Last modified by Admin on 2025/02/21 14:51

From version 26.6
edited by Admin
on 2025/02/04 08:08
Change comment: There is no comment for this version
To version 26.8
edited by Admin
on 2025/02/04 08:10
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -66,9 +66,12 @@
66 66  |Battery cover error|Battery cover is open|•|Yes|Yes|Yes|(% style="width:142px" %)Battery cover|BCE|(% style="width:142px" %) |(% style="width:134px" %)
67 67  |CH contactor feedback error|The control signal for the charging contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)CH cont. feed.|CCF|(% style="width:142px" %) |(% style="width:134px" %)
68 68  |CH/DCH contactor feedback error|The control signal for the charging/discharging contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)C/D cont. feed.|CDF|(% style="width:142px" %) |(% style="width:134px" %)
69 +|Charging current unbalance| | | | | |(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
69 69  |Critical error|Critical system error, the BMS is damaged| |Yes|Yes|Yes|(% style="width:142px" %)Critical error|CER|(% style="width:142px" %) |(% style="width:134px" %)
70 70  |Current limit error|Charging or discharging current is more than the limit calculated by Charge map or Discharge map| |Yes| |Yes|(% style="width:142px" %)Cur. limit error|CLE|(% style="width:142px" %) |(% style="width:134px" %)
71 71  |Current sensor error|Error in the current sensor circuit|•|Yes|Yes|Yes|(% style="width:142px" %)Current sensor|CSE|(% style="width:142px" %) |(% style="width:134px" %)
73 +|Current unbalance (CH)| | | | | |(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
74 +|Current unbalance (DCH)| | | | | |(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
72 72  |DCH contactor feedback error|The control signal for the discharging contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)DCH cont. feed.|DCF|(% style="width:142px" %) |(% style="width:134px" %)
73 73  |FS error|SD card read/write error| |Yes|Yes|Yes|(% style="width:142px" %)FS error|FSE|(% style="width:142px" %) |(% style="width:134px" %)
74 74  |High contactor temperature|Temperature of a contactor is too high| |Yes|Yes|Yes|(% style="width:142px" %)Hi. cont. temp.|HCT|(% style="width:142px" %) |(% style="width:134px" %)
... ... @@ -87,6 +87,8 @@
87 87  |Precharge error|Capacitive load pre-charge process did not end during the estimated time| |Yes|Yes|Yes|(% style="width:142px" %)Precharge error|PE|(% style="width:142px" %) |(% style="width:134px" %)
88 88  |Short circuit|Flowing high battery currents during a long time| |Yes|Yes|Yes|(% style="width:142px" %)Short circuit|SHC|(% style="width:142px" %) |(% style="width:134px" %)
89 89  |Stuck contactor|Some contactor got stuck|•|Yes|Yes|Yes|(% style="width:142px" %)Stuck contactor|STC|(% style="width:142px" %) |(% style="width:134px" %)
93 +|Voltage unbalance (CH)| | | | | |(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
94 +|Voltage unbalance (DCH)| | | | | |(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
90 90  |Water|There is water in the battery enclosure|•| |Yes|Yes|(% style="width:142px" %)Water|WHU|(% style="width:142px" %) |(% style="width:134px" %)
91 91  |WDT reset|Watchdog timer reset the device|•|Yes|Yes|Yes|(% style="width:142px" %)WDT reset|WDT|(% style="width:142px" %) |(% style="width:134px" %)
92 92