... ... @@ -16,7 +16,10 @@
16 16  
17 17  [[image:1732201986070-992.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="290" width="272"]]
18 18  
19 +(% class="box infomessage" %)
20 +(((
19 19  A list of available **discrete input assignments **is available in [[Input signals>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HInputsignals"]].
22 +)))
20 20  
21 21  If the "Signal from the battery cover" assignment is selected, the discrete input is used to monitor the state of the battery cover (see [[Battery cover protection>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HBatterycoverprotection"]]).
22 22  
... ... @@ -77,7 +77,14 @@
77 77  
78 78  In the «Primary sensor» и «Auxiliary sensor» sections:
79 79  
80 -* Sensor type – drop-down menu with supported sensor types;
83 +* Sensor type – drop-down menu with presets for most popular sensor types;
84 +* Mode – auxiliary sensor mode:
85 +** Disabled – auxiliary sensor is not used:
86 +** Parallel sensors – auxiliary sensor is located in parallel circuit. Final current is estimated as sum of both sensors values;
87 +** Serial sensors – auxiliary sensor is located on the same circuit. Final current is estimated as average of both sensors values;
88 +** Separated sensors – auxiliary sensor is used to measure the current in second series of cells (см. [[Series balancing>>url:https://docs.movicomelectric.com/bin/view/Battery%20management%20systems/BMS%20Main%202.1/3.%20Configuration/3.4%20Battery%20parameters/?HSeriesbalancing#HSeriesbalancing]]);
89 +** Dual range sensor – auxiliary sensor line i used to measure the second coil of dual range sensor;
90 +** Separate dual range sensors – auxiliary sensor and main sensor are dual range sensors, located on the same line (P13 header modification is required!);
81 81  * Nominal current – rated current of the sensor according to the datasheet, А;
82 82  * Sensitivity – sensitivity of the current sensor according to the datasheet, V / I,,nominal.,,;
83 83  * Zero level – level "0A" of the current sensor, V;
... ... @@ -159,7 +159,10 @@
159 159  
160 160  [[image:1732205046156-597.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="346" width="295"]]
161 161  
172 +(% class="box infomessage" %)
173 +(((
162 162  A list of available **discrete output assignments **is available in [[Internal signals>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HInternalsignals"]].
175 +)))
163 163  
164 164  If the "Low SOC" assignment is selected, the output indicates the low battery charge level (see [[Low SOC signal>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HLowSOCsignal"]]).
165 165  
... ... @@ -178,7 +178,10 @@
178 178  If the "Power up" assignment is selected, the output is used to indicate the power status of BMS (see [[Power down control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HPowerdowncontrol"]]).
179 179  
180 180  
194 +(% class="box infomessage" %)
195 +(((
181 181  A list of available **relay assignments **is available in [[Internal signals>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HInternalsignals"]].
197 +)))
182 182  