Changes for page 3.4 Battery parameters
Last modified by Admin on 2025/04/09 12:04
Summary
-
Page properties (2 modified, 0 added, 0 removed)
Details
- Page properties
-
- Parent
-
... ... @@ -1,1 +1,1 @@ 1 -drafts. bms-main-2.configuration.WebHome1 +drafts.BMS Main 2\.1.3\. Configuration.WebHome - Content
-
... ... @@ -2,7 +2,7 @@ 2 2 3 3 To change the default cell settings, select the menu "Cells → Cell defaults": 4 4 5 -[[image:1732205873121-893.png||data-xwiki-image-style-alignment="center" height=" 313" width="416"]]5 +[[image:1732205873121-893.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="281" width="374"]] 6 6 7 7 In this section: 8 8 ... ... @@ -31,7 +31,7 @@ 31 31 32 32 To change the parameters of the algorithm for calculating the battery SOC, select the menu "Cells → SOC estimation": 33 33 34 -[[image:1732206031847-819.png||data-xwiki-image-style-alignment="center" height="849" width="356"]] 34 +[[image:1732206031847-819.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="849" width="356"]] 35 35 36 36 In this section: 37 37 ... ... @@ -45,7 +45,7 @@ 45 45 * Scale the final SOC – flag to scale the battery SOC by the following values; 46 46 * Internal SOC corresponding to 0% – battery SOC that sets to be 0%; 47 47 * Internal SOC corresponding to 100% – battery SOC that sets to be 100%. 48 -* Uocv = Uocv(SOC, t °C) – the dependence of the cell open circuit voltage Uocv on SOC and the cell temperature (selected for specific batteries, can be established experimentally – see sectionDetermining the dischargecharacteristic);48 +* Uocv = Uocv(SOC, t °C) – the dependence of the cell open circuit voltage Uocv on SOC and the cell temperature (selected for specific batteries, can be established experimentally – see [[3.4.6 Cell analysis>>doc:||anchor="3.4.6 Cell analysis"]]); 49 49 * Linear zone – linear zone of dependence Uocv = Uocv(SOC, t °C): 50 50 ** Uocv ,,[point 1],, – starting point of the linear zone; 51 51 ** Uocv ,,[point 2],, – end point of the linear zone; ... ... @@ -81,7 +81,7 @@ 81 81 82 82 To change parameters of the algorithm for calculating the cell resistance, select the menu "Cells → Cell resistance estimation": 83 83 84 -[[image:1732207338609-903.png||data-xwiki-image-style-alignment="center" height="187" width="337"]] 84 +[[image:1732207338609-903.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="187" width="337"]] 85 85 86 86 In this section: 87 87 ... ... @@ -91,7 +91,7 @@ 91 91 * Minimum SOC – minimum cell SOC value for resistance calculation; 92 92 * Maximum SOC – maximum cell SOC value for resistance calculation. 93 93 94 -The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance/2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see section Cell defaults). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).94 +The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance/2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[3.4.1 Cell defaults>>doc:||anchor="3.4.1 Cell defaults"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance). 95 95 96 96 == 3.4.4 Cell balancing == 97 97 ... ... @@ -115,11 +115,11 @@ 115 115 * the voltage on the cell is higher than the starting voltage of the balancing; 116 116 * the difference between the cell voltage and the minimum voltage among the cells of the battery is greater than the balancing threshold. 117 117 118 -If the BMS Logic board overheats, then the balancing of the cells connected to this board will not be performed (see Logic high temperature protection). 118 +If the BMS Logic board overheats, then the balancing of the cells connected to this board will not be performed (see [[3.6.18 Logic high temperature protection>>doc:drafts.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="3.6.18 Logic high temperature protection"]]). 119 119 120 120 To change the cell balancing parameters, select the menu "Cell → Cell balancing": 121 121 122 -[[image:1732207485773-804.png||data-xwiki-image-style-alignment="center" height="264" width="387"]] 122 +[[image:1732207485773-804.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="264" width="387"]] 123 123 124 124 In this section: 125 125 ... ... @@ -140,7 +140,7 @@ 140 140 141 141 The BMS Main 2.x board supports work with two independent (galvanically unrelated) cell series. To monitor the status of two series, two current sensors are used: primary and secondary (AUX). A series of cells must be equivalent: they must have the same number of cells and the same capacity. 142 142 143 -Since the series of cells can operate at different loads, they must be balanced. For this, the BMS Main 2.x provides two relays: “Balancing series 1” and “Balancing series 2” (see s ection Configurationofoutputdiscrete signalsand relays), as well as a combined algorithm that considers both the voltage of each series and the charge that these series gave load. “Balancing series 1” and “Balancing series 2” relays are used to connect high-power balancing resistors in parallel with cells series 1 and 2.143 +Since the series of cells can operate at different loads, they must be balanced. For this, the BMS Main 2.x provides two relays: “Balancing series 1” and “Balancing series 2” (see [[3.3 Input and output signals>>doc:drafts.BMS Main 2\.1.3\. Configuration.3\.3 Input and output signals.WebHome]]), as well as a combined algorithm that considers both the voltage of each series and the charge that these series gave load. “Balancing series 1” and “Balancing series 2” relays are used to connect high-power balancing resistors in parallel with cells series 1 and 2. 144 144 145 145 When charging the battery, balancing is performed based on the voltage of the series. A balancing resistor is connected to the cell series if: 146 146 ... ... @@ -151,7 +151,7 @@ 151 151 152 152 To change the series balancing parameters, select the menu "Cell → Series balancing": 153 153 154 -[[image:1732207584941-447.png||data-xwiki-image-style-alignment="center" height="258" width="438"]] 154 +[[image:1732207584941-447.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="258" width="438"]] 155 155 156 156 In this section: 157 157 ... ... @@ -164,7 +164,7 @@ 164 164 165 165 == 3.4.6 Cell analysis == 166 166 167 -Discharge characteristics of the battery – the dependence Uocv = Uocv (DOD) – is used to determine the tabular dependence Uocv = Uocv (SOC, t °C) (see sectionCalculatingtheeofcharge(SOC)), which is necessary for calculating the state of charge of the battery.167 +Discharge characteristics of the battery – the dependence Uocv = Uocv (DOD) – is used to determine the tabular dependence Uocv = Uocv (SOC, t °C) (see [[3.4.2 SOC estimation>>doc:||anchor="3.4.2 SOC estimation"]]), which is necessary for calculating the state of charge of the battery. 168 168 169 169 The BMS Main 2.x board can automatically determine the battery discharge characteristic. 170 170 ... ... @@ -176,7 +176,7 @@ 176 176 177 177 To configure parameters for determining the discharge characteristic of the battery, select the menu "Cells → Cell analysis": 178 178 179 -[[image:1732207696322-587.png||data-xwiki-image-style-alignment="center" height="213" width="258"]] 179 +[[image:1732207696322-587.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="213" width="258"]] 180 180 181 181 In this section: 182 182 ... ... @@ -229,11 +229,11 @@ 229 229 230 230 The BMS Main 2.x board calculates maximum allowable charge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage. 231 231 232 -Calculated currents values are sending to chargers o r intellectual loads over the CAN bus.232 +Calculated currents values are sending to chargers over the CAN bus. 233 233 234 234 To configure parameters for determining the charge current limit, select the menu "Cells → Charge current map": 235 235 236 -[[image:1732208033738-498.png||data-xwiki-image-style-alignment="center" height="655" width="453"]] 236 +[[image:1732208033738-498.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="655" width="453"]] 237 237 238 238 In this section: 239 239 ... ... @@ -242,7 +242,7 @@ 242 242 * Limit charging current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on SOC and temperature; 243 243 * Limit charging current by the contactor temperature – a flag to enable correction of maximum allowable charging current Kcc depending on the contactor temperature; 244 244 * Limit charging current by the maximum cell voltage – a flag to enable correction of maximum allowable charging current Kcv depending on maximum cell voltage; 245 -* Limit charging current by the maximum cell temperature – a flag to enable correction of maximum allowable charging current Kct depending on maximumcell temperature.245 +* Limit charging current by the maximum cell temperature – a flag to enable correction of maximum allowable charging current Kct depending on cell temperature. 246 246 247 247 Value of the charge current limit at given SOC, temperature, contactors temperature and maximum cell voltage is calculated as follows: 248 248 ... ... @@ -252,11 +252,11 @@ 252 252 253 253 The BMS Main 2.x board calculates maximum allowable discharge current values in respect to SOC and battery temperature, contactor temperature and maximum cell voltage. 254 254 255 -Calculated currents values are sending tochargersorintellectual loads over the CAN bus.255 +Calculated currents values are sending or intellectual loads over the CAN bus. 256 256 257 257 To configure parameters for determining the charge current limit, select the menu "Cells → Charge current map": 258 258 259 -[[image:1732208218667-968.png||data-xwiki-image-style-alignment="center" height="631" width="434"]] 259 +[[image:1732208218667-968.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="631" width="434"]] 260 260 261 261 In this section: 262 262 ... ... @@ -266,7 +266,7 @@ 266 266 * Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current Kds depending on SOC and temperature; 267 267 * Limit discharging current by the contactor temperature – a flag to enable correction of maximum allowable discharging current Kdc depending on the contactor temperature; 268 268 * Limit discharging current by the maximum cell voltage - a flag to enable correction of maximum allowable discharging current Kdv depending on maximum cell voltage; 269 -* Limit discharging current by the maximum cell temperature - a flag to enable correction of maximum allowable discharging current Kdt depending on maximumcell temperature .269 +* Limit discharging current by the maximum cell temperature - a flag to enable correction of maximum allowable discharging current Kdt depending on cell temperature . 270 270 271 271 Value of the discharge current limit at given SOC, temperature, contactors temperature and maximum cell voltage is calculated as follows: 272 272 ... ... @@ -274,11 +274,11 @@ 274 274 275 275 == 3.4.9 SOC correction == 276 276 277 -The BMS Main 2.x board can recalculate the battery SOC after long-term storage or after long-term working in the case when the battery was not charged fully or discharged totally. Recalculation is done based on the tabular dependency Uocv = Uocv (SOC, t) (see sectionCalculatingtheeofcharge(SOC)).277 +The BMS Main 2.x board can recalculate the battery SOC after long-term storage or after long-term working in the case when the battery was not charged fully or discharged totally. Recalculation is done based on the tabular dependency Uocv = Uocv (SOC, t) (see [[3.4.2 SOC estimation>>doc:||anchor="3.4.2 SOC estimation"]]). 278 278 279 279 To configure parameters for periodically correcting the battery state of charge, select the menu "Cells → SOC correction": 280 280 281 -[[image:1732206262509-786.png||data-xwiki-image-style-alignment="center" height="291" width="298"]] 281 +[[image:1732206262509-786.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="291" width="298"]] 282 282 283 283 In this section: 284 284 ... ... @@ -285,6 +285,7 @@ 285 285 * Enable – a flag to enable SOC correction; 286 286 * Shutdown period – a time the battery is off, day. If the BMS detects on its startup that it was off during the “Shutdown period” time, the BMS recalculates the battery state of charge base on the tabular dependency Uocv = Uocv (SOC, t); 287 287 * Correction period – a period of correcting the battery SOC, day. If the BMS detects that the last correction was more than the “Correction period” ago, the BMS recalculates the battery state of charge base on the tabular dependency Uocv = Uocv (SOC, t) and tunes it gradually during the “SOC change time”; 288 -* SOC change time – a duration of the linear changing the battery SOC to the value calculated by the correction algorithm, minute. 288 +* SOC change time – a duration of the linear changing the battery SOC to the value calculated by the correction algorithm, minute; 289 +* Ignore the linear zone – a flag to ignore linear zone while calculating SOC correction. 289 289 290 290