... ... @@ -39,63 +39,49 @@
39 39  
40 40  === List of internal states ===
41 41  
42 -Here is the list of control internal states.
42 +Here is the list of control internal states. Signals marked with bold text can be assigned to discrete output or relay.
43 43  
44 44  (% style="width:1277px" %)
45 45  |=(% colspan="1" rowspan="2" style="width: 201px;" %)**Name**|=(% rowspan="2" style="width: 55px;" %)**Abbr.**|=(% colspan="1" rowspan="2" style="width: 531px;" %)**Description**|=(% colspan="3" rowspan="1" style="width: 255px;" %)**Compability**|=(% colspan="1" rowspan="2" style="width: 140px;" %)**CANopen SDO**|=(% colspan="1" rowspan="2" style="width: 142px;" %)**Modbus**
46 46  |=(% style="width: 94px;" %)**Mini S / Mini**|=(% style="width: 75px;" %)**Main 2.1**|=(% style="width: 84px;" %)**Main 3**
47 47  |Allow charging |ACH|a signal for a charger to start charging;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
48 -| | | | | | |(% style="width:140px" %) |(% style="width:142px" %)
49 -| | | | | | |(% style="width:140px" %) |(% style="width:142px" %)
50 -| | | | | | |(% style="width:140px" %) |(% style="width:142px" %)
51 -|Charging current present |CCP|the presence of the charging current;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
52 -|Charging |CH|state of the charging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
53 -|Charging/discharging|C/D|state of the charging/discharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
48 +|Balancing 1 |BA1|balancing the first series of cells;| |Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
49 +|Balancing 2 |BA2|balancing the second series of cells;| |Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
50 +|Cell analysis|CEA| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
51 +|Charging current present |CCP|the presence of the charging current;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
52 +|Charging |CH|state of the charging contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
53 +|Charging/discharging|C/D|state of the charging/discharging contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
54 54  |Cooler |COO|a command to turn on a cooler;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
55 -| | | | | | |(% style="width:140px" %) |(% style="width:142px" %)
55 +|Crown EWS|EWS| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
56 56  |Discharging (AUX) |AUX|state of the auxiliary discharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
57 -|Discharging current present |DCP|the presence of the discharging current;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
58 -|Discharging |DCH|state of the discharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
57 +|Discharging current present |DCP|the presence of the discharging current;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
58 +|Discharging |DCH|state of the discharging contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
59 59  |External 1 |EX1|a signal that activates by the remote request.|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
60 -|Heater |HEA|a command to turn on a heater;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
61 61  |Heater (AUX)|HA| | |Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
62 -|High charging current |HCC|charging current is high;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
63 -| | | | | | |(% style="width:140px" %) |(% style="width:142px" %)
61 +|Heater |HEA|a command to turn on a heater;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
62 +|High charging current |HCC|charging current is high;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
63 +|Init|INI| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
64 64  |Low SOC |LOS|a signal corresponding the low SOC of the battery;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
65 -|Main contactor |MCO|state of the main contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
66 -|Power down ACK |PDA|an acknowledgement of BMS power down. Acknowledgement is outputted when the charge and discharge contactors have been opened on power down request;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
65 +|Main contactor |MCO|state of the main contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
66 +|Power down ACK |PDA|an acknowledgement of BMS power down. Acknowledgement is outputted when the charge and discharge contactors have been opened on power down request;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |(% style="width:142px" %)
67 67  |Power up |PUP|an indication of BMS power status;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
68 68  |Precharging |PRE|state of the precharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
69 69  |Ready to charge |RTC|the battery is ready to be charged;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
70 70  |Ready to discharge |RTD|the battery is ready to be discharged;|Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
71 -|Crown EWS|EWS| |Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
72 -|Balancing 1 |BA1|balancing the first series of cells;| |Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
73 -|Balancing 2 |BA2|balancing the second series of cells;| |Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
74 -|Cell analysis|CEA| |Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
75 -|Shutdown request (Combilift)|CSH| |Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
76 -|Shutdown request (HYG/Spirit)|HSH| |Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
77 -|Voltage too high for charging|ENV| |Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
78 -|Init|INI| |Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
79 -|Service reset|SR| |Yes| |Yes|(% style="width:140px" %) |(% style="width:142px" %)
71 +|Service reset|SR| |Yes~*~**| |Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
72 +|Shutdown request (Combilift)|CSH| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
73 +|Shutdown request (HYG/Spirit)|HSH| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
74 +|Voltage too high for charging|ENV| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |(% style="width:142px" %)
80 80  
81 81  (% class="wikigeneratedid" %)
82 -Here is the list of internal states that are used just for information. They do not used to control or communicate with other devices and cannot be assigned to discrete output or relay.
77 +~* assignable to relay only
83 83  
84 -(% style="width:1277px" %)
85 -|=(% colspan="1" rowspan="2" style="width: 201px;" %)**Name**|=(% rowspan="2" style="width: 55px;" %)**Abbr.**|=(% colspan="1" rowspan="2" style="width: 531px;" %)**Description**|=(% colspan="3" rowspan="1" style="width: 255px;" %)**Compability**|=(% colspan="1" rowspan="2" style="width: 140px;" %)**CANopen SDO**|=(% colspan="1" rowspan="2" style="width: 142px;" %)**Modbus**
86 -|=(% style="width: 94px;" %)**Mini S / Mini**|=(% style="width: 75px;" %)**Main 2.1**|=(% style="width: 84px;" %)**Main 3**
87 -|Crown EWS|EWS| |Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
88 -|Balancing 1 |BA1|balancing the first series of cells;| |Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
89 -|Balancing 2 |BA2|balancing the second series of cells;| |Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
90 -|Cell analysis|CEA| |Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
91 -|Shutdown request (Combilift)|CSH| |Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
92 -|Shutdown request (HYG/Spirit)|HSH| |Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
93 -|Voltage too high for charging|ENV| |Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
94 -|Init|INI| |Yes|Yes|Yes|(% style="width:140px" %) |(% style="width:142px" %)
95 -|Service reset|SR| |Yes| |Yes|(% style="width:140px" %) |(% style="width:142px" %)
96 -| | | | | | |(% style="width:140px" %) |(% style="width:142px" %)
97 -| | | | | | |(% style="width:140px" %) |(% style="width:142px" %)
79 +(% class="wikigeneratedid" %)
80 +~** assignable to discrete input only
98 98  
82 +(% class="wikigeneratedid" %)
83 +~*~*~* state is indicative only and cannot be assigned to discrete output or relay.
84 +
99 99  === List of errors ===
100 100  
101 101  (% style="width:1279px" %)
... ... @@ -116,16 +116,16 @@
116 116  |DCH contactor cycles error |DCC|switching frequency of the discharging contactor is too high;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
117 117  |DCH contactor feedback error |DCF|the control signals for the discharging contactor and the contactor feedback differ;|•| |Yes| |(% style="width:142px" %) |(% style="width:134px" %)
118 118  |FS error|FSE| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
119 -|General error|GE| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
105 +|General error|GE| | |Yes*|Yes*|Yes|(% style="width:142px" %) |(% style="width:134px" %)
120 120  |High contactor temperature|CHT| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
121 -|High humidity |HH|humidity of the battery is increased;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
122 -|High Logic temperature |LHT|at least one of the Logic devices is overheated;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
107 +|High humidity |HH|humidity of the battery is increased;| | |Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
108 +|High Logic temperature |LHT|at least one of the Logic devices is overheated;| | |Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
123 123  |High temperature (CH) |HCT|temperature is too high for charging;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
124 124  |High temperature (DCH) |HDT|temperature is too high for discharging;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
125 125  |High voltage fault |HVF|failure of high voltage measuring circuits;|•| | |Yes|(% style="width:142px" %) |(% style="width:134px" %)
126 126  |HVIL error |HE|breakage of high-voltage interlock current loop;|•| | |Yes|(% style="width:142px" %) |(% style="width:134px" %)
127 127  |HYG offline |HYG|connection with a HYG forklift is lost;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
128 -|Insulation fault;|INF| |•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
114 +|Insulation fault|INF| |•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
129 129  |Logic count error|LOG| | | | | |(% style="width:142px" %) |(% style="width:134px" %)
130 130  |Logic offline |LOF|at least one of the Logic devices is offline;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
131 131  |Low temperature (CH) |LCT|temperature is too low for charging;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
... ... @@ -149,7 +149,7 @@
149 149  |Temperature sensor is shorted |TSS|some temperature sensors are shorted;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
150 150  |Unallowable charging |UCH|charging the battery through the discharging contactor;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
151 151  |Undervoltage|UV| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
152 -|Water |WA|there is water in the battery enclosure;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
138 +|Water |WA|there is water in the battery enclosure;|•| |Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
153 153  |WDT reset |WDT|watchdog timer reset the device;|•|Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %)
154 154  
155 -
141 +~* signal can be assigned to a discrete output and relay.