Last modified by Admin on 2025/03/18 13:04

From version 12.1
edited by Admin
on 2024/12/11 11:02
Change comment: There is no comment for this version
To version 22.1
edited by Admin
on 2025/03/18 12:52
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -drafts.BMS Logic 12.WebHome
1 +Battery management systems.BMS Logic 12.WebHome
Content
... ... @@ -1,6 +1,17 @@
1 1  (% data-numbered-headings-start="2" style="--numbered-headings-start: 1;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 -= Installation and connection =
2 += nstallation and connection =
3 3  
4 +== Safety rules ==
5 +
6 +Before use, **configure the system**. Proper operation of the BMS is possible only if it is correctly configured.
7 +
8 +It is not recommended to use the system in batteries formed by several series of cells connected in parallel. To increase capacity, it is recommended to connect several cells in parallel groups, and then connect the groups in series.
9 +
10 +(% class="box errormessage" %)
11 +(((
12 +The BMS can be connected to batteries with life-threatening and health-hazardous voltage levels. When working with high-voltage batteries, observe electrical safety regulations, use safety glasses, protective clothing, insulated tools and appliances. To prevent the damage of device avoid electrostatic discharges while working with the battery.
13 +)))
14 +
4 4  == Installation procedure ==
5 5  
6 6  The mounting area of the BMS Logic 12 must be protected from mechanical particles (dust, dirt, large objects) and water. The BMS Logic 12 is recommended to be placed close to the cells it controls, but away from high current circuits to reduce interference to measuring circuits and increase overall reliability of installation.
... ... @@ -11,22 +11,19 @@
11 11  
12 12  Overall and mounting dimensions of the BMS Logic 12 are shown below.
13 13  
14 -[[image:1733142832467-386.png||data-xwiki-image-style-alignment="center" height="410" width="486"]]
25 +[[image:1736773655076-566.png||data-xwiki-image-style-alignment="center" height="534" width="600"]]
15 15  
16 -
17 -
18 18  (% style="width:477px" %)
19 19  |**Parameter**|(% style="width:160px" %)**Value**
20 20  |Overall dimensions (length × width × height), mm|(% style="width:160px" %)139 × 126 × 16
21 21  |Mounting dimensions (length × width), mm|(% style="width:160px" %)123 × 118
22 22  |Mounting holes|(% style="width:160px" %)M4
23 -|Headers X1-X4 type|(% style="width:160px" %)Molex series Micro-Fit
24 24  
25 25  == Headers ==
26 26  
27 27  The BMS Logic 12 is designed to measure temperature and voltage of 12 battery cells.
28 28  
29 -[[image:1733143089674-767.png||data-xwiki-image-style-alignment="center" height="356" width="531"]]
37 +[[image:1736770542979-717.png||data-xwiki-image-style-alignment="center" height="356" width="450"]]
30 30  
31 31  (% class="box warningmessage" %)
32 32  (((
... ... @@ -36,6 +36,8 @@
36 36  
37 37  === X1 – header for cells ===
38 38  
47 +Receptacle Housing: Molex 430251400. Terminals: Molex 43030
48 +
39 39  [[image:1733143152741-474.jpeg||data-xwiki-image-style-alignment="center" height="81" width="210"]]
40 40  
41 41  |**Pin**|**Name**|**Description**
... ... @@ -56,6 +56,8 @@
56 56  
57 57  === X2 – header for temperature sensors ===
58 58  
69 +Receptacle Housing: Molex 430252400. Terminals: Molex 43030
70 +
59 59  [[image:1733143152745-708.jpeg||data-xwiki-image-style-alignment="center" height="92" width="368"]]
60 60  
61 61  |**Pin**|**Name**|**Description**
... ... @@ -86,6 +86,8 @@
86 86  
87 87  === X3, X4 – headers for communication with BMS Main ===
88 88  
101 +Receptacle Housing: Molex 430250400. Terminals: Molex 43030
102 +
89 89  [[image:1733151077073-306.png||data-xwiki-image-style-alignment="center" height="78" width="71"]]
90 90  
91 91  |**Pin**|**Name**|**Description**
... ... @@ -107,7 +107,7 @@
107 107  
108 108  (% class="box infomessage" %)
109 109  (((
110 -**Note: **There is no SWD1 switch in the recent revisions of the BMS Logic 12. The device address must be configured in the settings (see the section [[3. Configuration>>doc:drafts.BMS Logic 12.3\. Configuration.WebHome]]).
124 +**Note: **There is no SWD1 switch in the recent revisions of the BMS Logic 12. The device address must be configured in the settings (see the section [[Configuration>>doc:Battery management systems.BMS Logic 12.3\. Configuration.WebHome]]).
111 111  )))
112 112  
113 113  === SWD2 – RS-485 termination resistor switch ===
1736770542979-717.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +39.4 KB
Content
1736773655076-566.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +35.4 KB
Content