Last modified by Admin on 2025/02/21 14:51

From version 17.6
edited by Admin
on 2025/01/31 09:24
Change comment: There is no comment for this version
To version 17.16
edited by Admin
on 2025/01/31 09:27
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -53,16 +53,16 @@
53 53  |Discharging (AUX)|Command to control the auxiliary discharging contactor|Yes|Yes|Yes|(% style="width:140px" %) |AUX|(% style="width:140px" %) |(% style="width:142px" %)
54 54  |Discharging current present|Signal showing the presence of the discharging current|Yes|Yes~*~*|Yes|(% style="width:140px" %) |DCP|(% style="width:140px" %) |(% style="width:142px" %)
55 55  |Discharging|Command to control the discharging contactor|Yes|Yes*|Yes|(% style="width:140px" %) |DCH|(% style="width:140px" %) |(% style="width:142px" %)
56 -|External 1|Command to control an external shc|Yes|Yes|Yes|(% style="width:140px" %) |EX1|(% style="width:140px" %) |(% style="width:142px" %)
57 -|Heater (AUX)| | |Yes| |(% style="width:140px" %) |HA|(% style="width:140px" %) |(% style="width:142px" %)
58 -|Heater|a command to turn on a heater;|Yes|Yes|Yes|(% style="width:140px" %) |HEA|(% style="width:140px" %) |(% style="width:142px" %)
59 -|High charging current|charging current is high;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |HCC|(% style="width:140px" %) |(% style="width:142px" %)
60 -|Init| |Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |INI|(% style="width:140px" %) |(% style="width:142px" %)
61 -|Low SOC|a signal corresponding the low SOC of the battery;|Yes|Yes|Yes|(% style="width:140px" %) |LOS|(% style="width:140px" %) |(% style="width:142px" %)
62 -|Main contactor|state of the main contactor;|Yes|Yes*|Yes|(% style="width:140px" %) |MCO|(% style="width:140px" %) |(% style="width:142px" %)
63 -|Power down ACK|an acknowledgement of BMS power down. Acknowledgement is outputted when the charge and discharge contactors have been opened on power down request;|Yes|Yes~*~*|Yes|(% style="width:140px" %) |PDA|(% style="width:140px" %) |(% style="width:142px" %)
64 -|Power up|an indication of BMS power status;|Yes|Yes|Yes|(% style="width:140px" %) |PUP|(% style="width:140px" %) |(% style="width:142px" %)
65 -|Precharging|state of the precharging contactor;|Yes|Yes|Yes|(% style="width:140px" %) |PRE|(% style="width:140px" %) |(% style="width:142px" %)
56 +|External 1|Command to control an external scheme|Yes|Yes|Yes|(% style="width:140px" %) |EX1|(% style="width:140px" %) |(% style="width:142px" %)
57 +|Heater (AUX)|Command to control the auxiliary heater| |Yes| |(% style="width:140px" %) |HA|(% style="width:140px" %) |(% style="width:142px" %)
58 +|Heater|Command to control the heater|Yes|Yes|Yes|(% style="width:140px" %) |HEA|(% style="width:140px" %) |(% style="width:142px" %)
59 +|High charging current|Signal indicating that the charging current is high|Yes|Yes~*~*|Yes|(% style="width:140px" %) |HCC|(% style="width:140px" %) |(% style="width:142px" %)
60 +|Init|Signal showing that the device is in the initialization phase|Yes~*~**|Yes~*~**|Yes~*~**|(% style="width:140px" %) |INI|(% style="width:140px" %) |(% style="width:142px" %)
61 +|Low SOC|Signal indicatiing that the battery has low SOC|Yes|Yes|Yes|(% style="width:140px" %) |LOS|(% style="width:140px" %) |(% style="width:142px" %)
62 +|Main contactor|Command to control the main contactor|Yes|Yes*|Yes|(% style="width:140px" %) |MCO|(% style="width:140px" %) |(% style="width:142px" %)
63 +|Power down ACK|Command that acknowledges the BMS power down. Acknowledgement is outputted when the charge and discharge contactors have been opened on the power down request|Yes|Yes~*~*|Yes|(% style="width:140px" %) |PDA|(% style="width:140px" %) |(% style="width:142px" %)
64 +|Power up|Signal indicating the BMS power status|Yes|Yes|Yes|(% style="width:140px" %) |PUP|(% style="width:140px" %) |(% style="width:142px" %)
65 +|Precharging|Command to control the precharging contactor|Yes|Yes|Yes|(% style="width:140px" %) |PRE|(% style="width:140px" %) |(% style="width:142px" %)
66 66  |Ready to charge|the battery is ready to be charged;|Yes|Yes|Yes|(% style="width:140px" %) |RTC|(% style="width:140px" %) |(% style="width:142px" %)
67 67  |Ready to discharge|the battery is ready to be discharged;|Yes|Yes|Yes|(% style="width:140px" %) |RTD|(% style="width:140px" %) |(% style="width:142px" %)
68 68  |Service reset| |Yes~*~**| |Yes~*~**|(% style="width:140px" %) |SR|(% style="width:140px" %) |(% style="width:142px" %)