Last modified by Admin on 2025/03/18 13:04

From version 20.2
edited by Admin
on 2025/03/18 12:26
Change comment: There is no comment for this version
To version 14.1
edited by Admin
on 2024/12/11 11:19
Change comment: Renamed back-links.

Summary

Details

Page properties
Content
... ... @@ -1,16 +1,6 @@
1 1  (% data-numbered-headings-start="2" style="--numbered-headings-start: 1;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 -= nstallation and connection =
2 += Installation and connection =
3 3  
4 -== Safety rules ==
5 -
6 -
7 -It is not recommended to use the system in batteries formed by several series of cells connected in parallel. To increase capacity, it is recommended to connect several cells in parallel groups, and then connect the groups in series.
8 -
9 -(% class="box warningmessage" %)
10 -(((
11 -The BMS can be connected to batteries with life-threatening and health-hazardous voltage levels. When working with high-voltage batteries, observe electrical safety regulations, use safety glasses, protective clothing, insulated tools and appliances. To prevent the damage of device avoid electrostatic discharges while working with the battery.
12 -)))
13 -
14 14  == Installation procedure ==
15 15  
16 16  The mounting area of the BMS Logic 12 must be protected from mechanical particles (dust, dirt, large objects) and water. The BMS Logic 12 is recommended to be placed close to the cells it controls, but away from high current circuits to reduce interference to measuring circuits and increase overall reliability of installation.
... ... @@ -21,19 +21,22 @@
21 21  
22 22  Overall and mounting dimensions of the BMS Logic 12 are shown below.
23 23  
24 -[[image:1736773655076-566.png||data-xwiki-image-style-alignment="center" height="534" width="600"]]
14 +[[image:1733142832467-386.png||data-xwiki-image-style-alignment="center" height="410" width="486"]]
25 25  
16 +
17 +
26 26  (% style="width:477px" %)
27 27  |**Parameter**|(% style="width:160px" %)**Value**
28 28  |Overall dimensions (length × width × height), mm|(% style="width:160px" %)139 × 126 × 16
29 29  |Mounting dimensions (length × width), mm|(% style="width:160px" %)123 × 118
30 30  |Mounting holes|(% style="width:160px" %)M4
23 +|Headers X1-X4 type|(% style="width:160px" %)Molex series Micro-Fit
31 31  
32 32  == Headers ==
33 33  
34 34  The BMS Logic 12 is designed to measure temperature and voltage of 12 battery cells.
35 35  
36 -[[image:1736770542979-717.png||data-xwiki-image-style-alignment="center" height="356" width="450"]]
29 +[[image:1733143089674-767.png||data-xwiki-image-style-alignment="center" height="356" width="531"]]
37 37  
38 38  (% class="box warningmessage" %)
39 39  (((
... ... @@ -43,8 +43,6 @@
43 43  
44 44  === X1 – header for cells ===
45 45  
46 -Receptacle Housing: Molex 430251400. Terminals: Molex 43030
47 -
48 48  [[image:1733143152741-474.jpeg||data-xwiki-image-style-alignment="center" height="81" width="210"]]
49 49  
50 50  |**Pin**|**Name**|**Description**
... ... @@ -65,8 +65,6 @@
65 65  
66 66  === X2 – header for temperature sensors ===
67 67  
68 -Receptacle Housing: Molex 430252400. Terminals: Molex 43030
69 -
70 70  [[image:1733143152745-708.jpeg||data-xwiki-image-style-alignment="center" height="92" width="368"]]
71 71  
72 72  |**Pin**|**Name**|**Description**
... ... @@ -97,8 +97,6 @@
97 97  
98 98  === X3, X4 – headers for communication with BMS Main ===
99 99  
100 -Receptacle Housing: Molex 430250400. Terminals: Molex 43030
101 -
102 102  [[image:1733151077073-306.png||data-xwiki-image-style-alignment="center" height="78" width="71"]]
103 103  
104 104  |**Pin**|**Name**|**Description**
1736770542979-717.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -39.4 KB
Content
1736773655076-566.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -35.4 KB
Content