Change comment: There is no comment for this version
To version 17.1
edited by Admin
on 2024/12/02 15:09
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -drafts.bms-main-2.configuration.WebHome
1 +drafts.BMS Main 2\.1.3\. Configuration.WebHome
Content
... ... @@ -4,12 +4,12 @@
4 4  
5 5  BMS Main 2.x board has **4 analog inputs** for connecting current, temperature and humidity sensors.
6 6  
7 +The order of the numbering of the discrete and analog inputs corresponds to the order of the numbering on the board.
8 +
7 7  (% id="cke_bm_2415S" style="display:none" %) (%%)To configure the input discrete and analog signals, select the menu "Signals → Input signals":
8 8  
9 -[[image:1732201986070-992.png||data-xwiki-image-style-alignment="center" height="290" width="272"]]
11 +[[image:1732201986070-992.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="290" width="272"]]
10 10  
11 -The order of the numbering of the discrete and analog inputs corresponds to the order of the numbering on the board.
12 -
13 13  Discrete inputs in this section:
14 14  
15 15  * No input;
... ... @@ -83,9 +83,8 @@
83 83  
84 84  To configure the current sensor parameters, select the menu "Signals → Current sensor":
85 85  
86 -[[image:1732202357233-620.png||data-xwiki-image-style-alignment="center" height="453" width="284"]]
86 +[[image:1732202357233-620.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="453" width="284"]]
87 87  
88 -
89 89  In the «Primary sensor» и «Auxiliary sensor» sections:
90 90  
91 91  * Sensor type – drop-down menu with supported sensor types;
... ... @@ -114,17 +114,17 @@
114 114  
115 115  To configure the shunt current sensor parameters, select the menu "Signals → Current shunt sensor":
116 116  
117 -[[image:1732202640889-562.png||data-xwiki-image-style-alignment="center" height="342" width="265"]]
116 +[[image:1732202640889-562.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="342" width="265"]]
118 118  
119 119  In this section:
120 120  
121 121  * Settings:
122 -* Enable – a flag to start interaction with BMS Current Sensor (if interaction is enabled then BMS doesn’t use Hall-Effect current sensor which settings are described in the menu "Signals → Current sensor");
123 -* Node ID – an address of BMS Current Sensor in CANopen network;
124 -* Dispatch timeout – timeout of dispatching packages from BMS Current Sensor (if no data is being received from current sensor during this time, the “Shunt offline” flag is set), millisecond;
125 -* Zero level threshold – T,,0,, level, A (if module of instantaneous current (I,,I,,) which is received from shunt sensor is lower than T,,0,,, BMS will assume that current flowing through the battery is zero);
126 -* Mean level threshold – TM level, A (if module of instantaneous current (I,,I,,) which is received from shunt sensor is between T,,M,, and T,,0,,, BMS will use mean value of current I,,M,,; if I,,I,, is greater than T,,M,,, BMS will use instantaneous value of current I,,I,,);
127 -* Invert – a flag to invert current values;
121 +** Enable – a flag to start interaction with BMS Current Sensor (if interaction is enabled then BMS doesn’t use Hall-Effect current sensor which settings are described in the menu "Signals → Current sensor");
122 +** Node ID – an address of BMS Current Sensor in CANopen network;
123 +** Dispatch timeout – timeout of dispatching packages from BMS Current Sensor (if no data is being received from current sensor during this time, the “Shunt offline” flag is set), millisecond;
124 +** Zero level threshold – T,,0,, level, A (if module of instantaneous current (I,,I,,) which is received from shunt sensor is lower than T,,0,,, BMS will assume that current flowing through the battery is zero);
125 +** Mean level threshold – TM level, A (if module of instantaneous current (I,,I,,) which is received from shunt sensor is between T,,M,, and T,,0,,, BMS will use mean value of current I,,M,,; if I,,I,, is greater than T,,M,,, BMS will use instantaneous value of current I,,I,,);
126 +** Invert – a flag to invert current values;
128 128  * Sensor state:
129 129  ** Online – a flag showing that the communication with the BMS Current Sensor is established;
130 130  ** Errors – a list of internal errors of the shunt sensor;
... ... @@ -136,9 +136,8 @@
136 136  
137 137  To configure the temperature sensor parameters, select the menu "Signals → Temperature sensor":
138 138  
139 -[[image:1732204766138-628.png||data-xwiki-image-style-alignment="center" height="112" width="256"]]
138 +[[image:1732204766138-628.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="112" width="256"]]
140 140  
141 -
142 142  In this section:
143 143  
144 144  * Type – type of temperature sensors.
... ... @@ -153,7 +153,7 @@
153 153  
154 154  To set the humidity sensor parameters, select the menu "Signals → Humidity sensor":
155 155  
156 -[[Humidity sensor settings>>image:1732204899160-307.png||data-xwiki-image-style-alignment="center" height="120" width="195"]]
154 +[[image:1732204899160-307.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="120" width="195"]]
157 157  
158 158   In this section:
159 159  
... ... @@ -161,17 +161,16 @@
161 161  
162 162  == 3.3.6 Output signals ==
163 163  
164 -The BMS Main 2.x board has 4 discrete outputs. For each discrete output, its purpose and inversion requirement are specified.
162 +The BMS Main 2.x board has **4 discrete outputs**. For each discrete output, its purpose and inversion requirement are specified.
165 165  
166 -The BMS Main 2.x board has 4 solid-state relays (#1 and #2 of them are bipolar, and the #3 and #4 are unipolar). For each relay, its purpose and inversion requirement are specified.
164 +The BMS Main 2.x board has **4 solid-state relays** (#1 and #2 of them are bipolar, and the #3 and #4 are unipolar). For each relay, its purpose and inversion requirement are specified.
167 167  
166 +The order of the numbering of the discrete outputs and the relay corresponds to the order of the numbering on the board.
167 +
168 168  To configure output discrete signals and relays, select the menu "Signals → Output signals":
169 169  
170 -[[image:1732205046156-597.png||data-xwiki-image-style-alignment="center" height="346" width="295"]]
170 +[[image:1732205046156-597.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="346" width="295"]]
171 171  
172 -
173 -The order of the numbering of the discrete outputs and the relay corresponds to the order of the numbering on the board.
174 -
175 175  Discrete outputs in this section:
176 176  
177 177  * No output;
1732794334071-303.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +60.3 KB
Content