Last modified by Admin on 2025/02/21 14:51

From version 26.12
edited by Admin
on 2025/02/04 08:14
Change comment: There is no comment for this version
To version 27.1
edited by Admin
on 2025/02/04 08:19
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -30,70 +30,65 @@
30 30  (% style="width:1277px" %)
31 31  |=(% colspan="1" rowspan="2" style="width: 201px;" %)**Name**|=(% colspan="1" rowspan="2" style="width: 531px;" %)**Description**|=(% colspan="2" rowspan="1" style="width: 255px;" %)**Compability**|=(% colspan="2" rowspan="1" style="width: 140px;" %)BMS Display|=(% colspan="1" rowspan="2" style="width: 140px;" %)**CANopen SDO**|=(% colspan="1" rowspan="2" style="width: 142px;" %)**Modbus**
32 32  |=(% style="width: 94px;" %)**Main X**|=(% style="width: 84px;" %)**Main 3X**|=(% colspan="1" style="width: 137px;" %)Short name|=(% style="width: 137px;" %)Abbreviation
33 -|Charging current present|Signal showing the presence of the charging current|Yes|Yes|(% style="width:140px" %)CH curr. present|CCP|(% style="width:140px" %) |(% style="width:142px" %)
33 +|Charging current present|Signal showing the presence of the charging current|Yes*|Yes*|(% style="width:140px" %)CH curr. present|CCP|(% style="width:140px" %) |(% style="width:142px" %)
34 34  |Charging|Command to control the charging contactor|Yes|Yes|(% style="width:140px" %)Charging|CH|(% style="width:140px" %) |(% style="width:142px" %)
35 35  |Charging/Discharging|Command to control the charging/discharging contactor|Yes|Yes|(% style="width:140px" %)Charg./Discharg.|C/D|(% style="width:140px" %) |(% style="width:142px" %)
36 36  |Coolant pump|Command to control the coolant pump|Yes|Yes|(% style="width:140px" %)Coolant pump|CP|(% style="width:140px" %) |(% style="width:142px" %)
37 37  |Cooler|Command to control the cooler|Yes|Yes|(% style="width:140px" %)Cooler|COO|(% style="width:140px" %) |(% style="width:142px" %)
38 -|Discharging current present|Signal showing the presence of the discharging current|Yes|Yes|(% style="width:140px" %)DCH cur. present|DCP|(% style="width:140px" %) |(% style="width:142px" %)
38 +|Discharging current present|Signal showing the presence of the discharging current|Yes*|Yes*|(% style="width:140px" %)DCH cur. present|DCP|(% style="width:140px" %) |(% style="width:142px" %)
39 39  |Discharging|Command to control the discharging contactor|Yes|Yes|(% style="width:140px" %)Discharging|DCH|(% style="width:140px" %) |(% style="width:142px" %)
40 -|Fuse 1 (modules)|ORed internal signals "Fuse 1" from all battery modules|Yes|Yes|(% style="width:140px" %)Fuse 1 (mod.)|F1M|(% style="width:140px" %) |(% style="width:142px" %)
41 -|Fuse 2 (modules)|ORed internal signals "Fuse 2" from all battery modules|Yes|Yes|(% style="width:140px" %)Fuse 2 (mod.)|F2M|(% style="width:140px" %) |(% style="width:142px" %)
42 -|Fuse 3 (modules)|ORed internal signals "Fuse 3" from all battery modules|Yes|Yes|(% style="width:140px" %)Fuse 3 (mod.)|F3M|(% style="width:140px" %) |(% style="width:142px" %)
40 +|Fuse 1 (modules)|ORed internal signals "Fuse 1" from all battery modules|Yes*|Yes*|(% style="width:140px" %)Fuse 1 (mod.)|F1M|(% style="width:140px" %) |(% style="width:142px" %)
41 +|Fuse 2 (modules)|ORed internal signals "Fuse 2" from all battery modules|Yes*|Yes*|(% style="width:140px" %)Fuse 2 (mod.)|F2M|(% style="width:140px" %) |(% style="width:142px" %)
42 +|Fuse 3 (modules)|ORed internal signals "Fuse 3" from all battery modules|Yes*|Yes*|(% style="width:140px" %)Fuse 3 (mod.)|F3M|(% style="width:140px" %) |(% style="width:142px" %)
43 43  |General error (modules)|ORed internal signals "General error" from all battery modules|Yes|Yes|(% style="width:140px" %)Gen.error (mod.)|GEM|(% style="width:140px" %) |(% style="width:142px" %)
44 44  |Heater|Command to control the heater|Yes|Yes|(% style="width:140px" %)Heater|HEA|(% style="width:140px" %) |(% style="width:142px" %)
45 -|Init|Signal showing that the device is in the initialization phase|Yes|Yes|(% style="width:140px" %)Init|INI|(% style="width:140px" %) |(% style="width:142px" %)
46 -|Interlock (modules)|ORed internal signals "Interlock" from all battery modules|Yes|Yes|(% style="width:140px" %)Interlock (mod.)|INM|(% style="width:140px" %) |(% style="width:142px" %)
45 +|Init|Signal showing that the device is in the initialization phase|Yes*|Yes*|(% style="width:140px" %)Init|INI|(% style="width:140px" %) |(% style="width:142px" %)
46 +|Interlock (modules)|ORed internal signals "Interlock" from all battery modules|Yes*|Yes*|(% style="width:140px" %)Interlock (mod.)|INM|(% style="width:140px" %) |(% style="width:142px" %)
47 47  |Main contactor|Command to control the main contactor|Yes|Yes|(% style="width:140px" %)Main contactor|MCO|(% style="width:140px" %) |(% style="width:142px" %)
48 48  |Precharging|Command to control the precharging contactor|Yes|Yes|(% style="width:140px" %)Precharging|PCH|(% style="width:140px" %) |(% style="width:142px" %)
49 -|Service reset|Command to restart the device|Yes|Yes|(% style="width:140px" %)Service reset|SR|(% style="width:140px" %) |(% style="width:142px" %)
49 +|Service reset|Command to restart the device|Yes*|Yes*|(% style="width:140px" %)Service reset|SR|(% style="width:140px" %) |(% style="width:142px" %)
50 50  
51 51  (% class="wikigeneratedid" %)
52 -~* Assignable to relay only
52 +* Cannot be assigned to discrete outputs or relays.
53 53  
54 -(% class="wikigeneratedid" %)
55 -~** Assignable to discrete input only
56 56  
57 -(% class="wikigeneratedid" %)
58 -~*~*~* Cannot be assigned to discrete output or relay.
59 -
60 60  == Errors ==
61 61  
62 62  (% style="width:1279px" %)
63 -|(% colspan="1" rowspan="2" style="width:196px" %)**Name **|(% colspan="1" rowspan="2" style="width:443px" %)**Description**|(% colspan="1" rowspan="2" style="width:67px" %)**Is a Critical error?**|(% colspan="2" rowspan="1" style="width:248px" %)**Compability**|(% colspan="2" rowspan="1" style="width:142px" %)**BMS Display**|(% colspan="1" rowspan="2" style="width:142px" %)**CANopen SDO**|(% colspan="1" rowspan="2" style="width:134px" %)**Modbus**
64 -|=(% style="width: 93px;" %)**Main X**|=(% style="width: 80px;" %)**Main 3X**|=(% colspan="1" style="width: 137px;" %)Short name|=(% style="width: 137px;" %)Abbreviation
65 -|ADC error|Error of the ADC that measures the battery current|•|Yes|Yes|(% style="width:142px" %)ADC error|ADC|(% style="width:142px" %) |(% style="width:134px" %)
66 -|Battery cover error|Battery cover is open||Yes|Yes|(% style="width:142px" %)Battery cover|BCE|(% style="width:142px" %) |(% style="width:134px" %)
67 -|CH contactor feedback error|The control signal for the charging contactor and the contactor feedback differ|| |Yes|(% style="width:142px" %)CH cont. feed.|CCF|(% style="width:142px" %) |(% style="width:134px" %)
68 -|CH/DCH contactor feedback error|The control signal for the charging/discharging contactor and the contactor feedback differ|| |Yes|(% style="width:142px" %)C/D cont. feed.|CDF|(% style="width:142px" %) |(% style="width:134px" %)
69 -|Charging current unbalance| | | | |(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
70 -|Critical error|Critical system error, the BMS is damaged| |Yes|Yes|(% style="width:142px" %)Critical error|CER|(% style="width:142px" %) |(% style="width:134px" %)
71 -|Current limit error|Charging or discharging current is more than the limit calculated by Charge map or Discharge map| |Yes|Yes|(% style="width:142px" %)Cur. limit error|CLE|(% style="width:142px" %) |(% style="width:134px" %)
72 -|Current sensor error|Error in the current sensor circuit|•|Yes|Yes|(% style="width:142px" %)Current sensor|CSE|(% style="width:142px" %) |(% style="width:134px" %)
73 -|Current unbalance (CH)| | | | |(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
74 -|Current unbalance (DCH)| | | | |(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
75 -|DCH contactor feedback error|The control signal for the discharging contactor and the contactor feedback differ|| |Yes|(% style="width:142px" %)DCH cont. feed.|DCF|(% style="width:142px" %) |(% style="width:134px" %)
76 -|Discharging current unbalance| | | | |(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
77 -|FS error|SD card read/write error| |Yes|Yes|(% style="width:142px" %)FS error|FSE|(% style="width:142px" %) |(% style="width:134px" %)
78 -|High contactor temperature|Temperature of a contactor is too high| |Yes|Yes|(% style="width:142px" %)Hi. cont. temp.|HCT|(% style="width:142px" %) |(% style="width:134px" %)
79 -|High humidity|Increased humidity inside the battery| | |Yes|(% style="width:142px" %)High humidity|HHU|(% style="width:142px" %) |(% style="width:134px" %)
80 -|High voltage fault|Failure of high voltage measuring circuits|| |Yes|(% style="width:142px" %)HV fault|HVF|(% style="width:142px" %) |(% style="width:134px" %)
81 -|HVIL error|Breakage of high-voltage interlock current loop|| |Yes|(% style="width:142px" %)HVIL error|HE|(% style="width:142px" %) |(% style="width:134px" %)
82 -|Insulation fault|Insulation resistance is too low||Yes|Yes|(% style="width:142px" %)Insulation fault|INF|(% style="width:142px" %) |(% style="width:134px" %)
83 -|Module offline|Some of battery modules is offline||Yes|Yes|(% style="width:142px" %)Logic offline|LOF|(% style="width:142px" %) |(% style="width:134px" %)
84 -|Main contactor feedback error|The control signal for the main contactor and the contactor feedback differ|| |Yes|(% style="width:142px" %)Main cont. feed.|MCF|(% style="width:142px" %) |(% style="width:134px" %)
85 -|Mount error|SD card cannot be mounted| |Yes|Yes|(% style="width:142px" %)Mount error|MNT|(% style="width:142px" %) |(% style="width:134px" %)
86 -|Need acknowledge|There is an unacknowledged error in error journal| |Yes|Yes|(% style="width:142px" %)Need ACK|ACK|(% style="width:142px" %) |(% style="width:134px" %)
87 -|Overcurrent|The battery current is too high| |Yes|Yes|(% style="width:142px" %)Overcurrent|OC|(% style="width:142px" %) |(% style="width:134px" %)
88 -|PCH contactor feedback error|The control signal for the precharging contactor and the contactor feedback differ|| |Yes|(% style="width:142px" %)PCH cont. feed.|PCF|(% style="width:142px" %) |(% style="width:134px" %)
89 -|Power fault|External devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices|| |Yes|(% style="width:142px" %)Power fault|PF|(% style="width:142px" %) |(% style="width:134px" %)
90 -|Power switch error|Short circuit in contactor coil control circuit or power switch overheating|| |Yes|(% style="width:142px" %)PSW error|PSE|(% style="width:142px" %) |(% style="width:134px" %)
91 -|Precharge error|Capacitive load pre-charge process did not end during the estimated time| |Yes|Yes|(% style="width:142px" %)Precharge error|PE|(% style="width:142px" %) |(% style="width:134px" %)
92 -|Short circuit|Flowing high battery currents during a long time| |Yes|Yes|(% style="width:142px" %)Short circuit|SHC|(% style="width:142px" %) |(% style="width:134px" %)
93 -|Stuck contactor|Some contactor got stuck||Yes|Yes|(% style="width:142px" %)Stuck contactor|STC|(% style="width:142px" %) |(% style="width:134px" %)
94 -|Voltage unbalance (CH)| | | | |(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
95 -|Voltage unbalance (DCH)| | | | |(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
96 -|Water|There is water in the battery enclosure|| |Yes|(% style="width:142px" %)Water|WHU|(% style="width:142px" %) |(% style="width:134px" %)
97 -|WDT reset|Watchdog timer reset the device||Yes|Yes|(% style="width:142px" %)WDT reset|WDT|(% style="width:142px" %) |(% style="width:134px" %)
58 +|(% colspan="1" rowspan="2" style="width:196px" %)**Name **|(% colspan="1" rowspan="2" style="width:443px" %)**Description**|(% colspan="1" rowspan="2" style="width:87px" %)**Is a critical error?**|(% colspan="2" rowspan="1" style="width:179px" %)**Compability**|(% colspan="2" rowspan="1" style="width:142px" %)**BMS Display**|(% colspan="1" rowspan="2" style="width:142px" %)**CANopen SDO**|(% colspan="1" rowspan="2" style="width:134px" %)**Modbus**
59 +|=(% style="width: 76px;" %)**Main X**|=(% style="width: 81px;" %)**Main 3X**|=(% colspan="1" style="width: 137px;" %)Short name|=(% style="width: 137px;" %)Abbreviation
60 +|ADC error|Error of the ADC that measures the battery current|(% style="width:87px" %)Yes|(% style="width:76px" %) |(% style="width:81px" %)Yes|(% style="width:142px" %)ADC error|ADC|(% style="width:142px" %) |(% style="width:134px" %)
61 +|Battery cover error|Battery cover is open|(% style="width:87px" %)Yes|(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Battery cover|BCE|(% style="width:142px" %) |(% style="width:134px" %)
62 +|CH contactor feedback error|The control signal for the charging contactor and the contactor feedback differ|(% style="width:87px" %)Yes|(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)CH cont. feed.|CCF|(% style="width:142px" %) |(% style="width:134px" %)
63 +|CH/DCH contactor feedback error|The control signal for the charging/discharging contactor and the contactor feedback differ|(% style="width:87px" %)Yes|(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)C/D cont. feed.|CDF|(% style="width:142px" %) |(% style="width:134px" %)
64 +|Charging current unbalance| |(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
65 +|Critical error|Critical system error, the BMS is damaged|(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Critical error|CER|(% style="width:142px" %) |(% style="width:134px" %)
66 +|Current limit error|Charging or discharging current is more than the limit calculated by Charge map or Discharge map|(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Cur. limit error|CLE|(% style="width:142px" %) |(% style="width:134px" %)
67 +|Current sensor error|Error in the current sensor circuit|(% style="width:87px" %)Yes|(% style="width:76px" %) |(% style="width:81px" %)Yes|(% style="width:142px" %)Current sensor|CSE|(% style="width:142px" %) |(% style="width:134px" %)
68 +|Current unbalance (CH)| |(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
69 +|Current unbalance (DCH)| |(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
70 +|DCH contactor feedback error|The control signal for the discharging contactor and the contactor feedback differ|(% style="width:87px" %)Yes|(% style="width:76px" %) |(% style="width:81px" %)Yes|(% style="width:142px" %)DCH cont. feed.|DCF|(% style="width:142px" %) |(% style="width:134px" %)
71 +|Discharging current unbalance| |(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
72 +|FS error|SD card read/write error|(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)FS error|FSE|(% style="width:142px" %) |(% style="width:134px" %)
73 +|High contactor temperature|Temperature of a contactor is too high|(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Hi. cont. temp.|HCT|(% style="width:142px" %) |(% style="width:134px" %)
74 +|High humidity|Increased humidity inside the battery|(% style="width:87px" %) |(% style="width:76px" %) |(% style="width:81px" %)Yes|(% style="width:142px" %)High humidity|HHU|(% style="width:142px" %) |(% style="width:134px" %)
75 +|High voltage fault|Failure of high voltage measuring circuits|(% style="width:87px" %)Yes|(% style="width:76px" %) |(% style="width:81px" %)Yes|(% style="width:142px" %)HV fault|HVF|(% style="width:142px" %) |(% style="width:134px" %)
76 +|HVIL error|Breakage of high-voltage interlock current loop|(% style="width:87px" %)Yes|(% style="width:76px" %) |(% style="width:81px" %)Yes|(% style="width:142px" %)HVIL error|HE|(% style="width:142px" %) |(% style="width:134px" %)
77 +|Insulation fault|Insulation resistance is too low|(% style="width:87px" %)Yes|(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Insulation fault|INF|(% style="width:142px" %) |(% style="width:134px" %)
78 +|Module offline|Some of battery modules is offline|(% style="width:87px" %)Yes|(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Logic offline|LOF|(% style="width:142px" %) |(% style="width:134px" %)
79 +|Main contactor feedback error|The control signal for the main contactor and the contactor feedback differ|(% style="width:87px" %)Yes|(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Main cont. feed.|MCF|(% style="width:142px" %) |(% style="width:134px" %)
80 +|Mount error|SD card cannot be mounted|(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Mount error|MNT|(% style="width:142px" %) |(% style="width:134px" %)
81 +|Need acknowledge|There is an unacknowledged error in error journal|(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Need ACK|ACK|(% style="width:142px" %) |(% style="width:134px" %)
82 +|Overcurrent|The battery current is too high|(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Overcurrent|OC|(% style="width:142px" %) |(% style="width:134px" %)
83 +|PCH contactor feedback error|The control signal for the precharging contactor and the contactor feedback differ|(% style="width:87px" %)Yes|(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)PCH cont. feed.|PCF|(% style="width:142px" %) |(% style="width:134px" %)
84 +|Power fault|External devices power supply error: current sensors, HVIL, BMS Logic or CAN2 (int) bus powered devices|(% style="width:87px" %)Yes|(% style="width:76px" %) |(% style="width:81px" %)Yes|(% style="width:142px" %)Power fault|PF|(% style="width:142px" %) |(% style="width:134px" %)
85 +|Power switch error|Short circuit in contactor coil control circuit or power switch overheating|(% style="width:87px" %)Yes|(% style="width:76px" %) |(% style="width:81px" %)Yes|(% style="width:142px" %)PSW error|PSE|(% style="width:142px" %) |(% style="width:134px" %)
86 +|Precharge error|Capacitive load pre-charge process did not end during the estimated time|(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Precharge error|PE|(% style="width:142px" %) |(% style="width:134px" %)
87 +|Short circuit|Flowing high battery currents during a long time|(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Short circuit|SHC|(% style="width:142px" %) |(% style="width:134px" %)
88 +|Stuck contactor|Some contactor got stuck|(% style="width:87px" %)Yes|(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)Stuck contactor|STC|(% style="width:142px" %) |(% style="width:134px" %)
89 +|Voltage unbalance (CH)| |(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
90 +|Voltage unbalance (DCH)| |(% style="width:87px" %) |(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %) | |(% style="width:142px" %) |(% style="width:134px" %)
91 +|Water|There is water in the battery enclosure|(% style="width:87px" %)Yes|(% style="width:76px" %) |(% style="width:81px" %)Yes|(% style="width:142px" %)Water|WHU|(% style="width:142px" %) |(% style="width:134px" %)
92 +|WDT reset|Watchdog timer reset the device|(% style="width:87px" %)Yes|(% style="width:76px" %)Yes|(% style="width:81px" %)Yes|(% style="width:142px" %)WDT reset|WDT|(% style="width:142px" %) |(% style="width:134px" %)
98 98  
99 99  ~* The signal can be assigned to discrete outputs and relays.