Signals, states and errors
Input signals
Below is the list of input signals that can be assigned to discrete inputs of the BMS controller.
Name | Description | Compability | BMS DIsplay | CANopen SDO | Modbus | |||
---|---|---|---|---|---|---|---|---|
Mini S / Mini | Main 2.1 | Main 3 | Short name | Abbreviation | ||||
Balancing request | Request to balance the cells | Yes | Yes | Yes | Balancing req. | BR | ||
Battery cover | Signal from the battery cover | Yes | Yes | Yes | Battery cover | CVR | ||
CH contactor feedback | Signal from the charging contactor feedback loop | Yes* | Yes | Yes | CH cont. feed. | CCF | ||
CH/DCH contactor feedback | Signal from the charging/discharging contactor feedback loop | Yes* | Yes | Yes | DCH cont. feed. | DCF | ||
Charge request | Request to close the charging contactor | Yes | Yes | Yes | Charge request | CRE | ||
Charger connected | Signal indicating that the charger is connected | Yes | Yes | Yes | Charger connect. | CON | ||
Circuit breaker status | Status of protective disconnector | Yes | Yes | Yes | Circuit breaker | CBS | ||
Close External 1 | Request to set the External 1 signal | Yes | Yes | Yes | Close Ext.1 | CE1 | ||
Close Main contactor | Request to close the main contactor | Yes | Yes | Yes | Close Main cont. | CMC | ||
DCH contactor feedback | Signal from the discharging contactor feedback loop | Yes* | Yes | Yes | DCH cont. feed. | DCF | ||
Discharge request | Request to close the discharging contactor | Yes | Yes | Yes | Discharge req. | DRE | ||
Fuse 1 | Signal from fuse 1 | Yes | Yes | Yes | Fuse 1 | F1 | ||
Fuse 2 | Signal from fuse 2 | Yes | Yes | Yes | Fuse 2 | F2 | ||
Fuse 3 | Signal from fuse 3 | Yes | Yes | Yes | Fuse 3 | F3 | ||
Inhibit charging | Command to open the charging contactor | Yes | Yes | Yes | Inhibit charg. | ICH | ||
Inhibit discharging | Command to open the discharging contactor | Yes | Yes | Yes | Inhibit disch. | IDC | ||
Insulation status | Signal from an insulation monitoring device | Yes | Yes | Yes | Insul. status | INS | ||
Interlock | Signal from the interlock loop | Yes | Yes | Yes | Interlock | INT | ||
Main contactor feedback | Signal from the main contactor feedback loop | Yes* | Yes | Yes | Main cont. feed. | MCF | ||
PCH contactor feedback | Signal from the precharging contactor feedback loop | Yes* | Yes | Yes | PCH cont. feed. | PCF | ||
Power up/down request | Request to power down the device | Yes | Yes | Yes | Power down req. | PDN | ||
Precharge request | Request to close the precharging contactor | Yes | Yes | Yes | Precharge req. | PRE |
* Contactor feedback signals in BMS Mini / BMS Mini S are connected to X1 header and configured in "Signals → MOSFETs → Contactors feedback" section.
Internal signals
Below is the list of internal BMS signals. The signals marked with bold text can be assigned to discrete outputs and relays.
Name | Description | Compability | BMS Display | CANopen SDO | Modbus | |||
---|---|---|---|---|---|---|---|---|
Mini S / Mini | Main 2.1 | Main 3 | Short name | Abbreviation | ||||
Allow charging | Command for a charger to start charging | Yes | Yes | Yes | Allow charging | ACH | ||
Balancing 1 | Command to balance the first series of cells | Yes* | Yes | Balancing 1 | BA1 | |||
Balancing 2 | Command to balance the second series of cells | Yes* | Yes | Balancing 2 | BA2 | |||
Cell analysis | Signal indicating cell analysis process | Yes*** | Yes*** | Yes*** | Cell analysis | CEA | ||
Charging current present | Signal showing the presence of the charging current | Yes | Yes** | Yes | CH curr. present | CCP | ||
Charging | Command to control the charging contactor | Yes | Yes* | Yes | Charging | CH | ||
Charging/Discharging | Command to control the charging/discharging contactor | Yes | Yes* | Yes | Charg./Discharg. | C/D | ||
Cooler | Command to control the cooler | Yes | Yes | Yes | Cooler | COO | ||
Crown EWS | Yes*** | Yes*** | Yes*** | Crown EWS | EWS | |||
Discharging (AUX) | Command to control the auxiliary discharging contactor | Yes | Yes | Yes | Disch. AUX | AUX | ||
Discharging current present | Signal showing the presence of the discharging current | Yes | Yes** | Yes | DCH curr. pres. | DCP | ||
Discharging | Command to control the discharging contactor | Yes | Yes* | Yes | Discharging | DCH | ||
External 1 | Command to control an external scheme | Yes | Yes | Yes | External 1 | EX1 | ||
Heater (AUX) | Command to control the auxiliary heater | Yes | Heater (AUX) | HAU | ||||
Heater | Command to control the heater | Yes | Yes | Yes | Heater | HEA | ||
High charging current | Signal indicating that the charging current is high | Yes | Yes** | Yes | High ch. curr. | HCC | ||
Init | Signal showing that the device is in the initialization phase | Yes*** | Yes*** | Yes*** | Init | INI | ||
Low SOC | Signal indicatiing that the battery has low SOC | Yes | Yes | Yes | Low SOC | LOS | ||
Main contactor | Command to control the main contactor | Yes | Yes* | Yes | Main contactor | MCO | ||
Power down ACK | Command that acknowledges the BMS power down. Acknowledgement is outputted when the charge and discharge contactors have been opened on the power down request | Yes | Yes** | Yes | Power down ACK | PDA | ||
Power up | Signal indicating the BMS power status | Yes | Yes | Yes | Power up | PUP | ||
Precharging | Command to control the precharging contactor | Yes | Yes | Yes | Precharging | PCH | ||
Ready to charge | Signal showing that the battery is ready for charging | Yes | Yes | Yes | Ready to charge | RTC | ||
Ready to discharge | Signal showing that the battery is ready for discharging | Yes | Yes | Yes | Ready to disch. | RTD | ||
Service reset | Command to restart the device | Yes*** | Yes*** | Service reset | SR | |||
Shutdown request (Combilift) | Command to open the dischrging contactor from the Combilift truck | Yes*** | Yes*** | Yes*** | Combilift shutd. | CSH | ||
Shutdown request (HYG/Spirit) | Command to open the dischrging contactor from the HYG truck | Yes*** | Yes*** | Yes*** | HYG shutdown | HSH | ||
Voltage too high for charging | Signal indicating that the battery is fully charged | Yes*** | Yes*** | Yes*** | Volt. too high | VTH |
* Assignable to relay only
** Assignable to discrete input only
*** Cannot be assigned to discrete output or relay.
Errors
Name | Description | Is a Critical error? | Compability | BMS Display | CANopen SDO | Modbus | |||
Mini S / Mini | Main 2.1 | Main 3 | Short name | Abbreviation | |||||
---|---|---|---|---|---|---|---|---|---|
ADC error | Error of the ADC that measures the battery current | • | Yes | Yes | Yes | ADC | |||
Battery cover error | Battery cover is open | • | Yes | Yes | Yes | BC | |||
Cell count error | Number of cells does not match the specified value | • | Yes | Yes | Yes | CEL | |||
CH contactor cycles error | Switching frequency of the charging contactor is too high | Yes | Yes | Yes | CCC | ||||
CH contactor feedback error | The control signal for the charging contactor and the contactor feedback differ | • | Yes | Yes | CCF | ||||
CH/DCH contactor feedback error | The control signal for the charging/discharging contactor and the contactor feedback differ; | • | Yes | Yes | CDF | ||||
Combilift offline | connection with a Combilift forklift is lost; | Yes | Yes | Yes | COM | ||||
Contactor feedback error | Failure of one of the contactors feedback signal. Which contactor is failed can be found in "Signals -> MOSFETs -> Contactor feedback" section of BMS Mini device | Yes | CFE | ||||||
Critical error | Yes | Yes | Yes | CER | |||||
Crown error | connection with a Crown forklift is lost; | Yes | Yes | Yes | CRO | ||||
Current limit error | charging or discharging current is more than limit calculated by Charge map or Discharge map. | Yes | Yes | CLE | |||||
Current sensor error | error in the current sensor circuit; | • | Yes | Yes | Yes | CSE | |||
DCH contactor cycles error | switching frequency of the discharging contactor is too high; | Yes | Yes | Yes | DCC | ||||
DCH contactor feedback error | the control signals for the discharging contactor and the contactor feedback differ; | • | Yes | Yes | DCF | ||||
FS error | Yes | Yes | Yes | FSE | |||||
General error | Yes* | Yes* | Yes* | GE | |||||
High contactor temperature | Yes | Yes | Yes | CHT | |||||
High humidity | humidity of the battery is increased; | Yes | Yes | HH | |||||
High Logic temperature | at least one of the Logic devices is overheated; | Yes | Yes | LHT | |||||
High temperature (CH) | temperature is too high for charging; | Yes | Yes | Yes | HCT | ||||
High temperature (DCH) | temperature is too high for discharging; | Yes | Yes | Yes | HDT | ||||
High voltage fault | failure of high voltage measuring circuits; | • | Yes | HVF | |||||
HVIL error | breakage of high-voltage interlock current loop; | • | Yes | HE | |||||
HYG offline | connection with a HYG forklift is lost; | Yes | Yes | Yes | HYG | ||||
Insulation fault | • | Yes | Yes | Yes | INF | ||||
Logic count error | Yes | Yes | LOG | ||||||
Logic offline Cell monitor offline | BMS Main devices: at least one of the Logic devices is offline; BMS Mini devices: connection with cell monitor lost. | • | Yes | Yes | Yes | LOF | |||
Low temperature (CH) | temperature is too low for charging; | Yes | Yes | Yes | LCT | ||||
Low temperature (DCH) | temperature is too low for discharging; | Yes | Yes | Yes | LDT | ||||
Main contactor feedback error | the control signals for the main contactor and the contactor feedback differ; | • | Yes | Yes | MCF | ||||
Mount error | Yes | Yes | Yes | MNT | |||||
Need acknowledge | there is an unacknowledged error in Error journal; | Yes | Yes | Yes | ACK | ||||
No temperature sensors | the device has no temperature sensors connected; | • | Yes | Yes | Yes | NTS | |||
Overcurrent | Yes | Yes | Yes | OC | |||||
Overvoltage | Yes | Yes | Yes | OV | |||||
PCH contactor feedback error | the control signals for the precharging contactor and the contactor feedback differ; | • | Yes | Yes | PCF | ||||
Power fault | external devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices; | • | Yes | PF | |||||
Power switch error | short circuit in contactor coil control circuit or power switch overheating; | • | Yes | PSE | |||||
Precharge error | capacitive load pre-charge process did not end during the estimated time; | Yes | Yes | Yes | PE | ||||
Settings error | SET | ||||||||
Short circuit | Yes | Yes | Yes | SHC | |||||
Shunt error | internal error of the shunt current sensor; | • | Yes | Yes | Yes | SHE | |||
Shunt offline | connection with the shunt current sensor is lost; | • | Yes | Yes | Yes | SHO | |||
Spirit offline | connection with a Spirit forklift is lost; | Yes | Yes | Yes | SPI | ||||
Stuck contactor | • | Yes | Yes | Yes | STC | ||||
Temperature sensor is shorted | some temperature sensors are shorted; | • | Yes | Yes | Yes | TSS | |||
Unallowable charging | charging the battery through the discharging contactor; | Yes | Yes | Yes | UCH | ||||
Undervoltage | Yes | Yes | Yes | UV | |||||
Water | there is water in the battery enclosure; | • | Yes | Yes | WA | ||||
WDT reset | watchdog timer reset the device; | • | Yes | Yes | Yes | WDT |
* signal can be assigned to a discrete output and relay.