1 1  (% data-numbered-headings-start="1" style="--numbered-headings-start: 0;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 2  = Signals, states and errors =
3 3  
4 -== Input signals ==
4 +== List of input signals ==
5 5  
6 -Below is the list of input signals that can be assigned to discrete inputs of the BMS controller.
6 +Here is the list of input signals that can be assigned to discrete inputs of BMS controller.
7 7  
8 8  (% style="width:1278px" %)
9 9  |=(% colspan="1" rowspan="2" style="width: 198px;" %)**Name**|=(% colspan="1" rowspan="2" style="width: 500px;" %)**Description**|=(% colspan="3" rowspan="1" style="width: 243px;" %)**Compability**|=(% colspan="2" rowspan="1" style="width: 137px;" %)BMS DIsplay|=(% colspan="1" rowspan="2" style="width: 137px;" %)**CANopen SDO**|=(% colspan="1" rowspan="2" style="width: 137px;" %)**Modbus**
... ... @@ -25,18 +25,18 @@
25 25  |Inhibit charging|(% style="width:500px" %)Command to open the charging contactor|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Inhibit charg.|ICH|(% style="width:137px" %) |(% style="width:137px" %)
26 26  |Inhibit discharging|(% style="width:500px" %)Command to open the discharging contactor|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Inhibit disch.|IDC|(% style="width:137px" %) |(% style="width:137px" %)
27 27  |Insulation status|(% style="width:500px" %)Signal from an insulation monitoring device|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Insul. status|INS|(% style="width:137px" %) |(% style="width:137px" %)
28 -|Interlock|(% style="width:500px" %)Signal from the interlock loop|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Interlock|INT|(% style="width:137px" %) |(% style="width:137px" %)
29 -|Main contactor feedback|(% style="width:500px" %)Signal from the main contactor feedback loop|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Main cont. feed.|MCF|(% style="width:137px" %) |(% style="width:137px" %)
30 -|PCH contactor feedback|(% style="width:500px" %)Signal from the precharging contactor feedback loop|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)PCH cont. feed.|PCF|(% style="width:137px" %) |(% style="width:137px" %)
31 -|Power up/down request|(% style="width:500px" %)Request to power down the device|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Power down req.|PDN|(% style="width:137px" %) |(% style="width:137px" %)
32 -|Precharge request|(% style="width:500px" %)Request to close the precharging contactor|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Precharge req.|PRE|(% style="width:137px" %) |(% style="width:137px" %)
28 +|Interlock|(% style="width:500px" %)Signal from the interlock loop|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %)Interlock| |(% style="width:137px" %) |(% style="width:137px" %)
29 +|Main contactor feedback|(% style="width:500px" %)Signal from the main contactor feedback loop|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |MCF|(% style="width:137px" %) |(% style="width:137px" %)
30 +|PCH contactor feedback|(% style="width:500px" %)Signal from the precharging contactor feedback loop|(% style="width:92px" %)Yes*|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |PCF|(% style="width:137px" %) |(% style="width:137px" %)
31 +|Power up/down request|(% style="width:500px" %)Request to power down the device|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |PDN|(% style="width:137px" %) |(% style="width:137px" %)
32 +|Precharge request|(% style="width:500px" %)Request to close the precharging contactor|(% style="width:92px" %)Yes|(% style="width:73px" %)Yes|(% style="width:78px" %)Yes|(% style="width:137px" %) |PRE|(% style="width:137px" %) |(% style="width:137px" %)
33 33  
34 34  (% class="wikigeneratedid" %)
35 35  ~* Contactor feedback signals in BMS Mini / BMS Mini S are connected to [[X1 header>>doc:Battery management systems.BMS Mini S.2\. Installation and connection.WebHome||anchor="HHeaders"]] and configured in "Signals → MOSFETs → Contactors feedback" section.
36 36  
37 -== Internal signals ==
37 +== List of internal states ==
38 38  
39 -Below is the list of internal BMS signals. The signals marked with bold text can be assigned to discrete outputs arelays.
39 +Here is the list of control internal states. Signals marked with bold text can be assigned to discrete output or relay.
40 40  
41 41  (% style="width:1277px" %)
42 42  |=(% colspan="1" rowspan="2" style="width: 201px;" %)**Name**|=(% rowspan="2" style="width: 55px;" %)**Abbr.**|=(% colspan="1" rowspan="2" style="width: 531px;" %)**Description**|=(% colspan="3" rowspan="1" style="width: 255px;" %)**Compability**|=(% colspan="1" rowspan="2" style="width: 140px;" %)**CANopen SDO**|=(% colspan="1" rowspan="2" style="width: 142px;" %)**Modbus**