Title
... ... @@ -1,1 +1,1 @@
1 -3.3 Input and output signals
1 +signals
Content
... ... @@ -1,54 +1,19 @@
1 -== 3.3.1 Input signals ==
1 +== 3.3.1 Cell overview ==
2 2  
3 -The BMS Main 2.x board has 4 digital inputs of the "dry contact" type. For each discrete input, its purpose and the inversion requirement are specified. The following discrete input assignment options are supported:
3 +To display the minimum and maximum temperature and voltage of the cells, select the menu “Logic / Cell → Overview”:
4 4  
5 -* no signal;
6 -* signal from battery cover;
7 -* charger connected;
8 -* power up/down request;
9 -* inhibit charging;
10 -* inhibit discharging;
11 -* CH contactor feedback;
12 -* DCH contactor feedback;
13 -* Insulation status;
14 -* Charge request;
15 -* Precharge request;
16 -* Discharge request;
17 -* PCH contactor feedback;
18 -* CH/DCH contactor feedback;
19 -* Main contactor feedback.
5 +[[Logic and cell overview section>>image:1732201251933-291.png||data-xwiki-image-style-alignment="center" height="312" width="446"]]
20 20  
21 -If the "signal from the battery cover" assignment is selected, the discrete input is used to monitor the state of the battery cover (see section Battery cover protection).
7 +In this section:
22 22  
23 -if the "charger connected" assignment is selected, the discrete input is involved in the algorithms of charge and discharge control (see sections Charge control and Discharge control).
9 +* BMS Logic board parameters:
10 +** Minimum board temperature, °C;
11 +** Maximum board temperature, °C;
12 +** Command rate – rate of data exchange with BMS Logic boards, commands per second;
13 +* Cell parameters:
14 +** Minimum cell temperature, °C;
15 +** Maximum cell temperature, °C;
16 +** Minimum cell voltage, V;
17 +** Maximum cell voltage, V.
24 24  
25 -If the "power up/down request" assignment is selected, the discrete input is involved in the algorithms of opening the charging and discharging relays and sending acknowledgment of power down to the external equipment (see sections Charge control and Discharge control).
26 -
27 -If the “inhibit charging” assignment is selected, the discrete input is used to open the charging relay.
28 -
29 -If the “inhibit discharging” assignment is selected, the discrete input is used to open the discharging relay.
30 -
31 -If the “CH contactor feedback”, “DCH contactor feedback”, “PCH contactor feedback”, “CH/DCH contactor feedback” or “Main contactor feedback” assignment is selected, the discrete input is involved in monitoring the corresponding contactor’s feedback signal (see section Contactor feedback check).
32 -
33 -If the “Charge request”, “Precharge request” or “Discharge request” assignment is selected, the discrete input is used to control opening the corresponding contactor (see sections Charge control and Discharge control).
34 -
35 -If the “Insulation status” assignment is selected, the discrete input is used to monitor a signal from an external insulation monitoring device (see section Insulation monitoring).
36 -
37 -BMS Main 2.x board has 4 analog inputs for connecting current, temperature and humidity sensors. **Assignment of analog inputs must be selected as follows**:
38 -
39 -* Analog Input #1– Current sensor;
40 -* Analog Input #2– No input / Current zero level (see note);
41 -* Analog Input #3 – No input / Temperature sensor / Current sensor (AUX) / Current zero level (AUX);
42 -* Analog Input #4 – No input / Humidity sensor / Current sensor (AUX) / Current zero level (AUX).
43 -
44 -(% class="box warningmessage" %)
45 -(((
46 -**Important**: the connection of an additional current sensor (AUX) is possible for special hardware revision of the BMS Main 2.x board. Using an additional current sensor is possible in the configuration when BMS Main serves two galvanically isolated cell series (see section Series balancing).
47 -)))
48 -
49 -(% class="box warningmessage" %)
50 -(((
51 -**Reassignment of analog inputs is unacceptable.**
52 -)))
53 -
54 -Note – The default setting for Analog input #2 is "No signal". If it is necessary to use a current sensor with an additional zero level signal, set the "Current zero level" assignment.
19 +After the temperature and voltage values, the symbols "@" indicate the address of the BMS Logic board and the cell.