... ... @@ -46,9 +46,7 @@
46 46  * Temperature sensor;
47 47  * Humidity sensor;
48 48  * Current sensor signal (AUX) – additional (AUX) current sensor output;
49 -* Current sensor reference line (AUX) – additional (AUX) current sensor zero level;
50 -* Current sensor signal (2nd range) – second range output of main dual range sensor (used in "Dual range sensor" and "Separate dual range sensors" modes);
51 -* Current sensor signal (2nd range, AUX) – second range of additional (AUX) dual range sensor (used in "Separate dual range sensors" mode);
49 +* Current sensor reference line (AUX) – additional (AUX) current sensor zero level.
52 52  
53 53  (% class="box warningmessage" %)
54 54  (((
... ... @@ -66,12 +66,12 @@
66 66  In the «Primary sensor» и «Auxiliary sensor» sections:
67 67  
68 68  * Sensor type – drop-down menu with presets for most popular sensor types;
69 -* Mode – main and additional (AUX) sensors mode:
70 -** Disabled – additional (AUX)sensor is not used:
71 -** Parallel sensors – additional (AUX) sensor is located in parallel circuit. Final current is estimated as sum of both sensors values;
72 -** Serial sensors – additional (AUX) sensor is located on the same circuit. Final current is estimated as average of both sensors values;
73 -** Separated sensors – additional (AUX) sensor is used to measure the current in second series of cells (см. [[Series balancing>>url:https://docs.movicomelectric.com/bin/view/Battery%20management%20systems/BMS%20Main%202.1/3.%20Configuration/3.4%20Battery%20parameters/?HSeriesbalancing#HSeriesbalancing]]);
74 -** Dual range sensor – main sensor is a dual range sensor. Transition betwe;
67 +* Mode – auxiliary sensor mode:
68 +** Disabled – auxiliary sensor is not used:
69 +** Parallel sensors – auxiliary sensor is located in parallel circuit. Final current is estimated as sum of both sensors values;
70 +** Serial sensors – auxiliary sensor is located on the same circuit. Final current is estimated as average of both sensors values;
71 +** Separated sensors – auxiliary sensor is used to measure the current in second series of cells (см. [[Series balancing>>url:https://docs.movicomelectric.com/bin/view/Battery%20management%20systems/BMS%20Main%202.1/3.%20Configuration/3.4%20Battery%20parameters/?HSeriesbalancing#HSeriesbalancing]]);
72 +** Dual range sensor – auxiliary sensor line i used to measure the second coil of dual range sensor;
75 75  ** Separate dual range sensors – auxiliary sensor and main sensor are dual range sensors, located on the same line (P13 header modification is required!);
76 76  * Nominal current – rated current of the sensor according to the datasheet, А;
77 77  * Sensitivity – sensitivity of the current sensor according to the datasheet, V / I,,nominal.,,;