Changes for page 3. Configuration
Last modified by Admin on 2025/03/03 17:35
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -47,11 +47,11 @@ 47 47 In this section: 48 48 49 49 * Always allow work – a flag to enable work permanently; 50 -* Control via PDO – a flag that allows to control the device using a PDO message (see t he“BMS IMD1.x–CANopen protocol” document);50 +* Control via PDO – a flag that allows to control the device using a PDO message (see [[CANopen protocol>>doc:Battery management systems.BMS IMD.4\. CANopen protocol.WebHome]]); 51 51 * Alarm resistance, kOhm – resistance value which indicate the resistance fault and triggers discrete output OUT_ERROR, kOhm; 52 52 * Warning resistance, kOhm – resistance value which triggers the low resistance warning, kOhm; 53 -* Transition timeout – a maximum time of the measurement transient process, after which a Timeout error will be generated (see section4.3), s. This parameter should be increased if there is significant capacitance between the battery buses and the chassis.54 -* Minimum bus voltage – a battery voltage value below which a Low bus voltage error will be generated (see section4.3), V.53 +* Transition timeout – a maximum time of the measurement transient process, after which a Timeout error will be generated (see [[Reading device status>>doc:||anchor="HReadingdevicestatus"]]), s. This parameter should be increased if there is significant capacitance between the battery buses and the chassis. 54 +* Minimum bus voltage – a battery voltage value below which a Low bus voltage error will be generated (see [[Reading device status>>doc:||anchor="HReadingdevicestatus"]]), V. 55 55 56 56 === Connection parameters === 57 57