... ... @@ -16,7 +16,10 @@
16 16  
17 17  [[image:1732201986070-992.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="290" width="272"]]
18 18  
19 +(% class="box infomessage" %)
20 +(((
19 19  A list of available **discrete input assignments **is available in [[Input signals>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HInputsignals"]].
22 +)))
20 20  
21 21  If the "Signal from the battery cover" assignment is selected, the discrete input is used to monitor the state of the battery cover (see [[Battery cover protection>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HBatterycoverprotection"]]).
22 22  
... ... @@ -38,35 +38,18 @@
38 38  **Analog inputs** in this section:
39 39  
40 40  * No input;
41 -* Current sensor;
42 -* Current zero level;
44 +* Current sensor signal;
45 +* Current sensor reference line;
43 43  * Temperature sensor;
44 44  * Humidity sensor;
45 -* Current sensor (AUX) – additional current sensor for measuring current in a series of cells;
48 +* Current sensor signal (AUX) – additional current sensor for measuring current in a series of cells;
46 46  * Current zero level (AUX) – zero level bus for additional current sensor.
47 47  
48 -**Assignment of analog inputs must be selected as follows**:
49 -
50 -* Analog Input #1 – Current sensor;
51 -* Analog Input #2 – No input / Current sensor reference line / Current sensor (2nd range) (see note);
52 -* Analog Input #3 – No input / Temperature sensor / Current sensor (AUX);
53 -* Analog Input #4 – No input / Humidity sensor / Current reference line (AUX) / Current sensor (2nd range) (AUX).
54 -
55 55  (% class="box warningmessage" %)
56 56  (((
57 -**Important**: the connection of an additional current sensor (AUX) is possible for special hardware revision of the BMS Main 2.x board. Using an additional current sensor is possible in the configuration when BMS Main serves two galvanically isolated cell series (see [[Series balancing>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.4 Battery parameters.WebHome||anchor="HSeriesbalancing"]]).
53 +**Important**: the using of analog input #4 is possible hardware modification of the BMS Main 2.x board.
58 58  )))
59 59  
60 -(% class="box warningmessage" %)
61 -(((
62 -**Warning: **reassignment of analog inputs is **unacceptable.**
63 -)))
64 -
65 -(% class="box infomessage" %)
66 -(((
67 -**Note:** The default setting for Analog input #2 is "No signal". If it is necessary to use a current sensor with an additional zero level signal, set the "Current sensor reference line" assignment.
68 -)))
69 -
70 70  === Current sensor ===
71 71  
72 72  After selecting the assignment of the analog inputs, you need to configure the parameters of the sensors connected to the board.
... ... @@ -77,7 +77,14 @@
77 77  
78 78  In the «Primary sensor» и «Auxiliary sensor» sections:
79 79  
80 -* Sensor type – drop-down menu with supported sensor types;
66 +* Sensor type – drop-down menu with presets for most popular sensor types;
67 +* Mode – auxiliary sensor mode:
68 +** Disabled – auxiliary sensor is not used:
69 +** Parallel sensors – auxiliary sensor is located in parallel circuit. Final current is estimated as sum of both sensors values;
70 +** Serial sensors – auxiliary sensor is located on the same circuit. Final current is estimated as average of both sensors values;
71 +** Separated sensors – auxiliary sensor is used to measure the current in second series of cells (см. [[Series balancing>>url:https://docs.movicomelectric.com/bin/view/Battery%20management%20systems/BMS%20Main%202.1/3.%20Configuration/3.4%20Battery%20parameters/?HSeriesbalancing#HSeriesbalancing]]);
72 +** Dual range sensor – auxiliary sensor line i used to measure the second coil of dual range sensor;
73 +** Separate dual range sensors – auxiliary sensor and main sensor are dual range sensors, located on the same line (P13 header modification is required!);
81 81  * Nominal current – rated current of the sensor according to the datasheet, А;
82 82  * Sensitivity – sensitivity of the current sensor according to the datasheet, V / I,,nominal.,,;
83 83  * Zero level – level "0A" of the current sensor, V;
... ... @@ -159,7 +159,10 @@
159 159  
160 160  [[image:1732205046156-597.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="346" width="295"]]
161 161  
155 +(% class="box infomessage" %)
156 +(((
162 162  A list of available **discrete output assignments **is available in [[Internal signals>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HInternalsignals"]].
158 +)))
163 163  
164 164  If the "Low SOC" assignment is selected, the output indicates the low battery charge level (see [[Low SOC signal>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HLowSOCsignal"]]).
165 165  
... ... @@ -178,11 +178,14 @@
178 178  If the "Power up" assignment is selected, the output is used to indicate the power status of BMS (see [[Power down control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.6 Battery protection.WebHome||anchor="HPowerdowncontrol"]]).
179 179  
180 180  
177 +(% class="box infomessage" %)
178 +(((
181 181  A list of available **relay assignments **is available in [[Internal signals>>doc:Battery management systems.Additional information.1\. Battery controllers\: signals and errors.WebHome||anchor="HInternalsignals"]].
180 +)))
182 182  
183 -If the "Charging" assignment is selected, the relay is used to charge the battery (see [[Charge control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HChargecontrol"]]).
182 +If the "Charging" assignment is selected, the relay is used to charge the battery (see [[Charging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HChargingcontrol"]]).
184 184  
185 -If the "Discharging" assignment is selected, the relay is used to connect battery to the load (see [[Discharge control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HDischargecontrol"]]).
184 +If the "Discharging" assignment is selected, the relay is used to connect battery to the load (see [[Discharging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HDischargingcontrol"]]).
186 186  
187 187  If the "Allow charging" assignment is selected, the relay is used to give the charger an allowance to charge the battery (see [[Charging control>>doc:Battery management systems.BMS Main 2\.1.3\. Configuration.3\.5 Battery control.WebHome||anchor="HChargingcontrol"]]).
188 188