Last modified by Admin on 2025/02/21 14:51

From version 33.4
edited by Admin
on 2025/02/04 11:32
Change comment: There is no comment for this version
To version 33.5
edited by Admin
on 2025/02/04 11:49
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -53,41 +53,41 @@
53 53  
54 54  == Errors ==
55 55  
56 -(% style="width:1500px" %)
57 -|(% colspan="1" rowspan="2" style="width:200px" %)**Name **|(% colspan="1" rowspan="2" style="width:365px" %)**Description**|(% colspan="1" rowspan="2" style="width:63px" %)**Is a critical error?**|(% colspan="2" rowspan="1" style="width:137px" %)**Compability**|(% colspan="2" rowspan="1" style="width:177px" %)**BMS Display**|(% colspan="1" rowspan="2" style="width:266px" %)**CANopen SDO**|(% colspan="1" rowspan="2" style="width:300px" %)**Modbus**
58 -|=(% style="width: 66px;" %)**Main X**|=(% style="width: 70px;" %)**Main 3X**|=(% colspan="1" style="width: 129px;" %)Short name|=(% style="width: 48px;" %)Abbr.
59 -|(% style="width:200px" %)ADC error|(% style="width:365px" %)Error of the ADC that measures the battery current|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:129px" %)ADC error|(% style="width:48px" %)ADC|(% style="width:266px" %) |(% style="width:300px" %)
60 -|(% style="width:200px" %)Battery cover error|(% style="width:365px" %)Battery cover is open|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Battery cover|(% style="width:48px" %)BCE|(% style="width:266px" %) |(% style="width:300px" %)
61 -|(% style="width:200px" %)CH contactor feedback error|(% style="width:365px" %)The control signal for the charging contactor and the contactor feedback differ|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)CH cont. feed.|(% style="width:48px" %)CCF|(% style="width:266px" %) |(% style="width:300px" %)
62 -|(% style="width:200px" %)CH/DCH contactor feedback error|(% style="width:365px" %)The control signal for the charging/discharging contactor and the contactor feedback differ|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)C/D cont. feed.|(% style="width:48px" %)CDF|(% style="width:266px" %) |(% style="width:300px" %)
63 -|(% style="width:200px" %)Charging current unbalance|(% style="width:365px" %)Charging currents of battery modules differ too much|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)CH current unb.|(% style="width:48px" %)CCU|(% style="width:266px" %) |(% style="width:300px" %)
64 -|(% style="width:200px" %)Critical error|(% style="width:365px" %)Critical system error, the BMS is damaged|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Critical error|(% style="width:48px" %)CER|(% style="width:266px" %) |(% style="width:300px" %)
65 -|(% style="width:200px" %)Current limit error|(% style="width:365px" %)Charging or discharging current is more than the limit calculated by Charge map or Discharge map|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Cur. limit error|(% style="width:48px" %)CLE|(% style="width:266px" %) |(% style="width:300px" %)
66 -|(% style="width:200px" %)Current sensor error|(% style="width:365px" %)Error in the current sensor circuit|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:129px" %)Current sensor|(% style="width:48px" %)CSE|(% style="width:266px" %) |(% style="width:300px" %)
67 -|(% style="width:200px" %)Current unbalance (CH)|(% style="width:365px" %)Some of battery modules are unbalanced in current (for charging)|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Current unb. CH|(% style="width:48px" %)CUC|(% style="width:266px" %) |(% style="width:300px" %)
68 -|(% style="width:200px" %)Current unbalance (DCH)|(% style="width:365px" %)Some of battery modules are unbalanced in current (for discharging)|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Current unb. DCH|(% style="width:48px" %)CUD|(% style="width:266px" %) |(% style="width:300px" %)
69 -|(% style="width:200px" %)DCH contactor feedback error|(% style="width:365px" %)The control signal for the discharging contactor and the contactor feedback differ|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:129px" %)DCH cont. feed.|(% style="width:48px" %)DCF|(% style="width:266px" %) |(% style="width:300px" %)
70 -|(% style="width:200px" %)Discharging current unbalance|(% style="width:365px" %)Discharging currents of battery modules differ too much|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)DCH current unb.|(% style="width:48px" %)DCU|(% style="width:266px" %) |(% style="width:300px" %)
71 -|(% style="width:200px" %)FS error|(% style="width:365px" %)SD card read/write error|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)FS error|(% style="width:48px" %)FSE|(% style="width:266px" %) |(% style="width:300px" %)
72 -|(% style="width:200px" %)High contactor temperature|(% style="width:365px" %)Temperature of a contactor is too high|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Hi. cont. temp.|(% style="width:48px" %)HCT|(% style="width:266px" %) |(% style="width:300px" %)
73 -|(% style="width:200px" %)High humidity|(% style="width:365px" %)Increased humidity inside the battery|(% style="width:63px" %) |(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:129px" %)High humidity|(% style="width:48px" %)HHU|(% style="width:266px" %) |(% style="width:300px" %)
74 -|(% style="width:200px" %)High voltage fault|(% style="width:365px" %)Failure of high voltage measuring circuits|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:129px" %)HV fault|(% style="width:48px" %)HVF|(% style="width:266px" %) |(% style="width:300px" %)
75 -|(% style="width:200px" %)HVIL error|(% style="width:365px" %)Breakage of high-voltage interlock current loop|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:129px" %)HVIL error|(% style="width:48px" %)HE|(% style="width:266px" %) |(% style="width:300px" %)
76 -|(% style="width:200px" %)Insulation fault|(% style="width:365px" %)Insulation resistance is too low|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Insulation fault|(% style="width:48px" %)INF|(% style="width:266px" %) |(% style="width:300px" %)
77 -|(% style="width:200px" %)Module offline|(% style="width:365px" %)Some of battery modules is offline|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Module offline|(% style="width:48px" %)MOF|(% style="width:266px" %) |(% style="width:300px" %)
78 -|(% style="width:200px" %)Main contactor feedback error|(% style="width:365px" %)The control signal for the main contactor and the contactor feedback differ|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Main cont. feed.|(% style="width:48px" %)MCF|(% style="width:266px" %) |(% style="width:300px" %)
79 -|(% style="width:200px" %)Mount error|(% style="width:365px" %)SD card cannot be mounted|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Mount error|(% style="width:48px" %)MNT|(% style="width:266px" %) |(% style="width:300px" %)
80 -|(% style="width:200px" %)Need acknowledge|(% style="width:365px" %)There is an unacknowledged error in error journal|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Need ACK|(% style="width:48px" %)ACK|(% style="width:266px" %) |(% style="width:300px" %)
81 -|(% style="width:200px" %)Overcurrent|(% style="width:365px" %)The battery current is too high|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Overcurrent|(% style="width:48px" %)OC|(% style="width:266px" %) |(% style="width:300px" %)
82 -|(% style="width:200px" %)PCH contactor feedback error|(% style="width:365px" %)The control signal for the precharging contactor and the contactor feedback differ|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)PCH cont. feed.|(% style="width:48px" %)PCF|(% style="width:266px" %) |(% style="width:300px" %)
83 -|(% style="width:200px" %)Power fault|(% style="width:365px" %)External devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:129px" %)Power fault|(% style="width:48px" %)PF|(% style="width:266px" %) |(% style="width:300px" %)
84 -|(% style="width:200px" %)Power switch error|(% style="width:365px" %)Short circuit in contactor coil control circuit or power switch overheating|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:129px" %)PSW error|(% style="width:48px" %)PSE|(% style="width:266px" %) |(% style="width:300px" %)
85 -|(% style="width:200px" %)Precharge error|(% style="width:365px" %)Capacitive load pre-charge process did not end during the estimated time|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Precharge error|(% style="width:48px" %)PE|(% style="width:266px" %) |(% style="width:300px" %)
86 -|(% style="width:200px" %)Short circuit|(% style="width:365px" %)Flowing high battery currents during a long time|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Short circuit|(% style="width:48px" %)SHC|(% style="width:266px" %) |(% style="width:300px" %)
87 -|(% style="width:200px" %)Stuck contactor|(% style="width:365px" %)Some contactor got stuck|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Stuck contactor|(% style="width:48px" %)STC|(% style="width:266px" %) |(% style="width:300px" %)
88 -|(% style="width:200px" %)Voltage unbalance (CH)|(% style="width:365px" %)Some of battery modules are unbalanced in voltage (for charging)|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Voltage unb. CH|(% style="width:48px" %)VUC|(% style="width:266px" %) |(% style="width:300px" %)
89 -|(% style="width:200px" %)Voltage unbalance (DCH)|(% style="width:365px" %)Some of battery modules are unbalanced in voltage (for discharging)|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)Voltage unb. DCH|(% style="width:48px" %)VUD|(% style="width:266px" %) |(% style="width:300px" %)
90 -|(% style="width:200px" %)Water|(% style="width:365px" %)There is water in the battery enclosure|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:129px" %)Water|(% style="width:48px" %)WHU|(% style="width:266px" %) |(% style="width:300px" %)
91 -|(% style="width:200px" %)WDT reset|(% style="width:365px" %)Watchdog timer reset the device|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:129px" %)WDT reset|(% style="width:48px" %)WDT|(% style="width:266px" %) |(% style="width:300px" %)
56 +(% style="width:1499px" %)
57 +|(% colspan="1" rowspan="2" style="width:200px" %)**Name **|(% colspan="1" rowspan="2" style="width:365px" %)**Description**|(% colspan="1" rowspan="2" style="width:63px" %)**Is a critical error?**|(% colspan="2" rowspan="1" style="width:137px" %)**Compability**|(% colspan="2" rowspan="1" style="width:177px" %)**BMS Display**|(% colspan="1" rowspan="2" style="width:266px" %)**CANopen SDO**|(% colspan="1" rowspan="2" style="width:294px" %)**Modbus**
58 +|=(% style="width: 66px;" %)**Main X**|=(% style="width: 70px;" %)**Main 3X**|=(% colspan="1" style="width: 121px;" %)Short name|=(% style="width: 54px;" %)Abbr.
59 +|(% style="width:200px" %)ADC error|(% style="width:365px" %)Error of the ADC that measures the battery current|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:121px" %)ADC error|(% style="width:54px" %)ADC|(% style="width:266px" %) |(% style="width:294px" %)
60 +|(% style="width:200px" %)Battery cover error|(% style="width:365px" %)Battery cover is open|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Battery cover|(% style="width:54px" %)BCE|(% style="width:266px" %) |(% style="width:294px" %)
61 +|(% style="width:200px" %)CH contactor feedback error|(% style="width:365px" %)The control signal for the charging contactor and the contactor feedback differ|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)CH cont. feed.|(% style="width:54px" %)CCF|(% style="width:266px" %) |(% style="width:294px" %)
62 +|(% style="width:200px" %)CH/DCH contactor feedback error|(% style="width:365px" %)The control signal for the charging/discharging contactor and the contactor feedback differ|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)C/D cont. feed.|(% style="width:54px" %)CDF|(% style="width:266px" %) |(% style="width:294px" %)
63 +|(% style="width:200px" %)Charging current unbalance|(% style="width:365px" %)Charging currents of battery modules differ too much|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)CH current unb.|(% style="width:54px" %)CCU|(% style="width:266px" %) |(% style="width:294px" %)
64 +|(% style="width:200px" %)Critical error|(% style="width:365px" %)Critical system error, the BMS is damaged|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Critical error|(% style="width:54px" %)CER|(% style="width:266px" %) |(% style="width:294px" %)
65 +|(% style="width:200px" %)Current limit error|(% style="width:365px" %)Charging or discharging current is more than the limit calculated by Charge map or Discharge map|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Cur. limit error|(% style="width:54px" %)CLE|(% style="width:266px" %) |(% style="width:294px" %)
66 +|(% style="width:200px" %)Current sensor error|(% style="width:365px" %)Error in the current sensor circuit|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:121px" %)Current sensor|(% style="width:54px" %)CSE|(% style="width:266px" %) |(% style="width:294px" %)
67 +|(% style="width:200px" %)Current unbalance (CH)|(% style="width:365px" %)Some of battery modules are unbalanced in current (for charging)|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Current unb. CH|(% style="width:54px" %)CUC|(% style="width:266px" %) |(% style="width:294px" %)
68 +|(% style="width:200px" %)Current unbalance (DCH)|(% style="width:365px" %)Some of battery modules are unbalanced in current (for discharging)|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Current unb. DCH|(% style="width:54px" %)CUD|(% style="width:266px" %) |(% style="width:294px" %)
69 +|(% style="width:200px" %)DCH contactor feedback error|(% style="width:365px" %)The control signal for the discharging contactor and the contactor feedback differ|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:121px" %)DCH cont. feed.|(% style="width:54px" %)DCF|(% style="width:266px" %) |(% style="width:294px" %)
70 +|(% style="width:200px" %)Discharging current unbalance|(% style="width:365px" %)Discharging currents of battery modules differ too much|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)DCH current unb.|(% style="width:54px" %)DCU|(% style="width:266px" %) |(% style="width:294px" %)
71 +|(% style="width:200px" %)FS error|(% style="width:365px" %)SD card read/write error|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)FS error|(% style="width:54px" %)FSE|(% style="width:266px" %) |(% style="width:294px" %)
72 +|(% style="width:200px" %)High contactor temperature|(% style="width:365px" %)Temperature of a contactor is too high|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Hi. cont. temp.|(% style="width:54px" %)HCT|(% style="width:266px" %) |(% style="width:294px" %)
73 +|(% style="width:200px" %)High humidity|(% style="width:365px" %)Increased humidity inside the battery|(% style="width:63px" %) |(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:121px" %)High humidity|(% style="width:54px" %)HHU|(% style="width:266px" %) |(% style="width:294px" %)
74 +|(% style="width:200px" %)High voltage fault|(% style="width:365px" %)Failure of high voltage measuring circuits|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:121px" %)HV fault|(% style="width:54px" %)HVF|(% style="width:266px" %) |(% style="width:294px" %)
75 +|(% style="width:200px" %)HVIL error|(% style="width:365px" %)Breakage of high-voltage interlock current loop|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:121px" %)HVIL error|(% style="width:54px" %)HE|(% style="width:266px" %) |(% style="width:294px" %)
76 +|(% style="width:200px" %)Insulation fault|(% style="width:365px" %)Insulation resistance is too low|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Insulation fault|(% style="width:54px" %)INF|(% style="width:266px" %) |(% style="width:294px" %)
77 +|(% style="width:200px" %)Module offline|(% style="width:365px" %)Some of battery modules is offline|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Module offline|(% style="width:54px" %)MOF|(% style="width:266px" %) |(% style="width:294px" %)
78 +|(% style="width:200px" %)Main contactor feedback error|(% style="width:365px" %)The control signal for the main contactor and the contactor feedback differ|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Main cont. feed.|(% style="width:54px" %)MCF|(% style="width:266px" %) |(% style="width:294px" %)
79 +|(% style="width:200px" %)Mount error|(% style="width:365px" %)SD card cannot be mounted|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Mount error|(% style="width:54px" %)MNT|(% style="width:266px" %) |(% style="width:294px" %)
80 +|(% style="width:200px" %)Need acknowledge|(% style="width:365px" %)There is an unacknowledged error in error journal|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Need ACK|(% style="width:54px" %)ACK|(% style="width:266px" %) |(% style="width:294px" %)
81 +|(% style="width:200px" %)Overcurrent|(% style="width:365px" %)The battery current is too high|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Overcurrent|(% style="width:54px" %)OC|(% style="width:266px" %) |(% style="width:294px" %)
82 +|(% style="width:200px" %)PCH contactor feedback error|(% style="width:365px" %)The control signal for the precharging contactor and the contactor feedback differ|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)PCH cont. feed.|(% style="width:54px" %)PCF|(% style="width:266px" %) |(% style="width:294px" %)
83 +|(% style="width:200px" %)Power fault|(% style="width:365px" %)External devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:121px" %)Power fault|(% style="width:54px" %)PF|(% style="width:266px" %) |(% style="width:294px" %)
84 +|(% style="width:200px" %)Power switch error|(% style="width:365px" %)Short circuit in contactor coil control circuit or power switch overheating|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:121px" %)PSW error|(% style="width:54px" %)PSE|(% style="width:266px" %) |(% style="width:294px" %)
85 +|(% style="width:200px" %)Precharge error|(% style="width:365px" %)Capacitive load pre-charge process did not end during the estimated time|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Precharge error|(% style="width:54px" %)PE|(% style="width:266px" %) |(% style="width:294px" %)
86 +|(% style="width:200px" %)Short circuit|(% style="width:365px" %)Flowing high battery currents during a long time|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Short circuit|(% style="width:54px" %)SHC|(% style="width:266px" %) |(% style="width:294px" %)
87 +|(% style="width:200px" %)Stuck contactor|(% style="width:365px" %)Some contactor got stuck|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Stuck contactor|(% style="width:54px" %)STC|(% style="width:266px" %) |(% style="width:294px" %)
88 +|(% style="width:200px" %)Voltage unbalance (CH)|(% style="width:365px" %)Some of battery modules are unbalanced in voltage (for charging)|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Voltage unb. CH|(% style="width:54px" %)VUC|(% style="width:266px" %) |(% style="width:294px" %)
89 +|(% style="width:200px" %)Voltage unbalance (DCH)|(% style="width:365px" %)Some of battery modules are unbalanced in voltage (for discharging)|(% style="width:63px" %) |(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)Voltage unb. DCH|(% style="width:54px" %)VUD|(% style="width:266px" %) |(% style="width:294px" %)
90 +|(% style="width:200px" %)Water|(% style="width:365px" %)There is water in the battery enclosure|(% style="width:63px" %)Yes|(% style="width:66px" %) |(% style="width:70px" %)Yes|(% style="width:121px" %)Water|(% style="width:54px" %)WHU|(% style="width:266px" %) |(% style="width:294px" %)
91 +|(% style="width:200px" %)WDT reset|(% style="width:365px" %)Watchdog timer reset the device|(% style="width:63px" %)Yes|(% style="width:66px" %)Yes|(% style="width:70px" %)Yes|(% style="width:121px" %)WDT reset|(% style="width:54px" %)WDT|(% style="width:266px" %) |(% style="width:294px" %)
92 92  
93 93