... ... @@ -16,13 +16,15 @@
16 16  |Discharge request|(% style="width:500px" %)Request to close the discharging contactor|(% style="width:92px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Discharge req.|DRE|(% style="width:137px" %) |(% style="width:137px" %)
17 17  |Insulation status|(% style="width:500px" %)Signal from an insulation monitoring device|(% style="width:92px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Insul. status|INS|(% style="width:137px" %) |(% style="width:137px" %)
18 18  |Interlock|(% style="width:500px" %)Signal from the interlock loop|(% style="width:92px" %) |(% style="width:78px" %)Yes|(% style="width:137px" %)Interlock|INT|(% style="width:137px" %) |(% style="width:137px" %)
19 -|Join to charge|(% style="width:500px" %)Request to join the battery modules for charging|(% style="width:92px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Join to charge|JTC|(% style="width:137px" %) |(% style="width:137px" %)
20 -|Join to discharge|(% style="width:500px" %)Request to join the battery modules for discharging|(% style="width:92px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Join to dischar.|JTD|(% style="width:137px" %) |(% style="width:137px" %)
19 +|Join to charge|(% style="width:500px" %)Request to join the battery modules for charging|(% style="width:92px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) | |(% style="width:137px" %) |(% style="width:137px" %)
20 +|Join to discharge|(% style="width:500px" %)Request to join the battery modules for discharging|(% style="width:92px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) | |(% style="width:137px" %) |(% style="width:137px" %)
21 21  |Main contactor feedback|(% style="width:500px" %)Signal from the main contactor feedback loop|(% style="width:92px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Main cont. feed.|MCF|(% style="width:137px" %) |(% style="width:137px" %)
22 22  |PCH contactor feedback|(% style="width:500px" %)Signal from the precharging contactor feedback loop|(% style="width:92px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)PCH cont. feed.|PCF|(% style="width:137px" %) |(% style="width:137px" %)
23 23  |Power down request|(% style="width:500px" %)Request to power down the device|(% style="width:92px" %) |(% style="width:78px" %)Yes|(% style="width:137px" %)Power down req.|PDN|(% style="width:137px" %) |(% style="width:137px" %)
24 24  |Precharge request|(% style="width:500px" %)Request to close the precharging contactor|(% style="width:92px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Precharge req.|PRE|(% style="width:137px" %) |(% style="width:137px" %)
25 25  
26 +(% class="wikigeneratedid" %)
27 +~* Contactor feedback signals in BMS Mini / BMS Mini S are connected to [[X1 header>>doc:Battery management systems.BMS Mini S.2\. Installation and connection.WebHome||anchor="HHeaders"]] and configured in "Signals → MOSFETs → Contactors feedback" section.