... ... @@ -106,10 +106,9 @@
106 106  |(% style="width:196px" %)CH contactor feedback error |(% style="width:58px" %)CCF|(% style="width:443px" %) the control signals for the charging contactor and the contactor feedback differ;|(% style="width:67px" %)•|(% style="width:93px" %)Yes|(% style="width:76px" %)Yes|(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
107 107  |(% style="width:196px" %)DCH contactor feedback error |(% style="width:58px" %)DCF|(% style="width:443px" %) the control signals for the discharging contactor and the contactor feedback differ;|(% style="width:67px" %)•|(% style="width:93px" %)Yes|(% style="width:76px" %)Yes|(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
108 108  |(% style="width:196px" %)Insulation fault;|(% style="width:58px" %)INF|(% style="width:443px" %) |(% style="width:67px" %)•|(% style="width:93px" %)Yes|(% style="width:76px" %)Yes|(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
109 -|(% style="width:196px" %)PCH contactor feedback error |(% style="width:58px" %)PCF|(% style="width:443px" %) the control signals for the precharging contactor and the contactor feedback differ;|(% style="width:67px" %)•|(% style="width:93px" %) |(% style="width:76px" %)Yes|(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
110 -|(% style="width:196px" %)CH/DCH contactor feedback error |(% style="width:58px" %)CDF|(% style="width:443px" %) the control signals for the charging/discharging contactor and the contactor feedback differ;|(% style="width:67px" %)•|(% style="width:93px" %) |(% style="width:76px" %)Yes|(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
111 -|(% style="width:196px" %)Main contactor feedback error |(% style="width:58px" %)MCF|(% style="width:443px" %) the control signals for the main contactor and the contactor feedback differ;|(% style="width:67px" %)•|(% style="width:93px" %) |(% style="width:76px" %)Yes|(% style="width:80px" %) |(% style="width:142px" %) |(% style="width:134px" %)
112 -|(% style="width:196px" %)Contactor feedback error|(% style="width:58px" %)CFE|(% style="width:443px" %) |(% style="width:67px" %) |(% style="width:93px" %)Yes|(% style="width:76px" %) |(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
109 +|(% style="width:196px" %)PCH contactor feedback error |(% style="width:58px" %)PCF|(% style="width:443px" %) the control signals for the precharging contactor and the contactor feedback differ;|(% style="width:67px" %)•|(% style="width:93px" %)Yes|(% style="width:76px" %)Yes|(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
110 +|(% style="width:196px" %)CH/DCH contactor feedback error |(% style="width:58px" %)CDF|(% style="width:443px" %) the control signals for the charging/discharging contactor and the contactor feedback differ;|(% style="width:67px" %)•|(% style="width:93px" %)Yes|(% style="width:76px" %)Yes|(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
111 +|(% style="width:196px" %)Main contactor feedback error |(% style="width:58px" %)MCF|(% style="width:443px" %) the control signals for the main contactor and the contactor feedback differ;|(% style="width:67px" %)•|(% style="width:93px" %)Yes|(% style="width:76px" %)Yes|(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
113 113  |(% style="width:196px" %)General error|(% style="width:58px" %)GE|(% style="width:443px" %) |(% style="width:67px" %) |(% style="width:93px" %)Yes|(% style="width:76px" %)Yes|(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
114 114  |(% style="width:196px" %)High voltage fault |(% style="width:58px" %)HVF|(% style="width:443px" %) failure of high voltage measuring circuits;|(% style="width:67px" %)•|(% style="width:93px" %) |(% style="width:76px" %) |(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
115 115  |(% style="width:196px" %)Power switch error |(% style="width:58px" %)PSE|(% style="width:443px" %) short circuit in contactor coil control circuit or power switch overheating;|(% style="width:67px" %)•|(% style="width:93px" %) |(% style="width:76px" %) |(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
... ... @@ -116,6 +116,6 @@
116 116  |(% style="width:196px" %)HVIL error |(% style="width:58px" %)HE|(% style="width:443px" %) breakage of high-voltage interlock current loop;|(% style="width:67px" %)•|(% style="width:93px" %) |(% style="width:76px" %) |(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
117 117  |(% style="width:196px" %)Precharge error |(% style="width:58px" %)PE|(% style="width:443px" %) capacitive load pre-charge process did not end during the estimated time;|(% style="width:67px" %) |(% style="width:93px" %)Yes|(% style="width:76px" %)Yes|(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
118 118  |(% style="width:196px" %)Power fault |(% style="width:58px" %)PF|(% style="width:443px" %) external devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices;|(% style="width:67px" %)•|(% style="width:93px" %) |(% style="width:76px" %) |(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
119 -|(% style="width:196px" %)Current limit error |(% style="width:58px" %)CLE|(% style="width:443px" %) charging or discharging current is more than limit calculated by Charge map or Discharge map.|(% style="width:67px" %) |(% style="width:93px" %)Yes|(% style="width:76px" %) |(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)
118 +|(% style="width:196px" %)Current limit error |(% style="width:58px" %) |(% style="width:443px" %) charging or discharging current is more than limit calculated by Charge map or Discharge map.|(% style="width:67px" %) |(% style="width:93px" %)Yes|(% style="width:76px" %) |(% style="width:80px" %)Yes|(% style="width:142px" %) |(% style="width:134px" %)