Attachments (0 modified, 1 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -4,11 +4,12 @@ 4 4 5 5 BMS Main 2.x board has **4 analog inputs** for connecting current, temperature and humidity sensors. 6 6 7 +The order of the numbering of the discrete and analog inputs corresponds to the order of the numbering on the board. 8 + 7 7 (% id="cke_bm_2415S" style="display:none" %) (%%)To configure the input discrete and analog signals, select the menu "Signals → Input signals": 8 8 9 9 [[image:1732201986070-992.png||data-xwiki-image-style-alignment="center" height="290" width="272"]] 10 10 11 -The order of the numbering of the discrete and analog inputs corresponds to the order of the numbering on the board. 12 12 13 13 Discrete inputs in this section: 14 14 ... ... @@ -85,7 +85,6 @@ 85 85 86 86 [[image:1732202357233-620.png||data-xwiki-image-style-alignment="center" height="453" width="284"]] 87 87 88 - 89 89 In the «Primary sensor» и «Auxiliary sensor» sections: 90 90 91 91 * Sensor type – drop-down menu with supported sensor types; ... ... @@ -119,12 +119,12 @@ 119 119 In this section: 120 120 121 121 * Settings: 122 -* Enable – a flag to start interaction with BMS Current Sensor (if interaction is enabled then BMS doesn’t use Hall-Effect current sensor which settings are described in the menu "Signals → Current sensor"); 123 -* Node ID – an address of BMS Current Sensor in CANopen network; 124 -* Dispatch timeout – timeout of dispatching packages from BMS Current Sensor (if no data is being received from current sensor during this time, the “Shunt offline” flag is set), millisecond; 125 -* Zero level threshold – T,,0,, level, A (if module of instantaneous current (I,,I,,) which is received from shunt sensor is lower than T,,0,,, BMS will assume that current flowing through the battery is zero); 126 -* Mean level threshold – TM level, A (if module of instantaneous current (I,,I,,) which is received from shunt sensor is between T,,M,, and T,,0,,, BMS will use mean value of current I,,M,,; if I,,I,, is greater than T,,M,,, BMS will use instantaneous value of current I,,I,,); 127 -* Invert – a flag to invert current values; 122 +** Enable – a flag to start interaction with BMS Current Sensor (if interaction is enabled then BMS doesn’t use Hall-Effect current sensor which settings are described in the menu "Signals → Current sensor"); 123 +** Node ID – an address of BMS Current Sensor in CANopen network; 124 +** Dispatch timeout – timeout of dispatching packages from BMS Current Sensor (if no data is being received from current sensor during this time, the “Shunt offline” flag is set), millisecond; 125 +** Zero level threshold – T,,0,, level, A (if module of instantaneous current (I,,I,,) which is received from shunt sensor is lower than T,,0,,, BMS will assume that current flowing through the battery is zero); 126 +** Mean level threshold – TM level, A (if module of instantaneous current (I,,I,,) which is received from shunt sensor is between T,,M,, and T,,0,,, BMS will use mean value of current I,,M,,; if I,,I,, is greater than T,,M,,, BMS will use instantaneous value of current I,,I,,); 127 +** Invert – a flag to invert current values; 128 128 * Sensor state: 129 129 ** Online – a flag showing that the communication with the BMS Current Sensor is established; 130 130 ** Errors – a list of internal errors of the shunt sensor; ... ... @@ -138,7 +138,6 @@ 138 138 139 139 [[image:1732204766138-628.png||data-xwiki-image-style-alignment="center" height="112" width="256"]] 140 140 141 - 142 142 In this section: 143 143 144 144 * Type – type of temperature sensors. ... ... @@ -153,7 +153,7 @@ 153 153 154 154 To set the humidity sensor parameters, select the menu "Signals → Humidity sensor": 155 155 156 -[[ Humidity sensor settings>>image:1732204899160-307.png||data-xwiki-image-style-alignment="center" height="120" width="195"]]155 +[[image:1732204899160-307.png||data-xwiki-image-style-alignment="center" height="120" width="195"]] 157 157 158 158 In this section: 159 159 ... ... @@ -161,17 +161,16 @@ 161 161 162 162 == 3.3.6 Output signals == 163 163 164 -The BMS Main 2.x board has 4 discrete outputs. For each discrete output, its purpose and inversion requirement are specified. 163 +The BMS Main 2.x board has **4 discrete outputs**. For each discrete output, its purpose and inversion requirement are specified. 165 165 166 -The BMS Main 2.x board has 4 solid-state relays (#1 and #2 of them are bipolar, and the #3 and #4 are unipolar). For each relay, its purpose and inversion requirement are specified. 165 +The BMS Main 2.x board has **4 solid-state relays** (#1 and #2 of them are bipolar, and the #3 and #4 are unipolar). For each relay, its purpose and inversion requirement are specified. 167 167 167 +The order of the numbering of the discrete outputs and the relay corresponds to the order of the numbering on the board. 168 + 168 168 To configure output discrete signals and relays, select the menu "Signals → Output signals": 169 169 170 170 [[image:1732205046156-597.png||data-xwiki-image-style-alignment="center" height="346" width="295"]] 171 171 172 - 173 -The order of the numbering of the discrete outputs and the relay corresponds to the order of the numbering on the board. 174 - 175 175 Discrete outputs in this section: 176 176 177 177 * No output;
- 1732794334071-303.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.admin - Size
-
... ... @@ -1,0 +1,1 @@ 1 +60.3 KB - Content