... ... @@ -68,11 +68,11 @@
68 68  * Sensor type – drop-down menu with presets for most popular sensor types;
69 69  * Mode – main and additional (AUX) sensors mode:
70 70  ** Disabled – additional (AUX)sensor is not used:
71 -** Parallel sensors – auxiliary sensor is located in parallel circuit. Final current is estimated as sum of both sensors values;
72 -** Serial sensors – auxiliary sensor is located on the same circuit. Final current is estimated as average of both sensors values;
73 -** Separated sensors – auxiliary sensor is used to measure the current in second series of cells (см. [[Series balancing>>url:https://docs.movicomelectric.com/bin/view/Battery%20management%20systems/BMS%20Main%202.1/3.%20Configuration/3.4%20Battery%20parameters/?HSeriesbalancing#HSeriesbalancing]]);
74 -** Dual range sensor – auxiliary sensor line i used to measure the second coil of dual range sensor;
75 -** Separate dual range sensors – auxiliary sensor and main sensor are dual range sensors, located on the same line (P13 header modification is required!);
71 +** Parallel sensors – additional (AUX) sensor is located in parallel circuit. Final current is estimated as sum of both sensors values;
72 +** Serial sensors – additional (AUX) sensor is located on the same circuit. Final current is estimated as average of both sensors values;
73 +** Separated sensors – additional (AUX) sensor is used to measure the current in second series of cells (см. [[Series balancing>>url:https://docs.movicomelectric.com/bin/view/Battery%20management%20systems/BMS%20Main%202.1/3.%20Configuration/3.4%20Battery%20parameters/?HSeriesbalancing#HSeriesbalancing]]);
74 +** Dual range sensor – main sensor is a dual range sensor. Transition to a second range measurements is done by a "Current threshold" parameter;
75 +** Separate dual range sensors – main and additional sensorsand main sensor are dual range sensors, located on the same line (P13 header modification is required!);
76 76  * Nominal current – rated current of the sensor according to the datasheet, А;
77 77  * Sensitivity – sensitivity of the current sensor according to the datasheet, V / I,,nominal.,,;
78 78  * Zero level – level "0A" of the current sensor, V;