8 8  To connect to the device, launch ElectricDeviceMonitor, select "Unified monitor" in the main program window.
9 9  
10 -[[image:1734009713280-126.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="435" width="400"]]
10 +[[image:Battery management systems.BMS Main 3.3\. Configuration.3\.1 General information.WebHome@1735233230234-960.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="340" width="450"]]
11 11  
12 12  A window with the connection parameters will open:
13 13  
14 -[[image:1734009713285-258.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="331" width="600"]]
14 +[[image:1734009713285-258.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="248" width="450"]]
15 15  
16 16  In the Unified monitor launcher window, choose the used CAN-USB adapter and specify the following settings:
17 17  
... ... @@ -20,8 +20,16 @@
20 20  
21 21  and select the “Launch monitor” button.
22 22  
23 -When connected, the device asks for an access password. For the "User" account, the default password is "user" (without quotes).
23 +When connected, the device asks for an access password.
24 24  
25 +Below is the list of available users. Default passwords can be changed in "Device -> Change password" menu.
26 +
27 +|=User|=Default Password|=Description
28 +|Guest|guest|Guest access to view battery state. No permissions to change and view any settings
29 +|User|user|A common user access with permissions to change almost all the settings
30 +|Service|- (by request)|A service account for battery manufacturers. Has access to some additional settings
31 +|Manufacturer|-|This account is used by BMS manufacturer and not accessible for others
32 +
25 25  [[image:1734009713287-917.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="381" width="600"]]
26 26  
27 27  After successful authentication, the device will send settings and state profiles, which will be displayed as two tabs: "Settings" and "State":
... ... @@ -42,7 +42,7 @@
42 42  
43 43  To change the internal parameters of the BMS IMD, select the «IMD» section:
44 44  
45 -[[image:1734009713290-935.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="350" width="600"]]
53 +[[image:1751892873156-729.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="469" width="600"]]
46 46  
47 47  In this section:
48 48  
... ... @@ -51,7 +51,8 @@
51 51  * Alarm resistance, kOhm – resistance value which indicate the resistance fault and triggers discrete output OUT_ERROR, kOhm;
52 52  * Warning resistance, kOhm – resistance value which triggers the low resistance warning, kOhm;
53 53  * Transition timeout – a maximum time of the measurement transient process, after which a Timeout error will be generated (see [[Reading device status>>doc:||anchor="HReadingdevicestatus"]]), s. This parameter should be increased if there is significant capacitance between the battery buses and the chassis.
54 -* Minimum bus voltage – a battery voltage value below which a Low bus voltage error will be generated (see [[Reading device status>>doc:||anchor="HReadingdevicestatus"]]), V.
62 +* Minimum bus voltage – a battery voltage value below which a Low bus voltage error will be generated (see [[Reading device status>>doc:||anchor="HReadingdevicestatus"]]), V;
63 +* Minimum calculation time – минима
55 55  
56 56  === Connection parameters ===
57 57  
... ... @@ -101,6 +101,7 @@
101 101  ** Timeout error – timeout of transition process of measurement;
102 102  ** Anomaly error – the device cannot measure resistance, for example, due to a poor connection to the chassis;
103 103  ** Self test error;
113 +** Chassis break;
104 104  * Insulation status:
105 105  ** No data;
106 106  ** Ok;
... ... @@ -108,10 +108,9 @@
108 108  ** Alarm – resistance is lower than the Alarm resistance;
109 109  * Measurement state – state of measurement procedure:
110 110  ** Idle;
111 -** Chassis connection – chassis is connecting to measuring circuit;
112 -** First stage;
113 -** Offset connection – offset resistors are connecting to measuring circuit;
114 -** Second stage;
121 +** Bus voltage check;
122 +** Chassis connection;
123 +** Bias resistor connection;
115 115  * Resistance calculated – a flag showing that the insulation resistance is calculated;
116 116  * Resistance plus – resistance value between positive line and chassis, Ohm;
117 117  * Resistance minus – resistance value between negative line and chassis, Ohm;