... ... @@ -27,7 +27,7 @@
27 27  (% class="box warningmessage" %)
28 28  (((
29 29  **Attention!**
30 -All connectors are shown from the device side!
30 +All headers are shown from the device side!
31 31  )))
32 32  
33 33  === 2.2.1 X1 – header for cells and temperature sensors[[image:1733148735564-962.png||data-xwiki-image-style-alignment="center" height="84" width="218"]] ===
... ... @@ -88,12 +88,14 @@
88 88  1. Connect the BMS Logic 2.0 to each other (X2 -> X3).
89 89  1. Install jumper P1 on the last BMS Logic 2.0 in the chain.
90 90  
91 -Recommendations:
91 +(% class="box infomessage" %)
92 +(((
93 +**Recommendations:**
94 +~1. The total cable length (the sum of the lengths of all cables) between the BMS Main and the last BMS Logic 2.0 should not exceed 500 meters.
95 +2. Make all connections with the same cable.
96 +3. For a total cable length of more than 10 meters use twisted pair with the 120 Ohm wave impedance.
97 +)))
92 92  
93 -1. The total cable length (the sum of the lengths of all cables) between the BMS Main and the last BMS Logic 2.0 should not exceed 500 meters.
94 -1. Make all connections with the same cable.
95 -1. For a total cable length of more than 10 meters use twisted pair with the 120 Ohm wave impedance.
96 -
97 97  === 2.4.2 Connecting battery cells ===
98 98  