... ... @@ -45,25 +45,25 @@
45 45  |=(% colspan="1" rowspan="2" style="width: 201px;" %)**Name**|=(% rowspan="2" style="width: 55px;" %)**Abbr.**|=(% colspan="1" rowspan="2" style="width: 531px;" %)**Description**|=(% colspan="3" rowspan="1" style="width: 255px;" %)**Compability**|=(% colspan="1" rowspan="2" style="width: 140px;" %)**CANopen SDO**|=(% colspan="1" rowspan="2" style="width: 142px;" %)**Modbus**
46 46  |=(% style="width: 94px;" %)**Mini S / Mini**|=(% style="width: 75px;" %)**Main 2.1**|=(% style="width: 84px;" %)**Main 3**
47 47  |Allow charging |ACH|a signal for a charger to start charging;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
48 -|Balancing 1 |BA1|balancing the first series of cells;| |Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
49 -|Balancing 2 |BA2|balancing the second series of cells;| |Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
48 +|Balancing 1 |BA1|balancing the first series of cells;| |Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
49 +|Balancing 2 |BA2|balancing the second series of cells;| |Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
50 50  |Cell analysis|CEA| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
51 51  |Charging current present |CCP|the presence of the charging current;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
52 -|Charging |CH|state of the charging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
52 +|Charging |CH|state of the charging contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
53 53  |Charging/discharging|C/D|state of the charging/discharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
54 54  |Cooler |COO|a command to turn on a cooler;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
55 55  |Crown EWS|EWS| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
56 56  |Discharging (AUX) |AUX|state of the auxiliary discharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
57 -|Discharging current present |DCP|the presence of the discharging current;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
58 -|Discharging |DCH|state of the discharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
57 +|Discharging current present |DCP|the presence of the discharging current;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
58 +|Discharging |DCH|state of the discharging contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
59 59  |External 1 |EX1|a signal that activates by the remote request.|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
60 60  |Heater (AUX)|HA| | |Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
61 61  |Heater |HEA|a command to turn on a heater;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
62 -|High charging current |HCC|charging current is high;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
62 +|High charging current |HCC|charging current is high;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
63 63  |Init|INI| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
64 64  |Low SOC |LOS|a signal corresponding the low SOC of the battery;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
65 65  |Main contactor |MCO|state of the main contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
66 -|Power down ACK |PDA|an acknowledgement of BMS power down. Acknowledgement is outputted when the charge and discharge contactors have been opened on power down request;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
66 +|Power down ACK |PDA|an acknowledgement of BMS power down. Acknowledgement is outputted when the charge and discharge contactors have been opened on power down request;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
67 67  |Power up |PUP|an indication of BMS power status;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
68 68  |Precharging |PRE|state of the precharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
69 69  |Ready to charge |RTC|the battery is ready to be charged;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
... ... @@ -74,8 +74,13 @@
74 74  |Voltage too high for charging|ENV| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
75 75  
76 76  
77 +(% class="wikigeneratedid" %)
78 +~* assignable to relay only
77 77  
78 78  (% class="wikigeneratedid" %)
81 +~** assignable to discrete input only
82 +
83 +(% class="wikigeneratedid" %)
79 79  ~*~*~* those states are indicative only and cannot be assigned to discrete output or relay.
80 80  
81 81  === List of errors ===