80 80  |(% style="width:200px" %)Need acknowledge|(% style="width:365px" %)There is an unacknowledged error in error journal|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Need ACK|(% style="width:54px" %)ACK|(% style="width:266px" %) |(% style="width:294px" %)0x1022-0x1023, bit 9. Off = 0, On = 1.
81 81  |(% style="width:200px" %)Overcurrent|(% style="width:365px" %)The battery current is too high|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Overcurrent|(% style="width:54px" %)OC|(% style="width:266px" %) |(% style="width:294px" %)0x1022-0x1023, bit 15. Off = 0, On = 1.
82 82  |(% style="width:200px" %)PCH contactor feedback error|(% style="width:365px" %)The control signal for the precharging contactor and the contactor feedback differ|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)PCH cont. feed.|(% style="width:54px" %)PCF|(% style="width:266px" %) |(% style="width:294px" %)0x1022-0x1023, bit 28. Off = 0, On = 1.
83 -|(% style="width:200px" %)Power fault|(% style="width:365px" %)External devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:121px" %)Power fault|(% style="width:54px" %)PF|(% style="width:266px" %) |(% style="width:294px" %)0x1038-0x1039, bit 0. Off = 0, On = 1.
83 +|(% style="width:200px" %)Power fault|(% style="width:365px" %)External devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:121px" %)Power fault|(% style="width:54px" %)PF|(% style="width:266px" %) |(% style="width:294px" %)0x1038-0x1039, bit 0.
84 84  |(% style="width:200px" %)Power switch error|(% style="width:365px" %)Short circuit in contactor coil control circuit or power switch overheating|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:121px" %)PSW error|(% style="width:54px" %)PSE|(% style="width:266px" %) |(% style="width:294px" %)0x1022-0x1023, bit 16. Off = 0, On = 1.
85 85  |(% style="width:200px" %)Precharge error|(% style="width:365px" %)Capacitive load pre-charge process did not end during the estimated time|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Precharge error|(% style="width:54px" %)PE|(% style="width:266px" %) |(% style="width:294px" %)0x1022-0x1023, bit 30. Off = 0, On = 1.
86 86  |(% style="width:200px" %)Short circuit|(% style="width:365px" %)Flowing high battery currents during a long time|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Short circuit|(% style="width:54px" %)SHC|(% style="width:266px" %) |(% style="width:294px" %)0x1022-0x1023, bit 19. Off = 0, On = 1.