Changes for page 3.3 Input and output signals
Last modified by Admin on 2026/06/29 16:25
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -71,8 +71,8 @@ 71 71 ** Parallel sensors – additional (AUX) sensor is located in parallel circuit. Final current is estimated as sum of both sensors values; 72 72 ** Serial sensors – additional (AUX) sensor is located on the same circuit. Final current is estimated as average of both sensors values; 73 73 ** Separated sensors – additional (AUX) sensor is used to measure the current in second series of cells (см. [[Series balancing>>url:https://docs.movicomelectric.com/bin/view/Battery%20management%20systems/BMS%20Main%202.1/3.%20Configuration/3.4%20Battery%20parameters/?HSeriesbalancing#HSeriesbalancing]]); 74 -** Dual range sensor – main sensor is a dual range sensor. Transition to a second range measurements is doneby a "Currentthreshold" parameter;75 -** Separate dual range sensors – main and additionalsensorsand main sensor are dual range sensors, located on the same line (P13 header modification is required!);74 +** Dual range sensor – main sensor is a dual range sensor. Transition betwe; 75 +** Separate dual range sensors – auxiliary sensor and main sensor are dual range sensors, located on the same line (P13 header modification is required!); 76 76 * Nominal current – rated current of the sensor according to the datasheet, А; 77 77 * Sensitivity – sensitivity of the current sensor according to the datasheet, V / I,,nominal.,,; 78 78 * Zero level – level "0A" of the current sensor, V;