Changes for page 2. Strings controllers: signals and errors
Last modified by Admin on 2025/02/21 14:51
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -94,7 +94,7 @@ 94 94 |CH contactor feedback error|CCF|the control signals for the charging contactor and the contactor feedback differ;|•| |Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %) 95 95 |CH/DCH contactor feedback error|CDF|the control signals for the charging/discharging contactor and the contactor feedback differ;|•| |Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %) 96 96 |Combilift offline|COM|connection with a Combilift forklift is lost;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %) 97 -|Contactor feedback error|CFE|Failure of one of the contactors feedback signal. Which contactor is failed can be found in Signals -> MOSFETs Contactor feedback section of BMS Mini device| |Yes| | |(% style="width:142px" %) |(% style="width:134px" %) 97 +|Contactor feedback error|CFE|Failure of one of the contactors feedback signal. Which contactor is failed can be found in "Signals -> MOSFETs -> Contactor feedback" section of BMS Mini device| |Yes| | |(% style="width:142px" %) |(% style="width:134px" %) 98 98 |Critical error|CER| | |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %) 99 99 |Crown error|CRO|connection with a Crown forklift is lost;| |Yes|Yes|Yes|(% style="width:142px" %) |(% style="width:134px" %) 100 100 |Current limit error|CLE|charging or discharging current is more than limit calculated by Charge map or Discharge map.| |Yes| |Yes|(% style="width:142px" %) |(% style="width:134px" %)