2 2  = Installation and connection =
3 3  
4 +== Safety rules ==
5 +
6 +To perform the protection functions, the BMS must be able to disconnect the battery from the load and charger. To do this, at least one contactor able to break the load and charge circuits must be connected to the BMS.
7 +
8 +Before use, **configure the system**. Proper operation of the BMS is possible only if it is correctly configured.
9 +
10 +It is not recommended to use the system in batteries formed by several series of cells connected in parallel. To increase capacity, it is recommended to connect several cells in parallel groups, and then connect the groups in series.
11 +
12 +(% class="box warningmessage" %)
13 +(((
14 +The BMS can be connected to batteries with life-threatening and health-hazardous voltage levels. When working with high-voltage batteries, observe electrical safety regulations, use safety glasses, protective clothing, insulated tools and appliances. To prevent the damage of device avoid electrostatic discharges while working with the battery.
15 +)))
16 +
17 +(% class="box errormessage" %)
18 +(((
19 +**The system is not designed to operate with batteries whose total voltage exceeds 1200 V.**
20 +)))
21 +
4 4  == Installation procedure ==
5 5  
6 6  Overall and mounting dimensions of the BMS Main 2.1 are shown below.
... ... @@ -92,9 +92,9 @@
92 92  |**1**|**V+**|Switching voltage (up to 55V, max 3A)
93 93  |**2**|**NO**|Normally open contact
94 94  
95 -Contactor connection example:
113 +Contactor connection example for all relays:
96 96  
97 -[[image:1741619700532-367.png||height="184" width="246"]]
115 +[[image:1741619814065-850.png||height="189" width="252"]]
98 98  
99 99  === P9 – header of relay 2 ===
100 100  
... ... @@ -108,6 +108,8 @@
108 108  |**1**|**V+**|Switching voltage (up to 55V, max 3A)
109 109  |**2**|**NO**|Normally open contact
110 110  
129 +Contactor connection example: see relay 1.
130 +
111 111  === P6 – header of relay 3 ===
112 112  
113 113  Receptacle Housing: Molex 39012020. Terminals: Molex 5556
... ... @@ -121,6 +121,8 @@
121 121  up to 8A (board rev. 2.1b), up to 3A (board rev. 2.1c)
122 122  |**2**|**NO**|Normally open contact
123 123  
144 +Contactor connection example: see relay 1.
145 +
124 124  === P7 – header of relay 4 ===
125 125  
126 126  Receptacle Housing: Molex 39012020. Terminals: Molex 5556
... ... @@ -134,6 +134,8 @@
134 134  up to 8A (board rev. 2.1b), up to 3A (board rev. 2.1c)
135 135  |**2**|**NO**|Normally open contact
136 136  
159 +Contactor connection example: see relay 1.
160 +
137 137  === P14 – header for CAN and RS-485 interfaces ===
138 138  
139 139  Receptacle Housing: Molex 430250600. Terminals: Molex 43030