Last modified by Admin on 2025/02/21 14:51

From version 26.6
edited by Admin
on 2025/02/04 08:08
Change comment: There is no comment for this version
To version 26.1
edited by Admin
on 2025/02/04 08:03
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -64,29 +64,53 @@
64 64  |=(% style="width: 93px;" %)**Mini S / Mini**|=(% style="width: 76px;" %)**Main 2.1**|=(% style="width: 80px;" %)**Main 3**|=(% colspan="1" style="width: 137px;" %)Short name|=(% style="width: 137px;" %)Abbreviation
65 65  |ADC error|Error of the ADC that measures the battery current|•|Yes|Yes|Yes|(% style="width:142px" %)ADC error|ADC|(% style="width:142px" %) |(% style="width:134px" %)
66 66  |Battery cover error|Battery cover is open|•|Yes|Yes|Yes|(% style="width:142px" %)Battery cover|BCE|(% style="width:142px" %) |(% style="width:134px" %)
67 +|Cell count error|Number of cells does not match the specified value|•|Yes|Yes|Yes|(% style="width:142px" %)Cell count|CEL|(% style="width:142px" %) |(% style="width:134px" %)
68 +|CH contactor cycles error|Switching frequency of the charging contactor is too high| |Yes|Yes|Yes|(% style="width:142px" %)CH cont. cycle|CCC|(% style="width:142px" %) |(% style="width:134px" %)
67 67  |CH contactor feedback error|The control signal for the charging contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)CH cont. feed.|CCF|(% style="width:142px" %) |(% style="width:134px" %)
68 68  |CH/DCH contactor feedback error|The control signal for the charging/discharging contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)C/D cont. feed.|CDF|(% style="width:142px" %) |(% style="width:134px" %)
71 +|Combilift offline|Connection with the Combilift forklift is lost| |Yes|Yes|Yes|(% style="width:142px" %)Combilift offl.|COM|(% style="width:142px" %) |(% style="width:134px" %)
72 +|Contactor feedback error|Failure of one of the contactors feedback signal. Which contactor is failed can be found in "Signals -> MOSFETs -> Contactor feedback" section of the BMS Mini device| |Yes| | |(% style="width:142px" %)Cont. feed. er.|CFE|(% style="width:142px" %) |(% style="width:134px" %)
69 69  |Critical error|Critical system error, the BMS is damaged| |Yes|Yes|Yes|(% style="width:142px" %)Critical error|CER|(% style="width:142px" %) |(% style="width:134px" %)
74 +|Crown error|Connection with the Crown forklift is lost| |Yes|Yes|Yes|(% style="width:142px" %)Crown error|CRO|(% style="width:142px" %) |(% style="width:134px" %)
70 70  |Current limit error|Charging or discharging current is more than the limit calculated by Charge map or Discharge map| |Yes| |Yes|(% style="width:142px" %)Cur. limit error|CLE|(% style="width:142px" %) |(% style="width:134px" %)
71 71  |Current sensor error|Error in the current sensor circuit|•|Yes|Yes|Yes|(% style="width:142px" %)Current sensor|CSE|(% style="width:142px" %) |(% style="width:134px" %)
77 +|DCH contactor cycles error|Switching frequency of the discharging contactor is too high| |Yes|Yes|Yes|(% style="width:142px" %)DCH cont. cycle|DCC|(% style="width:142px" %) |(% style="width:134px" %)
72 72  |DCH contactor feedback error|The control signal for the discharging contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)DCH cont. feed.|DCF|(% style="width:142px" %) |(% style="width:134px" %)
73 73  |FS error|SD card read/write error| |Yes|Yes|Yes|(% style="width:142px" %)FS error|FSE|(% style="width:142px" %) |(% style="width:134px" %)
80 +|General error|Special configurable error depending on other errors| |Yes*|Yes*|Yes*|(% style="width:142px" %)General error|GE|(% style="width:142px" %) |(% style="width:134px" %)
74 74  |High contactor temperature|Temperature of a contactor is too high| |Yes|Yes|Yes|(% style="width:142px" %)Hi. cont. temp.|HCT|(% style="width:142px" %) |(% style="width:134px" %)
75 75  |High humidity|Increased humidity inside the battery| | |Yes|Yes|(% style="width:142px" %)High humidity|HHU|(% style="width:142px" %) |(% style="width:134px" %)
83 +|High Logic temperature|At least one of the Logic devices is overheated| | |Yes|Yes|(% style="width:142px" %)Hi. Logic temp.|HLT|(% style="width:142px" %) |(% style="width:134px" %)
84 +|High temperature (CH)|Temperature is too high for charging| |Yes|Yes|Yes|(% style="width:142px" %)High temp. CH|HTC|(% style="width:142px" %) |(% style="width:134px" %)
85 +|High temperature (DCH)|Temperature is too high for discharging| |Yes|Yes|Yes|(% style="width:142px" %)High temp. DCH|HTD|(% style="width:142px" %) |(% style="width:134px" %)
76 76  |High voltage fault|Failure of high voltage measuring circuits|•| | |Yes|(% style="width:142px" %)HV fault|HVF|(% style="width:142px" %) |(% style="width:134px" %)
77 77  |HVIL error|Breakage of high-voltage interlock current loop|•| | |Yes|(% style="width:142px" %)HVIL error|HE|(% style="width:142px" %) |(% style="width:134px" %)
88 +|HYG offline|Connection with the HYG forklift is lost| |Yes|Yes|Yes|(% style="width:142px" %)HYG offline|HYG|(% style="width:142px" %) |(% style="width:134px" %)
78 78  |Insulation fault|Insulation resistance is too low|•|Yes|Yes|Yes|(% style="width:142px" %)Insulation fault|INF|(% style="width:142px" %) |(% style="width:134px" %)
79 -|Module offline|Some of battery modules is offline|•|Yes|Yes|Yes|(% style="width:142px" %)Logic offline|LOF|(% style="width:142px" %) |(% style="width:134px" %)
90 +|Logic count error|The number of BMS Logic devices differs from the required value| | |Yes|Yes|(% style="width:142px" %)Logic count|LOG|(% style="width:142px" %) |(% style="width:134px" %)
91 +|Logic offline (Cell monitor offline)|BMS Main devices: at least one of the Logic devices is offline.
92 +BMS Mini devices: connection with cell monitor is lost.|•|Yes|Yes|Yes|(% style="width:142px" %)Logic offline|LOF|(% style="width:142px" %) |(% style="width:134px" %)
93 +|Low temperature (CH)|Temperature is too low for charging;| |Yes|Yes|Yes|(% style="width:142px" %)Low temp. CH|LTC|(% style="width:142px" %) |(% style="width:134px" %)
94 +|Low temperature (DCH)|Temperature is too low for discharging;| |Yes|Yes|Yes|(% style="width:142px" %)Low temp. DCH|LTD|(% style="width:142px" %) |(% style="width:134px" %)
80 80  |Main contactor feedback error|The control signal for the main contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)Main cont. feed.|MCF|(% style="width:142px" %) |(% style="width:134px" %)
81 81  |Mount error|SD card cannot be mounted| |Yes|Yes|Yes|(% style="width:142px" %)Mount error|MNT|(% style="width:142px" %) |(% style="width:134px" %)
82 82  |Need acknowledge|There is an unacknowledged error in error journal| |Yes|Yes|Yes|(% style="width:142px" %)Need ACK|ACK|(% style="width:142px" %) |(% style="width:134px" %)
98 +|No temperature sensors|The device has no temperature sensors connected|•|Yes|Yes|Yes|(% style="width:142px" %)No temp. sens.|NTS|(% style="width:142px" %) |(% style="width:134px" %)
83 83  |Overcurrent|The battery current is too high| |Yes|Yes|Yes|(% style="width:142px" %)Overcurrent|OC|(% style="width:142px" %) |(% style="width:134px" %)
100 +|Overvoltage|Voltage of any cell is too high| |Yes|Yes|Yes|(% style="width:142px" %)Overvoltage|OV|(% style="width:142px" %) |(% style="width:134px" %)
84 84  |PCH contactor feedback error|The control signal for the precharging contactor and the contactor feedback differ|•| |Yes|Yes|(% style="width:142px" %)PCH cont. feed.|PCF|(% style="width:142px" %) |(% style="width:134px" %)
85 85  |Power fault|External devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices|•| | |Yes|(% style="width:142px" %)Power fault|PF|(% style="width:142px" %) |(% style="width:134px" %)
86 86  |Power switch error|Short circuit in contactor coil control circuit or power switch overheating|•| | |Yes|(% style="width:142px" %)PSW error|PSE|(% style="width:142px" %) |(% style="width:134px" %)
87 87  |Precharge error|Capacitive load pre-charge process did not end during the estimated time| |Yes|Yes|Yes|(% style="width:142px" %)Precharge error|PE|(% style="width:142px" %) |(% style="width:134px" %)
105 +|Settings error|Wrong checksum of the device settings| | |Yes| |(% style="width:142px" %)Settings err.|SET|(% style="width:142px" %) |(% style="width:134px" %)
88 88  |Short circuit|Flowing high battery currents during a long time| |Yes|Yes|Yes|(% style="width:142px" %)Short circuit|SHC|(% style="width:142px" %) |(% style="width:134px" %)
107 +|Shunt error|Internal error of the shunt current sensor|•|Yes|Yes|Yes|(% style="width:142px" %)Shunt error|SHE|(% style="width:142px" %) |(% style="width:134px" %)
108 +|Shunt offline|Connection with the shunt current sensor is lost|•|Yes|Yes|Yes|(% style="width:142px" %)Shunt offline|SHO|(% style="width:142px" %) |(% style="width:134px" %)
109 +|Spirit offline|Connection with the Spirit forklift is lost| |Yes|Yes|Yes|(% style="width:142px" %)Spirit offline|SPI|(% style="width:142px" %) |(% style="width:134px" %)
89 89  |Stuck contactor|Some contactor got stuck|•|Yes|Yes|Yes|(% style="width:142px" %)Stuck contactor|STC|(% style="width:142px" %) |(% style="width:134px" %)
111 +|Temperature sensor is shorted|Some temperature sensors are shorted|•|Yes|Yes|Yes|(% style="width:142px" %)Shorted temp.|TSS|(% style="width:142px" %) |(% style="width:134px" %)
112 +|Unallowable charging|Charging the battery through the discharging contactor| |Yes|Yes|Yes|(% style="width:142px" %)Unallowable CH|UCH|(% style="width:142px" %) |(% style="width:134px" %)
113 +|Undervoltage|Voltage of any cell is too low| |Yes|Yes|Yes|(% style="width:142px" %)Undervoltage|UV|(% style="width:142px" %) |(% style="width:134px" %)
90 90  |Water|There is water in the battery enclosure|•| |Yes|Yes|(% style="width:142px" %)Water|WHU|(% style="width:142px" %) |(% style="width:134px" %)
91 91  |WDT reset|Watchdog timer reset the device|•|Yes|Yes|Yes|(% style="width:142px" %)WDT reset|WDT|(% style="width:142px" %) |(% style="width:134px" %)
92 92