... ... @@ -90,7 +90,7 @@
90 90  ** Current sensor (AUX) – additional current sensor for measuring current in a series of cells;
91 91  ** Current zero level (AUX) – zero level bus for additional current sensor.
92 92  
93 -== 3.3.2 Current sensor ==
93 +=== 3.3.2 Current sensor ===
94 94  
95 95  After selecting the assignment of the analog inputs, you need to configure the parameters of the sensors connected to the board.
96 96  
... ... @@ -123,7 +123,7 @@
123 123  
124 124  Calibration of the current sensor (“Calibrate sensor on startup” flag) is necessary if the sensor does not have a reference line (zero level signal).
125 125  
126 -== 3.3.3 Current shunt sensor ==
126 +=== 3.3.3 Current shunt sensor ===
127 127  
128 128  To configure the shunt current sensor parameters, select the menu "Signals → Current shunt sensor":
129 129  
... ... @@ -145,7 +145,7 @@
145 145  ** Current (mean) – a mean value of current measured by the BMS Current Sensor, A (the value is calculated as an average of 100 consistent measurements);
146 146  ** Temperature – a temperature of the shunt sensor, °C.
147 147  
148 -== 3.3.4 Temperature sensor ==
148 +=== 3.3.4 Temperature sensor ===
149 149  
150 150  To configure the temperature sensor parameters, select the menu "Signals → Temperature sensor":
151 151  
... ... @@ -162,7 +162,7 @@
162 162  **Note:** Temperature sensors connected to the BMS Main 2.x and BMS Logic boards must be the same type.
163 163  )))
164 164  
165 -== 3.3.5 Humidity sensor ==
165 +=== 3.3.5 Humidity sensor ===
166 166  
167 167  To set the humidity sensor parameters, select the menu "Signals → Humidity sensor":
168 168  
... ... @@ -172,7 +172,7 @@
172 172  
173 173  * Type – type of the humidity sensor.
174 174  
175 -== 3.3.6 Output signals ==
175 +=== 3.3.6 Output signals ===
176 176  
177 177  The BMS Main 2.x board has 4 discrete outputs. For each discrete output, its purpose and inversion requirement are specified. The following discrete output assignment options are supported:
178 178  
... ... @@ -242,33 +242,4 @@
242 242  
243 243  To configure output discrete signals and relays, select the menu "Signals → Output signals":
244 244  
245 -[[Output signals section>>image:1732205046156-597.png||data-xwiki-image-style-alignment="center" height="346" width="295"]]
246 -
247 -
248 -The order of the numbering of the discrete outputs and the relay corresponds to the order of the numbering on the board.
249 -
250 -In this section:
251 -
252 -* Discrete outputs:
253 -** No output;
254 -** Low SOC;
255 -** High charging current;
256 -** Cooler;
257 -** Heater;
258 -** Allow charging;
259 -** Precharging;
260 -** Acknowledgement of power down;
261 -** Power up;
262 -* Relay:
263 -** No relay;
264 -** Charging;
265 -** Discharging;
266 -** Allow charging;
267 -** Cooler;
268 -** Heater;
269 -** Precharging;
270 -** Balancing series 1;
271 -** Balancing series 2;
272 -** Discharging (AUX);
273 -** Main contactor;
274 -** Power up.
245 +[[Outp>>image:1732205046156-597.png||data-xwiki-image-style-alignment="center" height="346" width="295"]]