Wiki source code of 1. General information

Version 17.1 by Admin on 2024/11/13 17:41

Hide last authors
Admin 16.1 1 [[image:https://movicomelectric.com/wa-data/public/site/img/08-BMS-Main-2-1.png||alt="BMS Main 2.1" height="266" width="408"]]
Admin 13.1 2
Admin 15.2 3 The BMS Main 2.1b is a controller of the modular battery management system that has the following features:
Admin 13.1 4
Admin 15.2 5 * measuring current flowing through the battery;
6 * communication with BMS Logic that measure voltage and temperature of the battery cells;
7 * management of charging and discharging the battery;
8 * management of balancing the battery cells;
9 * protection of the battery from damage caused by current, voltage, temperature, etc.;
10 * communication with external equipment (chargers, inverters, indication panels) to provide needed battery operation mode;
11 * communication with external systems over Ethernet, CAN, RS-485, Wi-Fi;
12 * collecting and storing battery history data on an SD card.
Admin 13.1 13
Admin 15.2 14 The BMS Main 2.1b is used solely in civil areas. It does not use encryption and cryptography.
Admin 13.1 15
Admin 15.2 16 The BMS Main 2.1b is a part of Movicom Electric BMS, a modular battery management system, and controls the following devices:
17
18 * //BMS Logic 2.0//;
19 * //BMS Logic 12//;
20 * //BMS Logic 18//;
21 * //BMS Logic RET//.
22
23 = Specifications =
24
Admin 17.1 25 |(% style="width:429px" %)**Parameter**|(% style="width:1092px" %)**Value**
26 |(% style="width:429px" %)Supply voltage, V|(% style="width:1092px" %)9÷30
27 |(% style="width:429px" %)Current consumption @12 V, mA (max)|(% style="width:1092px" %)100
28 |(% style="width:429px" %)Number of relays|(% style="width:1092px" %)4
29 |(% style="width:429px" %)Number of discrete inputs (dry contact)|(% style="width:1092px" %)4
30 |(% style="width:429px" %)Number of discrete outputs (+5V)|(% style="width:1092px" %)4
31 |(% style="width:429px" %)Relay 1-2 output voltage, V (max)|(% style="width:1092px" %)55
32 |(% style="width:429px" %)Relay 1-2 output current, A (max)|(% style="width:1092px" %)2
33 |(% style="width:429px" %)Relay 3-4 output voltage, V (max)|(% style="width:1092px" %)55
34 |(% style="width:429px" %)Relay 3-4 output current, A (max)|(% style="width:1092px" %)8
35 |(% style="width:429px" %)Current sensor type|(% style="width:1092px" %)(((
36 Hall-Effect sensor, bidirectional, supply voltage 5 V (LEM series HASS, HTFS)
Admin 15.2 37 )))
Admin 17.1 38 |(% style="width:429px" %)CAN bus speed, kbps|(% style="width:1092px" %)125, 250 (by default), 500, 1000
39 |(% style="width:429px" %)RS-485 baud rate, bps|(% style="width:1092px" %)600, 1200, 2400, 4800, 9600 (by default), 19200, 38400, 57600, 115200
40 |(% style="width:429px" %)Ethernet speed, Mbps|(% style="width:1092px" %)10/100
41 |(% style="width:429px" %)RS-485 for communication with BMS Logic baud rate, bps|(% style="width:1092px" %)115200
42 |(% style="width:429px" %)Maximum number of the BMS Logic|(% style="width:1092px" %)20
43 |(% style="width:429px" %)Dimensions (length × width × height), mm|(% style="width:1092px" %)120 × 120 × 32
44 |(% style="width:429px" %)Weight, g|(% style="width:1092px" %)100±5
Admin 15.2 45 |(% colspan="2" %)**Operating conditions**
Admin 17.1 46 |(% style="width:429px" %)Operating temperature range, °С|(% style="width:1092px" %)-40÷75
47 |(% style="width:429px" %)The degree of protection from external influences|(% style="width:1092px" %)IP00
Admin 15.2 48
49
Admin 13.1 50