parallel with cells series 1 and 2.
143 +Since the series of cells can operate at different loads, they must be balanced. For this, the BMS Main 2.x provides two relays: “Balancing series 1” and “Balancing series 2” (see [[3.3 Input and output signals>>doc:drafts.BMS Main 2\.1.3\. Configuration.3\.3 Input and output signals.WebHome]]), as well as a combined algorithm that considers both the voltage of each series and the charge that these series gave load. “Balancing series 1” and “Balancing series 2” relays are used to connect high-power balancing resistors in parallel with cells series 1 and 2.
164 164  
165 165  When charging the battery, balancing is performed based on the voltage of the series. A balancing resistor is connected to the cell series if:
166 166  
... ... @@ -182,9 +182,9 @@
182 182  * Coulomb threshold – the difference of the charges Qthr, given by a series of cells, above which balancing to be started, Ah;
183 183  * Period – period to reset of charge counters for each series (to avoid accumulation of error), second.
184 184  
185 -=== Cell analysis ===
165 +== 3.4.6 Cell analysis ==
186 186  
187 -Discharge characteristics of the battery – the dependence Uocv = Uocv (DOD) – is used to determine the tabular dependence Uocv = Uocv (SOC, t °C) (see [[SOC estimation>>doc:||anchor="HSOCestimation"]]), which is necessary for calculating the state of charge of the battery.
167 +Discharge characteristics of the battery – the dependence Uocv = Uocv (DOD) – is used to determine the tabular dependence Uocv = Uocv (SOC, t °C) (see [[3.4.2 SOC estimation>>doc:||anchor="3.4.2 SOC estimation"]]), which is necessary for calculating the state of charge of the battery.
188 188  
189 189  The BMS Main 2.x board can automatically determine the battery discharge characteristic.
190 190  
... ... @@ -245,7 +245,7 @@
245 245  * OCV – cell voltage Uocv, V;
246 246  * Resistance – cell resistance, Ohm.
247 247  
248 -=== Charge current map ===
228 +== 3.4.7 Charge current map ==
249 249  
250 250  The BMS Main 2.x board calculates maximum allowable charge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage.
251 251  
... ... @@ -268,7 +268,7 @@
268 268  
269 269  Charging current limit = Maximum charging current × Kcs × Kcc × Kcv × Kct.
270 270  
271 -=== Discharge current map ===
251 +== 3.4.8 Discharge current map ==
272 272  
273 273  The BMS Main 2.x board calculates maximum allowable discharge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage.
274 274  
... ... @@ -292,9 +292,9 @@
292 292  
293 293  Discharging current limit = Maximum discharging current × Kds × Kdc × Kdv × Kdt.
294 294  
295 -=== SOC correction ===
275 +== 3.4.9 SOC correction ==
296 296  
297 -The BMS Main 2.x board can recalculate the battery SOC after long-term storage or after long-term working in the case when the battery was not charged fully or discharged totally. Recalculation is done based on the tabular dependency Uocv = Uocv (SOC, t) (see [[SOC estimation>>doc:||anchor="HSOCestimation"]]).
277 +The BMS Main 2.x board can recalculate the battery SOC after long-term storage or after long-term working in the case when the battery was not charged fully or discharged totally. Recalculation is done based on the tabular dependency Uocv = Uocv (SOC, t) (see [[3.4.2 SOC estimation>>doc:||anchor="3.4.2 SOC estimation"]]).
298 298  
299 299  To configure parameters for periodically correcting the battery state of charge, select the menu "Cells → SOC correction":
300 300  
1739812799920-892.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -28.1 KB
Content