Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -Battery management systems.BMS Logic 2\.0.WebHome
1 +drafts.BMS Logic 2\.0.WebHome
Content
... ... @@ -1,8 +1,5 @@
1 -(% data-numbered-headings-start="2" style="--numbered-headings-start: 1;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 -= Installation and connection =
1 +== ​​​​​2.1 Installation procedure ==
3 3  
4 -== ​​​​​Installation procedure ==
5 -
6 6  The mounting area of the BMS Logic 2.0 must be protected from mechanical particles (dust, dirt, large objects) and water. The BMS Logic 2.0 is recommended to be placed close to the cells it controls, but away from high current circuits to reduce interference to measuring circuits and increase overall reliability of installation.
7 7  
8 8  The installation site must provide convenient access for subsequent connection to the device’s headers.
... ... @@ -21,7 +21,7 @@
21 21  |Mounting holes|M4
22 22  |Headers X1-X3 type|Molex series Mini-Fit
23 23  
24 -== Headers ==
21 +== 2.2 Headers ==
25 25  
26 26  The BMS Logic 2.0 is designed to measure battery parameters – temperature (for a stack of 12 cells there are 2 temperature sensors) and the voltages of 12 cells.
27 27  
... ... @@ -30,10 +30,10 @@
30 30  (% class="box warningmessage" %)
31 31  (((
32 32  **Attention!**
33 -All headers are shown from the device side!
30 +All connectors are shown from the device side!
34 34  )))
35 35  
36 -=== X1 – header for cells and temperature sensors[[image:1733148735564-962.png||data-xwiki-image-style-alignment="center" height="84" width="218"]] ===
33 +=== 2.2.1 X1 – header for cells and temperature sensors[[image:1733148735564-962.png||data-xwiki-image-style-alignment="center" height="84" width="218"]] ===
37 37  
38 38  |**Pin**|**Name**|**Description**
39 39  |**1**|**TEMP2**|Signal from the thermistor #2
... ... @@ -53,7 +53,7 @@
53 53  |**15**|**C4**|Cell #4
54 54  |**16**|**C2**|Cell #2
55 55  
56 -=== X2, X3 – headers for communication with BMS Main ===
53 +=== 2.2.2 X2, X3 – headers for communication with BMS Main ===
57 57  
58 58  [[image:1733148758240-550.jpeg||data-xwiki-image-style-alignment="center" height="86" width="344"]]
59 59  
... ... @@ -63,9 +63,9 @@
63 63  |**3**|**+5V**|Supply voltage 5V
64 64  |**4**|**GND**|Ground
65 65  
66 -== (% style="color:#333333" %)Switches and indicators(%%) ==
63 +== (% style="color:#333333" %)2.3 Switches and indicators(%%) ==
67 67  
68 -=== SWD1 – address switch ===
65 +=== 2.3.1 SWD1 – address switch ===
69 69  
70 70  |**Switch number**|**Description**
71 71  |**1**|The first (the lowest) bit of the address. Position ON - bit is 1
... ... @@ -75,15 +75,15 @@
75 75  |**5**|The fifth bit of the address. Position ON - bit is 1
76 76  |**6**|The sixth (the highest) bit of the address. Position ON - bit is 1
77 77  
78 -=== DS1 – mode indicator ===
75 +=== 2.3.2 DS1 – mode indicator ===
79 79  
80 80  |**State**|**Description**
81 81  |**Blinking**|Communication between the BMS Main and the device is established
82 82  |**No light**|There is no communication between the BMS Main and the device
83 83  
84 -== Connection procedure ==
81 +== 2.4 Connection procedure ==
85 85  
86 -=== Connection to BMS Main ===
83 +=== 2.4.1 Connection to BMS Main ===
87 87  
88 88  To connect the BMS Main to BMS Logic 2.0 do the following steps:
89 89  
... ... @@ -91,16 +91,14 @@
91 91  1. Connect the BMS Logic 2.0 to each other (X2 -> X3).
92 92  1. Install jumper P1 on the last BMS Logic 2.0 in the chain.
93 93  
94 -(% class="box infomessage" %)
95 -(((
96 -**Recommendations:**
97 -~1. The total cable length (the sum of the lengths of all cables) between the BMS Main and the last BMS Logic 2.0 should not exceed 500 meters.
98 -2. Make all connections with the same cable.
99 -3. For a total cable length of more than 10 meters use twisted pair with the 120 Ohm wave impedance.
100 -)))
91 +Recommendations:
101 101  
102 -=== Connecting battery cells ===
93 +1. The total cable length (the sum of the lengths of all cables) between the BMS Main and the last BMS Logic 2.0 should not exceed 500 meters.
94 +1. Make all connections with the same cable.
95 +1. For a total cable length of more than 10 meters use twisted pair with the 120 Ohm wave impedance.
103 103  
97 +=== 2.4.2 Connecting battery cells ===
98 +
104 104  To connect the battery cells, follow the picture below. Incorrect connection of the cells can damage the BMS Logic 2.0.
105 105  
106 106  Begin the connection with the negative of the battery: the "V-" of the first BMS Logic 2.0 is connected to "B-", then the first cell (C1) of the battery is connected, then the second (C2), etc. The “V-“ of the next BMS Logic 2.0 is connected to the C12 of the previous BMS Logic 2.0. If not all inputs of the cells are used, then the remaining inputs are connected to the cell with the highest potential.
... ... @@ -114,7 +114,7 @@
114 114  Connect the battery according to the diagram, otherwise the device may be damaged!
115 115  )))
116 116  
117 -=== Connecting thermistors ===
112 +=== 2.4.3 Connecting thermistors ===
118 118  
119 119  Thermistors should be fastened to the cells, excluding short circuits to the cell terminals (for example, isolate thermistors with heat shrink). For reliable operation, it is recommended to use all thermistors (1 temperature sensor for 6 cells).
120 120  