6
7 === Input signals ===
8
9 The BMS Main 2.x board has **4 discrete inputs** of the "dry contact" type. For each discrete input, its purpose and the inversion requirement are specified.
10
11 BMS Main 2.x board has **4 analog inputs** for connecting current, temperature and humidity sensors.
12
13 The order of the numbering of the discrete and analog inputs corresponds to the order of the numbering on the board.
14
15 (% id="cke_bm_2415S" style="display:none" %) (%%)To configure the input discrete and analog signals, select the menu "Signals → Input signals":
16
17 [[image:1732201986070-992.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="290" width="272"]]
18
19 (% class="box infomessage" %)
20 (((
21 A list of available **discrete input assignments **is available in [[Input signals>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HInputsignals"]].
22 )))
23
24 If the "Signal from the battery cover" assignment is selected, the discrete input is used to monitor the state of the battery cover (see [[Battery cover protection>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HBatterycoverprotection"]]).
25
26 if the "Charger connected" assignment is selected, the discrete input is involved in the algorithms of charge and discharge control (see [[Charging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HChargingcontrol"]] and [[Discharging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HDischargingcontrol"]]).
27
28 If the "Power up/down request" assignment is selected, the discrete input is involved in the algorithms of opening the charging and discharging relays and sending acknowledgment of power down to the external equipment (see [[Charging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HChargingcontrol"]] and [[Discharging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HDischargingcontrol"]]).
29
30 If the “Inhibit charging” assignment is selected, the discrete input is used to open the charging relay.
31
32 If the “Inhibit discharging” assignment is selected, the discrete input is used to open the discharging relay.
33
34 If the “CH contactor feedback”, “DCH contactor feedback”, “PCH contactor feedback”, “CH/DCH contactor feedback” or “Main contactor feedback” assignment is selected, the discrete input is involved in monitoring the corresponding contactor’s feedback signal (see [[Contactor feedback check>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HContactorfeedbackcheck"]]).
35
36 If the “Charge request”, “Precharge request” or “Discharge request” assignment is selected, the discrete input is used to control opening the corresponding contactor (see [[Charging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HChargingcontrol"]] and [[Discharging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HDischargingcontrol"]]).
37
38 If the “Insulation status” assignment is selected, the discrete input is used to monitor a signal from an external insulation monitoring device (see [[Insulation monitoring>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HInsulationmonitoring"]]).
39
40
41 **Analog inputs** in this section:
42
43 * No input;
44 * Current sensor;
45 * Current zero level;
46 * Temperature sensor;
47 * Humidity sensor;
48 * Current sensor (AUX) – additional current sensor for measuring current in a series of cells;
49 * Current zero level (AUX) – zero level bus for additional current sensor.
50
51 **Assignment of analog inputs must be selected as follows**:
52
53 * Analog Input #1 – Current sensor;
54 * Analog Input #2 – No input / Current sensor reference line / Current sensor (2nd range) (see note);
55 * Analog Input #3 – No input / Temperature sensor / Current sensor (AUX);
56 * Analog Input #4 – No input / Humidity sensor / Current reference line (AUX) / Current sensor (2nd range) (AUX).
57
58 (% class="box warningmessage" %)
59 (((
60 **Important**: the connection of an additional current sensor (AUX) is possible for special hardware revision of the BMS Main 2.x board. Using an additional current sensor is possible in the configuration when BMS Main serves two galvanically isolated cell series (see [[Series balancing>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.4 Battery parameters.WebHome||anchor="HSeriesbalancing"]]).
61 )))
62
63 (% class="box warningmessage" %)
64 (((
65 **Warning: **reassignment of analog inputs is **unacceptable.**
66 )))
67
68 (% class="box infomessage" %)
69 (((
70 **Note:** The default setting for Analog input #2 is "No signal". If it is necessary to use a current sensor with an additional zero level signal, set the "Current sensor reference line" assignment.
71 )))
72
73 === Current sensor ===
74
75 After selecting the assignment of the analog inputs, you need to configure the parameters of the sensors connected to the board.
76
77 To configure the current sensor parameters, select the menu "Signals → Current sensor":
78
79 [[image:1732202357233-620.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="453" width="284"]]
80
81 In the «Primary sensor» и «Auxiliary sensor» sections:
82
83 * Sensor type – drop-down menu with supported sensor types;
84 * Nominal current – rated current of the sensor according to the datasheet, А;
85 * Sensitivity – sensitivity of the current sensor according to the datasheet, V / I,,nominal.,,;
86 * Zero level – level "0A" of the current sensor, V;
87 * Multiply the charging current (experimental) – experimental flag for scaling the charging current by given multiplier;
88 * Multiplier – charging current multiplier;
89
90 In the «Options» section:
91
92 * Calibrate sensor on startup – calibration flag (zero level setting) of the current sensor when the board is started;
93 * Calibration time – calibration time of the current sensor, second;
94 * System consumption (current offset) – consumption of the BMS system from the battery, A; This setting is used to adjust the current sensor;
95 * Set sensor zero level – command set the zero level of the current sensor (used for service purposes).
96
97 (% class="box infomessage" %)
98 (((
99 If the "Sensor type" is selected, the “Nominal current” and “Sensitivity” fields are automatically filled.
100 If the "Sensor type" has no necessary preset, the “Nominal current” and “Sensitivity” parameters must be **manually **entered.
101 )))
102
103 Calibration of the current sensor (“Calibrate sensor on startup” flag) is necessary if the sensor does not have a reference line (zero level signal).
104
105 === Current shunt sensor ===
106
107 To configure the shunt current sensor parameters, select the menu "Signals → Current shunt sensor":
108
109 [[image:1732202640889-562.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="342" width="265"]]
110
111 In this section:
112
113 * Settings:
114 ** Enable – a flag to start interaction with BMS Current Sensor (if interaction is enabled then BMS doesn’t use Hall-Effect current sensor which settings are described in the menu "Signals → Current sensor");
115 ** Node ID – an address of BMS Current Sensor in CANopen network;
116 ** Dispatch timeout – timeout of dispatching packages from BMS Current Sensor (if no data is being received from current sensor during this time, the “Shunt offline” flag is set), millisecond;
117 ** Zero level threshold – T,,0,, level, A (if module of instantaneous current (I,,I,,) which is received from shunt sensor is lower than T,,0,,, BMS will assume that current flowing through the battery is zero);
118 ** Mean level threshold – TM level, A (if module of instantaneous current (I,,I,,) which is received from shunt sensor is between T,,M,, and T,,0,,, BMS will use mean value of current I,,M,,; if I,,I,, is greater than T,,M,,, BMS will use instantaneous value of current I,,I,,);
119 ** Invert – a flag to invert current values;
120 * Sensor state:
121 ** Online – a flag showing that the communication with the BMS Current Sensor is established;
122 ** Errors – a list of internal errors of the shunt sensor;
123 ** Current – an instantaneous value of current measured by the BMS Current Sensor, A (measuring frequency is 50 Hz);
124 ** Current (mean) – a mean value of current measured by the BMS Current Sensor, A (the value is calculated as an average of 100 consistent measurements);
125 ** Temperature – a temperature of the shunt sensor, °C.
126
127 === Temperature sensor ===
128
129 To configure the temperature sensor parameters, select the menu "Signals → Temperature sensor":
130
131 [[image:1732204766138-628.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="112" width="256"]]
132
133 In this section:
134
135 * Type – type of temperature sensors;
136 * Mask – mask to ignore the temperature from the corresponding temperature sensors; bit //i// corresponds to temperature input //#(i+1)// of each BMS Logic device; mask 0x5 means that the BMS marks all temperature sensors connected to inputs #1 and #3 of each BMS Logic device as missing and doesn't use them in calculations.
137
138 (% class="box infomessage" %)
139 (((
140 **Note:** Temperature sensors connected to the BMS Main 2.x and BMS Logic boards must be the same type.
141 )))
142
143 === Humidity sensor ===
144
145 To set the humidity sensor parameters, select the menu "Signals → Humidity sensor":
146
147 [[image:1732204899160-307.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="120" width="195"]]
148
149 In this section:
150
151 * Type – type of the humidity sensor.
152
153 === Output signals ===
154
155 The BMS Main 2.x board has **4 discrete outputs**. For each discrete output, its purpose and inversion requirement are specified.
156
157 The BMS Main 2.x board has **4 solid-state relays** (#1 and #2 of them are bipolar, and the #3 and #4 are unipolar). For each relay, its purpose and inversion requirement are specified.
158
159 The order of the numbering of the discrete outputs and the relay corresponds to the order of the numbering on the board.
160
161 To configure output discrete signals and relays, select the menu "Signals → Output signals":
162
163 [[image:1732205046156-597.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="346" width="295"]]
164
165 (% class="box infomessage" %)
166 (((
167 A list of available **discrete output assignments **is available in [[Internal signals>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HInternalsignals"]].
168 )))
169
170 If the "Low SOC" assignment is selected, the output indicates the low battery charge level (see [[Low SOC signal>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HLowSOCsignal"]]).
171
172 If the "High battery charge current" assignment is selected, the output indicates that the charging current exceeds the predefined value (see [[High charging current signal>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HHighchargingcurrentsignal"]]).
173
174 If the "Cooler" assignment is selected, the output indicates the overheating of the battery (see [[High temperature protection>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HHightemperatureprotection"]]).
175
176 If the "Heater" assignment is selected, the output indicates the low battery temperature signal (see [[Low temperature protection>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HLowtemperatureprotection"]]).
177
178 If the "Allow charging" assignment is selected, the output is used to give the charger the allowance to charge the battery (see [[Charging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HChargingcontrol"]]).
179
180 If the "Precharging" assignment is selected, the output is used to charge the capacitive load (see [[Discharging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HDischargingcontrol"]]).
181
182 If the "Acknowledgement of power down" assignment is selected, the output is used to acknowledge power down of the BMS. Acknowledgement is outputted when the charge and discharge relays have been opened on power down request (see [[Charging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HChargingcontrol"]] and [[Discharging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HDischargingcontrol"]]).
183
184 If the "Power up" assignment is selected, the output is used to indicate the power status of BMS (see [[Power down control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HPowerdowncontrol"]]).
185
186
187 (% class="box infomessage" %)
188 (((
189 A list of available **relay assignments **is available in [[Internal signals>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HInternalsignals"]].
190 )))
191
192 If the "Charging" assignment is selected, the relay is used to charge the battery (see [[Charging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HChargingcontrol"]]).
193
194 If the "Discharging" assignment is selected, the relay is used to connect battery to the load (see [[Discharging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HDischargingcontrol"]]).
195
196 If the "Allow charging" assignment is selected, the relay is used to give the charger an allowance to charge the battery (see [[Charging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HChargingcontrol"]]).
197
198 If the "Cooler" assignment is selected, the relay receives a signal indicating overheating of the battery (see [[High temperature protection>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HHightemperatureprotection"]]) or the signal "Cooler" (see [[Cooler control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HCoolercontrol"]]).
199
200 If the "Heater" assignment is selected, a low battery temperature signal is outputted to the relay (see [[Low temperature protection>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HLowtemperatureprotection"]]) or a signal "Heater" (see [[Heater control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HHeatercontrol"]]).
201
202 If the "Precharging" assignment is selected, the relay is used to charge the capacitive load (see [[Discharging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HDischargingcontrol"]]).
203
204 If the "Balancing series 1" assignment is selected, the relay is used to connect a balancing resistor to the cell series 1 (see [[Series balancing>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.4 Battery parameters.WebHome||anchor="HSeriesbalancing"]]).
205
206 If the "Balancing series 2" assignment is selected, the relay is used to connect a balancing resistor to the cell series 2 (see [[Series balancing>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.4 Battery parameters.WebHome||anchor="HSeriesbalancing"]]).
207
208 If the "Discharging (AUX)" assignment is selected, the relay is used to power external equipment (see [[Discharging (AUX) control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HDischarging(AUX)control"]]).
209
210 If the "Main contactor" assignment is selected, the relay is used to close the main contactor in the common (minus) power bus.
211
212 If the "Power up" assignment is selected, the relay is used to close the contactor in the BMS Main power bus.